    Yep we have had failures too. I have them stop...

    Yep we have had failures too. I have them stop driving after being installed for a few months(only to drive again normal after a power cycle), I have had them drive 10-0 no matter where the switch is...
  2. Thread: Spyder VVT Logic

    by MDaly
    Replies
    5
    Views
    522

    I did one. Very simple program per-say, My...

    I did one. Very simple program per-say, My program has heat cool and fan only. when in between heat or cool unit is in fan only mode and zone dampers go to 50%. I pass only terminal mode from zones...
  3. Replies
    7
    Views
    1,784

    I think this is John talking to fast, He never...

    I think this is John talking to fast, He never does that right,. LOL


    Here is why I say.
    If, then you would be in full heat at Setpoint and wouldn't get to start cooling until sensor =...
  4. Replies
    21
    Views
    2,883

    Spyder

    Also take care to know which Rev controller you have, look for a side ways 2 on the sticker next to the part number on the side. If this is there then you may need to flash it back to work with your...
  5. Replies
    15
    Views
    3,058

    Yeah that was some great stuff. Let the genie out...

    Yeah that was some great stuff. Let the genie out of the jar baby, lol. I was all over the ASC for VAV's and CAV's until I saw that new Venom.

    Is it here yet? Is it here Yet? How about now? Now?...
  6. Thread: AX Lon Links

    by MDaly
    Replies
    5
    Views
    562

    Any proxy linked points would be gone. for...

    Any proxy linked points would be gone. for example let's say you link OSA from one controller to another but do it from proxy points under the point folder to proxy points under another devices point...
  7. Replies
    6
    Views
    925

    I did something like this with the trend service....

    I did something like this with the trend service. Not so realtize as much but more of a copy find replace and past though, worked great.
  8. Replies
    95
    Views
    6,003

    I concur, most all my programing is done in the...

    I concur, most all my programing is done in the field controller. I do have some exception you did not list though.

    1. AHU supply resets as-well as some other resets depending on the job. Because...
  9. Replies
    13
    Views
    1,910

    MatrixTransform, That was great and I thought...

    MatrixTransform, That was great and I thought Invensys was "No" happy. I am so glad I got out from under the BC/Siebe/Invensys/Schneider/"add soon to be new name here".
    The first two years after I...
  10. Replies
    127
    Views
    7,763

    Oh also forgot something very important that was...

    Oh also forgot something very important that was told to me.

    "Marriage is about Love Divorce is about business. Don't let love screw up the business, just because business screwed up the love."
    ...
  11. Replies
    127
    Views
    7,763

    I went through this last year. It was a little...

    I went through this last year. It was a little different but all the same in the end. Life is great now. I just moved into a new place (to many old ghosts at the old place). I have my kids one week...
  12. The cost of living in Los Angeles, CA (just an...

    The cost of living in Los Angeles, CA (just an example) is 62.8% higher than in Dayton, OH . Therefore, you would have to earn a salary of $105,840 to maintain your current standard of living (if you...
  13. 50K-$65K A year? That seams like more...

    50K-$65K A year? [/QUOTE]

    That seams like more of a Controls Operation Manager position than a Control specialist.
    Are the wages in Ohio really that much less then here in Cali? That Job would...
  14. Replies
    7
    Views
    784

    I see both being used. With Honeywell we can use...

    I see both being used. With Honeywell we can use either for our field controllers. MOst of the time we use LON. I have a big job right now where we are useing LON for over 90% and BacNet for the...
  15. Thread: Network 8000

    by MDaly
    Replies
    13
    Views
    1,600

    I cut my teeth on Network 8000 and IMHO it's a...

    I cut my teeth on Network 8000 and IMHO it's a great system. One thing I really miss is the OSS block. It was a very simple and effective use of Optimal Start Stop. One block did it all.

    If I were...
  16. Thread: Network 8000

    by MDaly
    Replies
    13
    Views
    1,600

    the green plug is most likely the RS-485 ASD...

    the green plug is most likely the RS-485 ASD connector. There are two ways to connect a Jace to a Network 8000 system.
    1, The wam bam thank you mam way use a 9 to 9 pin Rs-232 cable and connect...
  17. Thread: Network 8000

    by MDaly
    Replies
    13
    Views
    1,600

    There should have ben no need to mess with the...

