  1. Replies
    30
    Views
    1,159

    Most likely it's what you said: "good luck on...

    Most likely it's what you said: "good luck on that". I have been rebuilding compressors since 1972 in Michigan and when I started it was about 50/50 open drives and semi hermetics. Now its about...
  2. Replies
    30
    Views
    1,159

    I remember water cooled seals, what a blast from...

    I remember water cooled seals, what a blast from the past! Theaters around here used to run open drive Chrysler AirTemp radials.
  3. Replies
    30
    Views
    1,159

    tranger03, Do you work on any of the smaller...

    tranger03,
    Do you work on any of the smaller 340 series Vilters? If so, do they leak at the rates shown for the 400 series units? Just curious because we don't see any of the 400 series machines...
  4. Replies
    30
    Views
    1,159

    I've been in the compressor remanufacturing...

    I've been in the compressor remanufacturing business since 1972 and have some experience with both open and semi hermetic compressors. Open drives, of course, are the original design dating back to...
  5. Replies
    79
    Views
    6,764

    VTP99 Apparently we need to keep to the topic of...

    VTP99
    Apparently we need to keep to the topic of single cylinder compressors, although the concept applies to single or multi cylinder compressors and I thought it would be good intel for all. I'll...
  6. Replies
    79
    Views
    6,764

    Yes. You could replace a valve plate on a...

    Yes. You could replace a valve plate on a compressor and accidentally leave a suction valve reed out (which would be the same as having one broken reed). The compressor would still pump down and...
  7. Replies
    79
    Views
    6,764

    Everyone, Valving off the suction service valve...

    Everyone,
    Valving off the suction service valve to check for proper valve operation is not a definitive test. A compressor can have a broken suction reed and still pull into a vacuum, it just takes...
  8. Replies
    5
    Views
    469

    ar-hvac-man, I have never heard of a compressor...

    ar-hvac-man,
    I have never heard of a compressor beginning to leak after a power outage. If you are going to re-torque the bolts watch out, the two center bolts have a different spec than the rest....
  9. Replies
    52
    Views
    3,039

    pherman, That was a Chrysler Airtemp model 3011...

    pherman,
    That was a Chrysler Airtemp model 3011 or 3015. They were suspended in the unit by that top bracket and isolated with rubber mounts. Those compressors were 3600 rpm instead of everyone...
  10. Replies
    17
    Views
    862

    Most likely the clearances inside the compressor...

    Most likely the clearances inside the compressor are excessive. You can try to clean the pick up screen, though. On a 9R compressor the screen is behind the small diamond shaped cap on the lower...
  11. Replies
    8
    Views
    434

    Dave1234, The oil screen is screwed into a...

    Dave1234,
    The oil screen is screwed into a fitting on the inside of the casting. you need to remove the front bearing housing to access it. When you do this be careful, there are thrust washers on...
  12. Thread: Bad O6E?

    by remanworld
    Replies
    14
    Views
    1,037

    Hockeynut, Yes you have a bad compressor. When...

    Hockeynut,
    Yes you have a bad compressor. When a discharge valve fails high side pressure is always pushing on the head of the piston. The constant pressure does not allow load reversal to occur. ...
  13. Replies
    2
    Views
    377

    Servman, I believe that you have a defective...

    Servman,
    I believe that you have a defective compressor. Sometimes the low oil pressure is caused by a worn out oil pump. The Carlyle oil pump in NOT a gear style pump like a Copeland. Instead,...
  14. Replies
    4
    Views
    357

    1SikLBZ, The Trane model E open is an awesome...

    1SikLBZ,
    The Trane model E open is an awesome machine, and servicing it is very straight forward. The connecting rods in all Trane compressors are cast from aluminum and the bearing surface is...
  15. shouldn't this be in the AOP section? Clearly...

    shouldn't this be in the AOP section? Clearly this question is from a building owner and not a service tech.
  16. Replies
    2
    Views
    279

    Thats a #8 Frigidaire. 4 cylinder, slow speed,...

    Thats a #8 Frigidaire. 4 cylinder, slow speed, trunk type pistons inside. The biggest problem with those was when someone would convert them from R-12 to anything else. If you look at the size of...
  17. Replies
    81
    Views
    5,014

    Alcomech, NICELY DONE! If all the techs in the...

    Alcomech,
    NICELY DONE! If all the techs in the Michigan area had the basic understanding that you have demonstrated my reman shop would be closed for lack of business!
  18. Replies
    3
    Views
    345

    Has anyone changed a valve plate before on that...

    Has anyone changed a valve plate before on that compressor? Was the unloader added in the field? Taking the unloader off to see if the piston "snaps up" won't work. Remember, on a scou the piston...
  19. Replies
    4
    Views
    357

    Do you intend to rebuild or remanufacture? ...

    Do you intend to rebuild or remanufacture? Seriously, this is a question that I get asked all the time. We remanufacture. It does make a difference in the quality of the end product.
  20. Replies
    2
    Views
    198

    Did you lose all oil pressure or just see a...

    Did you lose all oil pressure or just see a decline in pressure? The compressor vibrates a little more now than it used to, right? It also sounds different, almost like a little rattle that comes...
  21. Replies
    81
    Views
    5,014

    Is the unloader suction cut off style or hot gas...

    Is the unloader suction cut off style or hot gas bypass style? If it is SCOU, when you put the unloader in the cylinder head did you take the full load tube out of the opening first? I have seen...
  22. Replies
    81
    Views
    5,014

    20 ton Carlyle semi hermetic compressors for air...

    20 ton Carlyle semi hermetic compressors for air conditioning are all 4 cylinder models and can only be unloaded 50% (one head).
  23. Replies
    81
    Views
    5,014

    I would just like to re-state that 1/2 a sight...

    I would just like to re-state that 1/2 a sight glass will cause compressor failure. Consult the green Carlyle service guide on page 12. It states 3/8's MAX and I'm telling you that based on my...
  24. Replies
    81
    Views
    5,014

    Carlyle 06E compressors are extremely sensitive...

    Carlyle 06E compressors are extremely sensitive to oil levels in the compressors. Too much oil will blow gaskets! Blown gaskets cause the compressor to run "burn the paint off" hot. Is this whats...
  25. Replies
    6
    Views
    456

    I've seen compressors withstand abuse from poor...

    I've seen compressors withstand abuse from poor maintenance or shoddy installation work last as long as a year before the bearings finally failed from liquid dilution or prolonged short cycling,or...
Results 1 to 25 of 70