Search:

Type: Posts; User: trippintl0

Page 1 of 20 1 2 3 4

Search: Search took 0.04 seconds.

  1. Replies
    7
    Views
    288

    This would probably be more useful if the DTAV's...

    This would probably be more useful if the DTAV's actually worked.. just sayin...

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  2. Replies
    8
    Views
    220

    Lol as soon as you said "power on light" I...

    Lol as soon as you said "power on light" I pictured the old beverage air with the flickering power light.... sorry I'm of no help with the thermometer though! AL the square thermometers ive seen,...
  3. Replies
    17
    Views
    1,656

    I left about 3 feet of extra wire going to the...

    I left about 3 feet of extra wire going to the control, so yes you can remove the side panel and set it down on the shelf and still have plenty of slack for service.

    Sent from my SAMSUNG-SM-G890A...
  4. Replies
    4
    Views
    211

    She's frozen Sent from my SAMSUNG-SM-G890A...

    She's frozen

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  5. Replies
    6
    Views
    284

    There are 2 heaters to the solid state timer,...

    There are 2 heaters to the solid state timer, make sure they aren't heating during refrigeration cycle.

    If you stop the evap fans, will the coil frost up nicely, TXV throttle down and suction...
  6. Replies
    7
    Views
    221

    Sorry for the misinformation. I'm slacking...

    Sorry for the misinformation. I'm slacking today. The RST45 is 1/2, RST55 is 3/4hp and RST70 is 1hp. I think I need to catch up on my sleep. 😊😊

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  7. Replies
    32
    Views
    923

    My mistake, that was cond unit numbers not evap. ...

    My mistake, that was cond unit numbers not evap. Thanks for catching that!

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  8. Replies
    32
    Views
    923

    Delete

    Delete
  9. Replies
    32
    Views
    923

    Delete

    Delete
  10. Replies
    7
    Views
    221

    Generally a 1hp cond unit uses the RST70. The...

    Generally a 1hp cond unit uses the RST70. The RST45 is usually on 3/4 hp. Not sure about the RST55.

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  11. Replies
    39
    Views
    1,325

    Hate the solder on ones you have to use the...

    Hate the solder on ones you have to use the special piercing Schrader valve. I never use them. Pinch off, real valve, reround, braze over pinch off. Or if I am in a hurry, piercing line taps work...
  12. IT SUCKETH. WE HAVE SPOKEN Sent from my...

    IT SUCKETH. WE HAVE SPOKEN

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  13. Replies
    9
    Views
    264

    Try talking to tech support. There's plenty of...

    Try talking to tech support. There's plenty of other reasons. In my experience, after using data loggers we'd find it wasn't the case at all.

    Imagine this, machine has been off for 2 hours. ...
  14. Replies
    48
    Views
    1,283

    It's a bad practice because in the future, it may...

    It's a bad practice because in the future, it may get restricted . Tech will change txv and it still won't work til he finds the hidden gem in the liquid line. But as I said, it shouldn't cause any...
  15. Replies
    48
    Views
    1,283

    Nylon allthread is preferred for hanging...

    Nylon allthread is preferred for hanging evaporator to prevent sweating in attic space (which will eventually drip down through ceiling panel and make ice droplets on floor)

    Sent from my...
  16. Replies
    48
    Views
    1,283

    I doubt it will cause harm. Sent from my...

    I doubt it will cause harm.

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  17. Replies
    48
    Views
    1,283

    If you forgot to put it in, it's not worth...

    If you forgot to put it in, it's not worth opening system up to install it. Next time get the SBF valve instead of EBS and the strainer is removable for cleaning.

    I wouldn't put it in line...
  18. Replies
    48
    Views
    1,283

    I would leave the strainer out at this point. ...

    I would leave the strainer out at this point.

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  19. Replies
    48
    Views
    1,283

    Just slide the armaflex back (bunch it up) and...

    Just slide the armaflex back (bunch it up) and use tubing cutters to hold armaflex away from weld joint. Braze like normal, cool, and slide insulation back over the joint

    Sent from my...
  20. Replies
    48
    Views
    1,283

    Yes. Sent from my SAMSUNG-SM-G890A using...

    Yes.

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  21. Replies
    48
    Views
    1,283

    Shoot silicone on inside of the sealtite...

    Shoot silicone on inside of the sealtite electrical conduit to prevent air infiltration through the wires and create ice block at defrost timer

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  22. Replies
    48
    Views
    1,283

    Next time flip ptrap around the other way, so the...

    Next time flip ptrap around the other way, so the vertical rise of the trap goes directly into the vertical suction line. You'll do much better to run your lineset, then prior to making the final...
  23. Replies
    7
    Views
    332

    On Dixell if you set IBD to 0 then it will never...

    On Dixell if you set IBD to 0 then it will never defrost.

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  24. I would most certainly not recommend taking blame...

    I would most certainly not recommend taking blame for this. The unit was broken. If it wasn't broken you wouldn't have been working on it. It is not uncommon to do a major repair then have the...
  25. Thread: New install

    by trippintl0
    Replies
    37
    Views
    1,234

    I just wish condensing unit wasn't on edge of...