    There should have ben no need to mess with the buss. They should have just disconected the ASD from the GCM and connect it to the Jace.


    No and yes. There are many sites that have run for years...
  18. Thread: Network 8000

    by MDaly
    Replies
    13
    Views
    1,600

    Just to make sure, when you replaced the 14...

    Just to make sure, when you replaced the 14 MicroNets did you make sure you set the adresses?
    Did you verify the addresses are corect and match the Micronets in the MNFLO blocks in the GCM? Address...
  19. Thread: Bacnet spyder

    by MDaly
    Replies
    12
    Views
    1,978

    I just got done with the first phase of a small...

    I just got done with the first phase of a small BACnet Spyder job.
    This phase was an unoccupied remodel that used 12 Spyders (1 AHU, CP, and 9 VAV's) and 7 Viconics BACnet Fan Coil Thermostats. All...
  20. Thread: Workplace Pro

    by MDaly
    Replies
    9
    Views
    1,629

    The other thing you will need is a new Jace...

    The other thing you will need is a new Jace license with your ORG id or you will not be able to access it with your copy of Workplace Pro.
  21. Thread: Idiot sightings

    by MDaly
    Replies
    17
    Views
    2,841

    Years ago when I was at a friends house during...

    Years ago when I was at a friends house during our band practice there was a power outage. So we all sat around drinking beer waiting for the power to come on. After a while we all started noticing...
  22. Replies
    11
    Views
    1,094

    You could always add sump heaters to your tower.

    You could always add sump heaters to your tower.
  23. Replies
    4
    Views
    442

    Did you move the .bmp's over there also or just...

    Did you move the .bmp's over there also or just the .ssf's?
  24. Replies
    5
    Views
    893

    Spyders are nice, but I like the simplicity of...

    Spyders are nice, but I like the simplicity of the Smart VAV. With the Spyder S series you can use the new TR70 which is nice because you only have to run 1 cable to get a ton of information from the...
  25. Replies
    24
    Views
    8,317

    I'm hearing phase out but with continued support....

    I'm hearing phase out but with continued support. No new IA jobs, Phase out of Invensys control line. It's all suppose to Start happening around Aug. Sept. this year. That's just the rumors I'm...
  26. Replies
    21
    Views
    4,135

    For the most part. I Have not played with the...

    For the most part.
    I Have not played with the BacNet stuff much. However I would say for most field devices configure Yes, not sure though on fully program. However there are some devices that are...
  27. Replies
    21
    Views
    4,135

    Not just Invensys but JCI too. Back then I work...

    Not just Invensys but JCI too. Back then I work for an Invensys IFO and we bought 3 Jace's with the N2 driver. At the same time Tridium announced the ASD driver JCI was causing grief about the N2...
  28. Replies
    21
    Views
    4,135

    Straight from tridium.com. Also

    Straight from tridium.com.



    Also
  29. Replies
    5
    Views
    1,430

    Are you using only the state part only? I found...

    Are you using only the state part only? I found and I don't know if it just with the TAC controllers or not but If I didn't send a valid value on the VALUE part of the switch SNVT it did what you are...
  30. Thread: AX brain fart

    by MDaly
    Replies
    12
    Views
    821

    I always thought that it would be nice if there...

    I always thought that it would be nice if there was a little red flag Icon next to the station name in Workbench to show you it was running a different rev then what you had opened.
    I don't see how...
  31. Replies
    143
    Views
    3,826

    To me the point of life is about the journey to...

    To me the point of life is about the journey to the end. It has been my experience with most religious people that their journey is about the end.
    I might say "those flowers smell nice", "they might...
  32. Replies
    30
    Views
    2,449

    They use the same tool to program. You can use...

    They use the same tool to program. You can use existing LON Spyder apps and just drop them in, so you don't have to recreate the programs you already use. You don't have to create a SNVT for every...
  33. Replies
    30
    Views
    2,449

    We are actual look into doing our first BACnet...

