    I have never seen this error before either. Have...

    I have never seen this error before either. Have you sent the error thru your local support channels?

    The tech tools cable did not change. You cable sounds good as you find and start uploading.
    ...
  2. Replies
    16
    Views
    439

    If these are new controllers I would agree you...

    If these are new controllers I would agree you need v6.0. It would be a good idea to load the August Cumulative Patches into FieldAssistant before you upload. They have made driver changes since the...
  3. Replies
    1
    Views
    212

    Do you have the recent patches installed? The...

    Do you have the recent patches installed? The cumulative patch releases for i-Vu also need to be applied to Field Assistant, which will also patch Snap & Equipment Builder if installed.

    Start...
  4. Not sure if it is wise to remove the CCN...

    Not sure if it is wise to remove the CCN ComfortLink Controls and replace with another controller.

    Carrier sells an Open UPC that will convert the CCN controls to BACnet MS/TP. Not sure if you can...
  5. Version 6 and down is accessed with...

    Version 6 and down is accessed with Hyper-Terminal. Version 10 and up is accessed with Trane's Tracker software.
  6. Replies
    6
    Views
    478

    You can find older versions here .......

    You can find older versions here .... http://www.oracle.com/technetwork/java/javase/downloads/java-archive-downloads-javase7-521261.html

    There are version all the way back to v7u1 on this page,...
  7. Thread: Trane VSEE vav

    by Balibe
    Replies
    5
    Views
    305

    +1 .... don't reuse the existing assembly. We...

    +1 .... don't reuse the existing assembly.

    We retrofit a lot of these, they are very common in my area. We are in the process of doing two floors with 60 of these per floor.

    We pull the...
  8. Replies
    3
    Views
    262

    +1 Rover will not configure a BCU. You will...

    +1

    Rover will not configure a BCU. You will not be able to access the BCU with a display by just adding one. They are configured, setup and downloaded to a BCU with Summit.
  9. Replies
    20
    Views
    802

    Check the updates they gave you, the USB...

    Check the updates they gave you, the USB communications update is a driver not included in cumulative update released in August. The driver file should have been “drv_ivuexp_6-00a-023.driver” which...
  10. Replies
    20
    Views
    802

    What version? If v6.0 Standard with the USB...

    What version? If v6.0 Standard with the USB adapter, there is a new driver released in March that resolves communications issues. Controls Bulletin #IOB14003A references the update.
  11. It is a 26.8mb zipped file, if you have access it...

    It is a 26.8mb zipped file, if you have access it is downloadable from hvacpartners.com.
  12. Replies
    1
    Views
    158

    You have mail .......

    You have mail .......
  13. Replies
    4
    Views
    316

    With CCN you broadcast, with Open you will need...

    With CCN you broadcast, with Open you will need to read. Open will broadcast when a Linkage is setup.

    You want System Outdoor Air Temperature, which is found under Properties\Network Points....
  14. Replies
    32
    Views
    1,424

    Your FXWorkbench should be licensed for...

    Your FXWorkbench should be licensed for everything [all drivers/protocols]. I have never had an issue hooking up directly to lon networks with FXWorkbench and a USB Lon adapter.
  15. Replies
    35
    Views
    2,874

    +1 Getting old seeing this guy resurrecting...

    +1

    Getting old seeing this guy resurrecting all these threads that are over a year old .... each with a PDF attachment??
  16. Thread: Orion Controls

    by Balibe
    Replies
    1
    Views
    248

    http://orioncontrols.wattmaster.com/literature-new...

    http://orioncontrols.wattmaster.com/literature-new.html
  17. Replies
    7
    Views
    345

    Johnson Controls also has a wireless system that...

    Johnson Controls also has a wireless system that works well.
  18. I have one jobsite with this same issue, works...

    I have one jobsite with this same issue, works fine on my Verizon hot spot and all hardwired connections but will not connect with the customers AT&T hot spot. I always thought the issue was with...
  19. Replies
    10
    Views
    515

    I did some research with a v4.2 and v6.0. I will...