    I just wish condensing unit wasn't on edge of box. It makes it unnecessarily difficult to wash condenser, you'll be leaning over the edge trying to spray it out, or have to work off the ladder.
    ...
  26. At first I'm thinking, a 1998 compressor died,...

    At first I'm thinking, a 1998 compressor died, you didn't kill it, it was already in hospice care, on life support, it WANTED to be put down.

    But after thinking about it, I suppose the nitro, on a...
  27. Replies
    15
    Views
    553

    Pull condenser fan, buy a gallon of NuBrite and a...

    Pull condenser fan, buy a gallon of NuBrite and a pump up sprayer, foam the s**t out of that condenser, realize that it WAS actually filthy, feel a new motivation to wash out every dang coil you see....
  28. Problem is there is basically no information on...

    Problem is there is basically no information on these. Our wholesaler recommended them, but they are really marketed for minisplit air conditioner that is a fixed installation. Ours leaked at the...
  29. We used them on a refrigerated case that gets...

    We used them on a refrigerated case that gets moved frequently for cleaning, on a 50hp parallel rack, running R22 at +10f SST, mostly mineral oil but some poe oil... Within 6 months pretty much all...
  30. For starters, don't stick the Stat capillary into...

    For starters, don't stick the Stat capillary into the stupid copper tube. Fold it up and shove it right into back of evap. The copper tubes get loose and stop making good contact with fins even if...
  31. Replies
    23
    Views
    875

    Thank you we always appreciate when people post...

    Thank you we always appreciate when people post the resolution!

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  32. Replies
    19
    Views
    853

    Damn ice set em straight Sent from my...

    Damn ice set em straight

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  33. Replies
    69
    Views
    1,732

    I have many stores with 6x30. Doesn't cause any...

    I have many stores with 6x30. Doesn't cause any issues.

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  34. Replies
    23
    Views
    875

    Give us model numbers of condenser, evaporator,...

    Give us model numbers of condenser, evaporator, compressor, pressures, temperatures, and we'll have this thing taken care of

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  35. Replies
    23
    Views
    875

    10 at compressor is actually too low. Need to...

    10 at compressor is actually too low. Need to close txv, minimum of 20 at compressor. The overload on most hermetic compressors just opens. It doesn't draw power. It's just like a thermostat. ...
  36. Replies
    23
    Views
    875

    If you wired the thermostat to kill contactor, it...

    If you wired the thermostat to kill contactor, it won't work. That means you aren't pumping down. Guarantees high amps whenever compressor restarts. Put it back like it was, and if low pressure...
  37. Replies
    23
    Views
    875

    You should also confirm compressor superheat is...

    You should also confirm compressor superheat is within correct range, as high superheat can overheat the compressor.

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  38. Replies
    4
    Views
    423

    keep trying Sent from my SAMSUNG-SM-G890A...

    keep trying

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  39. Replies
    19
    Views
    853

    Now that's a condenser! Sent from my...

    Now that's a condenser!

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  40. Replies
    23
    Views
    875

    Did you replace contactor with compressor Sent...

    Did you replace contactor with compressor

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  41. Replies
    69
    Views
    1,732

    Personally I would have selected an EBFSE-B-C for...

    Personally I would have selected an EBFSE-B-C for that evap, but since your superheat is right on the money it doesn't appear to be an issue.

    Try 6 defrosts per day. Adjust door hardware so...
  42. Replies
    8
    Views
    709

    Great advice Sent from my SAMSUNG-SM-G890A...

    Great advice

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  43. Replies
    17
    Views
    1,656

    Actually there is a saddle on the wall clamp. ...

    Actually there is a saddle on the wall clamp. But I ran out didn't have one for the roof, thanks for the compliments!

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  44. Replies
    8
    Views
    709

    Is it actually the evaporator barrel cracked or...

    Is it actually the evaporator barrel cracked or just the extruding head?

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  45. Replies
    8
    Views
    709

    The ice machine was broke when he got there, he...

    The ice machine was broke when he got there, he started to clean it, and found a damaged evaporator, and you think he broke it. Did you forget it was broke when he got there?

    Sent from my...
  46. Replies
    3
    Views
    333

    High side not important, just clean condenser and...

    High side not important, just clean condenser and it is what it is

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  47. Replies
    3
    Views
    333

    Usually 15-30#. What you need to do is look at...

    Usually 15-30#. What you need to do is look at total amp draw after defrost and close the valve to reduce amp draw of unit to well below 80% of breaker rating

    Sent from my SAMSUNG-SM-G890A using...
  48. Replies
    16
    Views
    602

    Stand your ground. You know what it takes to...

    Stand your ground. You know what it takes to make it right. Either they'll be back to have it fixed right, or they'll go to Mr. Bandaid tech, then they'll be back soon after.

    Sent from my...
  49. Replies
    16
    Views
    602

    Honestly, it's foolish to spend any amount of...

    Honestly, it's foolish to spend any amount of money on an old r12 freezer. They need to buy a new box.

    Sent from my SAMSUNG-SM-G890A using Tapatalk
  50. Replies
    16
    Views
    602

    I say take her back to a semi-hemi with a...

    I say take her back to a semi-hemi with a DJAL-0149-CAV, or the DJAL-0150-CAV has same compressor but a little bit bigger condenser if you can fit it 😊

    Sent from my SAMSUNG-SM-G890A using Tapatalk