    Just to echo Dingman, this TEC is just an...

    Just to echo Dingman, this TEC is just an extended I/O controller. It only has a single application in it of 2497, and nothing else.

    All of the I/O has to be controlled/monitored by the field...
  2. Replies
    7
    Views
    484

    The non lab tecs have a built in flow sensor...

    The non lab tecs have a built in flow sensor ranged for 0-1 in wc diff press. This equates out to about 4000 feet per min max range.
    A 6' duct has an area of 0.2 sq ft. So 0.2 * 4000 = 800 cfm max...
  3. Basically, the journal files are created by a...

    Basically, the journal files are created by a loss of communication between the server and client in the middle of a database write. The loss of communication can be caused by power down of one of...
  4. Replies
    4
    Views
    318

    The PXM-AI8 is just a point expansion module that...

    The PXM-AI8 is just a point expansion module that can have up to 8 analog inputs. There are no "points" or application in it. It is just an I/O device with no internal smarts.

    The field panel goes...
  5. Replies
    4
    Views
    313

    The modules you show in the picture are analog...

    The modules you show in the picture are analog output pnuematic. The light on these modules is an actual feedback of the output pressure sensed in the line. If you do not have a supply line hooked...
  6. If you have an integration panel on the site,...

    If you have an integration panel on the site, (modbus, bacnet, etc), then sunrise and sunset are built into the diagnostic point. All you have to do is enter you Lat and Long.

    Otherwise, here is...
  7. Thread: TEC ?

    by Daramoe
    Replies
    2
    Views
    378

    After the tec has been through a calibration...

    After the tec has been through a calibration cycle,
    Then
    (Balancer CFM reading / TEC CFM reading) * Old Flo Coeff
  8. Thread: Siemens PXM10S

    by Daramoe
    Replies
    4
    Views
    557

    What firmware revision is your panel? The PXM...

    What firmware revision is your panel? The PXM display is only supported on some of the new firmware.
  9. Replies
    4
    Views
    426

    Speaking of logic, I missed one in the example....

    Speaking of logic, I missed one in the example. You will need to add the 50, 41 to the end of the last table statement, or you will not get readings between 40 and 50.
  10. Replies
    4
    Views
    426

    Break it into 2 table statements IF (HA08CV...

    Break it into 2 table statements

    IF (HA08CV .GE. 50.) THEN TABLE(HA08CV,HA08GP,50,41,60,53,70,63,80,74,90,75) ELSE TABLE(HA08CV,HA08GP,0,0,10,1,20,7,30,17,40,27)
  11. What I think you are looking for is Slope and...

    What I think you are looking for is Slope and Intercept. Coefficient is the term used to adjust the CFM flow readings to the air balancers readings.

    That being said, while the app you are using...
  12. It's a little to involved to try to explain in a...

    It's a little to involved to try to explain in a forum (IMO). Your best bet would be to get a Apogee Field Panel Users manual. There is a very good chapter in there that explains enhanced alarming in...
  13. Replies
    6
    Views
    500

    More then likely, either there is a name...

    More then likely, either there is a name resolution issue between your client PC and the server (host file not setup if static IPs, or DNS server does not have all of the info properly registered) ,...
  14. If you know how, you can change the alarm to an...

    If you know how, you can change the alarm to an enhanced alarm, and use the schedule point as the mode point in your alarm setup.
  15. Replies
    5
    Views
    964

    The damper command point will stay in OVRD, and...

    The damper command point will stay in OVRD, and the TEC will do the calibration procedure normally, as it doesn't command the damper command. However, as the damper command is a calculated point, the...
  16. Replies
    3
    Views
    1,426

    Chapter 5 of the field panel users manual deals...

    Chapter 5 of the field panel users manual deals with nothing except the point database, and has a table going into detail on each of these points.
  17. Sounds like a trend buffer full upload. I would...

    Sounds like a trend buffer full upload. I would guess that somebody who didn't understand what they are doing, used the trend wizard to add all the points in the system in trend, and one of the...
  18. Replies
    1
    Views
    427

    Just a combination of resolution of the a-d...

    Just a combination of resolution of the a-d converter, and the auto scaling of the commander box. You didn't say what the range of the controlled device is, 0-10, 2-10, 4-20ma, etc). As to it showing...
  19. Replies
    3
    Views
    816

    The 535-741 is an 100K thermistor. The point...

    The 535-741 is an 100K thermistor. The point expansion module only supports 1K RTD (375 type) , 0-10 VDC and 4-20ma for inputs.
  20. Replies
    8
    Views
    1,948

    Are these wireless FLNs?