    I did some research with a v4.2 and v6.0. I will try to make this easy to understand, but there is no formula/logic (decoder ring) that will easily get you the info you want. You will need to have...
  20. Replies
    10
    Views
    515

    So you are looking at the points on the IP side...

    So you are looking at the points on the IP side of the Router and trying to figure out which VAV the BACnet points are assigned to?

    If so I can look at one of my sites on the IP side to see if...
  21. Replies
    10
    Views
    515

    You wil not see the address under network points...

    You wil not see the address under network points with a factory control program. All point address's under the network points tab will be ccn:\\link\point_info, the "link" can be changed to the...
  22. Replies
    3
    Views
    338

    Snap has a programming block for lead/lag under...

    Snap has a programming block for lead/lag under Misc\Proof. It does rotation based on runtime and failsafe if the lead does not proof. It will also generate fail & hand alarms if needed. If you have...
  23. Replies
    6
    Views
    330

    The 4th digit of the model number is the...

    The 4th digit of the model number is the Development Sequence. F = Sixth & G = Seventh. The breakdown is in one of the PDF's I emailed you.
  24. Replies
    6
    Views
    330

    Model Number: SXHFC6040M56C79D6001BELRT8PK Job...

    Model Number: SXHFC6040M56C79D6001BELRT8PK
    Job Name: Concord Park
    Shipped: 10-16-1997

    The original model number breakdown does not show an LCI. The unit documents only go back so far. I found...
  25. Replies
    6
    Views
    330

    From my understanding is the older panels do not...

    From my understanding is the older panels do not support the LCI. I don't know when the change occurs. Not 100% but think you can replace the panel with a newer version that works with an LCI. That...
  26. Replies
    11
    Views
    698

    When you right click the VAV graphic and edit...

    When you right click the VAV graphic and edit UCM, you are in the UCM. You can use Summit to modify the settings. They are live settings in the UCM versus a local saved database.
  27. Replies
    11
    Views
    698

    UCM address of 1 on the dipswitch will be VAV...

    UCM address of 1 on the dipswitch will be VAV address 65 in Tracer. Address 2 will be 66, etc .....

    There should be a sticker inside one of the VAV's showing the dipswitch address scheme ....
  28. Thread: CCN Issue

    by Balibe
    Replies
    10
    Views
    398

    How are you changing the broadcast acknowledger...

    How are you changing the broadcast acknowledger [BA]?

    These are Gen2 VVT?

    Older Gen2 VVT will not talk CCN without a Gateway. Only Gen3 and up will talk CCN.

    If they have a display and 4...
  29. Replies
    7
    Views
    268

    The controller files are separate. The v1.4 you...

    The controller files are separate. The v1.4 you want will only work with FieldLoader v3.3 or v4.2. If you have NSTV and want to use the USB converter you will need FieldLoader v4.2
  30. Thread: FX PCV

    by Balibe
    Replies
    4
    Views
    305

    The issue with 3113 is it has around a 10,000...

    The issue with 3113 is it has around a 10,000 write limit. Not an issue if only used for balancing.
  31. Thread: Carrier Ivu

    by Balibe
    Replies
    11
    Views
    2,127

    Drac is correct, you will need v4.2 tools. The...

    Drac is correct, you will need v4.2 tools. The program was ApplicationBuilder, not EquipmentBuilder. This issue also applies to View Graphics. The tools were shipped with the i-Vu v4.2 if the...
  32. Replies
    7
    Views
    268

    The current version is 1.4. You will need...

    The current version is 1.4. You will need FieldLoader v3.3 or v4.2 and the translator files. If you don't have a physical com port on the computer you will also need Network Service Tool so...
  33. Replies
    1
    Views
    232

    That is a Comfort Controller 1600, you will need...

    That is a Comfort Controller 1600, you will need Network Service Tool V to access it.
  34. Replies
    8
    Views
    387

    Trane Tracker talks Trane Comm3/Comm4 to the RTU....

    Trane Tracker talks Trane Comm3/Comm4 to the RTU. You will not talk to a Carrier Open RTU. Your only option is to add the RTU card to the Tracker panel. This will allow R,G,Y,W to the RTU.
  35. Replies
    3
    Views
    173

    If the chiller has the CH530 controls you will...