    We are actual look into doing our first BACnet job. It's a retro that has a RS485 buss in place. I have done this kind of retro before going to LON but have had to deal with sever com issues that pop...
  34. Replies
    285
    Views
    47,906

    B&B electronics Model 485LPRJ

    B&B electronics

    Model 485LPRJ
  35. Replies
    33
    Views
    3,082

    Rapidbalance 3 works, and you have a HWV...

    Rapidbalance 3 works, and you have a HWV override as well.
    Doing this system with XL15C using Rapidzone then bringing it into AX works well. You just have to go about it the right way. Just don't...
  36. Replies
    21
    Views
    1,495

    Not the greatest install by any means, Also I...

    Not the greatest install by any means, Also I don't think your furnace closet was made to be a storage shed/ janitor closet.:rolleyes:
  37. Replies
    6
    Views
    750

    Yep, Fly in Sat @ noon.

    Yep, Fly in Sat @ noon.
  38. Replies
    166
    Views
    7,504

    Just asking, but are you talking R2 or AX. In R2...

    Just asking, but are you talking R2 or AX. In R2 yes the owner needs to send a relicense request in to the big T to have the new contractors Org ID added. I can understand why they did this back when...
  39. Replies
    55
    Views
    2,086

    And I third it. The Outlaw Josie Wales... ...

    And I third it.

    The Outlaw Josie Wales...

    Dying ain't much of a living boy.
    you boys gonna pull them guns or whistle dixie?
    Buzzards got to eat, same as the worms.
    We got somethin' in this...
  40. Replies
    0
    Views
    369

    MicroFloII Double duct boxes

    I'm looking for the BC or Invensys or TAC doc that had the setup info for MicroFlo II Double duct mixing VAV box. When I worked for the local IFO I had seen this once but did not keep a copy because...
  41. Replies
    29
    Views
    2,378

    208, 209 whatever it takes.:eek: Hire an...

    208, 209 whatever it takes.:eek:

    Hire an electrician or buy some books, but don't hire any of the guys that said it could be put on either side though.

    Transformers with built in is a good idea...
  42. Replies
    13
    Views
    863

    I use a wireless router with a Jace.

    I use a wireless router with a Jace.
  43. Replies
    7
    Views
    1,049

    Out here in the central valley of CA. we don't...

    Out here in the central valley of CA. we don't have to worry to much about humidity and don't use enthalpy too much unless a back east engineer calls for it, however comparing return Temp to outside...
  44. My thoughts exactly. Each head of house hold get...

    My thoughts exactly. Each head of house hold get one voucher for one new American made automobile not to exceed $30,000.00. This way we get more newer reliable vehicles on the road. Plus think of all...
  45. Thread: AX question

    by MDaly
    Replies
    7
    Views
    606

    The Niagara Network is for the Jace's and the...

    The Niagara Network is for the Jace's and the Server to communicate with each other.
  46. I was recently at a facility finishing up some...

    I was recently at a facility finishing up some control work mid 60 deg morning . I was with one of the facility maintenance crew when I herd his two way radio go off, It was his supervisor. His...
  47. Thread: LON Trunk Gage?

    by MDaly
    Replies
    10
    Views
    918

    And that was my point if he has over 60 devices...

    And that was my point if he has over 60 devices he will need a repeater/router anyway which will increase his bus length, thus he can stick with the 22 ga.
  48. Thread: LON Trunk Gage?

    by MDaly
    Replies
    10
    Views
    918

    5000' and under 60 devices? I would still use a...

    5000' and under 60 devices?
    I would still use a LPR-10 but only as a repeater (in and out on net-A) not using both net-A and net-B

    I would assume (I know the whole A@@ u and me thing) that with a...
  49. Thread: Invensys I/A

    by MDaly
    Replies
    9
    Views
    1,191

    Yes. I have used two in the past the work well....

    Yes. I have used two in the past the work well. "Ghost" and "Go Back" When I worked for the local Invensys rep now TAC rep we (us tech in the department) played around with these kind of things. We...
  50. Thread: Invensys I/A

    by MDaly
    Replies
    9
    Views
    1,191

    You can run a 30 day demo of WPtech for free. All...

    You can run a 30 day demo of WPtech for free. All you need is Vissio 2002-3 licensed and LON plug n play. Use ghost or go back start with a fresh session, load WPtech, do what you have to, save...