    If the chiller has the CH530 controls you will need Trane's chiller software as the Comm Cards need to be added before you will get data.
  36. Thread: Service tool 5

    by Balibe
    Replies
    7
    Views
    628

    These part numbers are for older NST and...

    These part numbers are for older NST and obsolete. For NSTV the part number is 33CNNSTKIT-01.
  37. Thread: ivu 6 ccn

    by Balibe
    Replies
    4
    Views
    344

    That driver is the original fix in IOB14003, I...

    That driver is the original fix in IOB14003, I would apply that driver. Carrier just released a new fix yesterday [03/18/2014] in IOB14003A. It is the same driver but has another step to the...
  38. Replies
    5
    Views
    453

    Which version are you installing? If v2.0 or...

    Which version are you installing? If v2.0 or v2.1, believe you will need to upgrade to v2.2 for Windows 7. There is an v2.2 update .exe on havcpartners.com. If you have an older usb converter at...
  39. Replies
    9
    Views
    793

    According to the picture, your MSTP address is 70...

    According to the picture, your MSTP address is 70 and the baud rate is 19.2k. Did you power cycle the UPC after setting the address and baud rate?

    They are field programmable but should have been...
  40. Replies
    9
    Views
    716

    The OP stated v4.2 in the title, that is CCN so...

    The OP stated v4.2 in the title, that is CCN so SNAP wont work as it for v5.0 & higher. In v4.2, the *.equips just expose the CCN points to I-Vu. ApplicationBuilder is the program used to edit the...
  41. It is a PCT UI bug, I had the same issue and...

    It is a PCT UI bug, I had the same issue and contacted JCI back in November. JCI is aware of this issue. Now that 10.0 is out, it should be resolved. I received v10.0.1 last week and will be testing...
  42. Replies
    6
    Views
    509

    Do you have Windows Restore backing up the...

    Do you have Windows Restore backing up the machine? If so go back a week or two, I resolved this issue before this way. Worth a shot .....
  43. Not sure why Carrier stated this, the bridges...

    Not sure why Carrier stated this, the bridges will not bottleneck traffic or restrict trending if they are working correctly. They basically work like a repeater. I have a lot of i-Vu's with bridges...
  44. Replies
    17
    Views
    942

    The Network Visible will be found on the BACnet...

    The Network Visible will be found on the BACnet Tab, which his access doesn't have. Think he will need installers access to see that tab.
  45. Thread: i-Vu 6.0

    by Balibe
    Replies
    5
    Views
    618

    We have upgraded a few to v6.0, but none of them...

    We have upgraded a few to v6.0, but none of them were on the same IP that would show your issue.

    There are two patches recently issued that fixes over 25 UI issues but doesn't list your issue.
    ...
  46. Replies
    10
    Views
    838

    It also communicates MSTP/N2/ModBus. Have you...

    It also communicates MSTP/N2/ModBus. Have you check the dip switch's on the RTU-Open and verified them for Lon? I have attached the Carrier's RTU-Open Integration Guide, it shows the dip switch...
  47. Replies
    10
    Views
    838

    I have never dealt with the LON option either....

    I have never dealt with the LON option either. Appears the LON Card is good as it responds to the service pin.

    Have you checked the RTUOpen? There are dip switch's that need to be set for the...
  48. Replies
    32
    Views
    4,907

    If you order the part with the number on the...

    If you order the part with the number on the board it will come blank. If you order the board with the model and serial of the equipment it should come programmed for your specific equipment.

    Just...
  49. Replies
    33
    Views
    2,792

    Dapper is correct, even with TGP licensed you can...

    Dapper is correct, even with TGP licensed you can only run it when connected to a MP581. If you to start is in Rover before connecting, you will get the error. I have even attempted to start it...
  50. NSTV works on XP, we have it running on several...

    NSTV works on XP, we have it running on several XP laptops at our office. AFAIK only Windows 8 is an issue with NSTV.

    Sound like you have a defective adapter. As 381 suggested, try the adapter on...
Results 1 to 50 of 528
Page 1 of 11 1 2 3 4
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event