    Are these wireless FLNs?
  21. Replies
    3
    Views
    862

    I would suspect that it is not that the Point Exp...

    I would suspect that it is not that the Point Exp Block does not support LPACIs, but more that it does not support being on the FLN. The original Point Exp Blocks could only exist on the MEC...
  22. Replies
    5
    Views
    1,232

    If you upgrade your panels to 3.2 firmware, this...

    If you upgrade your panels to 3.2 firmware, this is a BTL certified firmware. The siemens panel at that time is a native bacnet device.
    There will have to be a database conversion done at the same...
  23. Replies
    5
    Views
    1,232

    The PX controllers can be flashed from 2.x...

    The PX controllers can be flashed from 2.x firmware to the bacnet firmware 3.2
    If the MECs and MBCs are Power MECs and MBCs, and are the ethernet variety (they have an ethernet port) then they can...
  24. Replies
    4
    Views
    1,000

    What revision of Insight What is the panel type...

    What revision of Insight
    What is the panel type and firmware listed in system profile.

    Your slope and intercept calculates out to 125 = 0 volts 0 = 10 volts, so I am assuming you are hooking up a...
  25. Replies
    37
    Views
    13,569

    For the PXC 24: Part Numer PXC24.2-PEF.A or ...

    For the PXC 24:
    Part Numer PXC24.2-PEF.A

    or

    For the PXC 36:
    Base Panel
    Part number PXC36-PE.A
    P2, 36 points
  26. Replies
    37
    Views
    13,569

    For which one? In each of the controllers, the P2...

    For which one? In each of the controllers, the P2 and the bacnet are different part numbers as they are different firmware loads.
  27. Replies
    37
    Views
    13,569

    The PXC Modular, the PXC 36, and the second...

    The PXC Modular, the PXC 36, and the second generation of the PXC 24 ( the one that has both a 485 and an ethernet connection on it) can be used as an AEM with the correct license. That means that...
  28. Thread: Siemens FLN

    by Daramoe
    Replies
    4
    Views
    1,321

    The database of the UCs can be backed up in...

    The database of the UCs can be backed up in system profile. The UCs have an EEprom just like the TECs, so it usually takes physical or electrical damage to get to the point that you need to replace a...
  29. Replies
    3
    Views
    1,366

    If the existing MEC and PXC are Bacnet, they you...

    If the existing MEC and PXC are Bacnet, they you should be able to discover them in a normal fashion. If they are the propriatary protocal (P2 and P1) then they would have to have the Bacnet Client...
  30. Replies
    11
    Views
    1,492

    It definitely works. I have done about a dozen...

    It definitely works. I have done about a dozen over the last 2-3 years, with very little issues.
  31. Replies
    11
    Views
    1,492

    There is an application guide, but it is a...

    There is an application guide, but it is a Proprietary Siemens manual available to thier techs only. It takes you step by step through collecting the data from the JCI system, converting it into...
  32. Replies
    4
    Views
    694

    Also, if you are unsure on the application, just...

    Also, if you are unsure on the application, just add the TEC at the proper address, and leave the application blank (if you are doing this at the MMI port of the panel). As long as the TEC is...
  33. Replies
    28
    Views
    5,065

    Again, it depends on where the line of PPCL is....

    Again, it depends on where the line of PPCL is. For example, using a loop statement for example, if the loop is in panel 1, and the physical output is in panel 2, every minute change in the loop...
  34. Replies
    5
    Views
    1,055

    Verify that your Windows firewall is disabled on...

    Verify that your Windows firewall is disabled on the PC you are working on. If you changed out PCs, and the new PC has a different name then the original one, you will have to change the node name...
  35. Replies
    5
    Views
    1,055

    In system profile, you have a BLN name. That name...

    In system profile, you have a BLN name. That name has to be defined in the ethernet field panels as part of the start up of the field panels. The BLN names have to match, and they ARE case sensitive....
  36. Replies
    8
    Views
    1,516

    If it's Datamate Base, you won't be doing much...

    If it's Datamate Base, you won't be doing much modifying with it. Base only has the capablity to back up and restore the database from a field panel, and it has the terminal mode capablity to talk to...
  37. Thread: Siemens apogee

    by Daramoe
    Replies
    12
    Views
    1,535

    Depends on what they have for hardware and...

    Depends on what they have for hardware and software. If they have an Apogee front end of at least 3.8 or higher, then they could install the Bacnet client option on the front end, and talk bacnet IP...
  38. Replies
    2
    Views
    1,470

    A few basis architecture questions if you do not...

    A few basis architecture questions if you do not mind:

    1. In an Apogee network, which device owns and stores the "global" data". I'm assuming network name, controllers, addresses, printers etc....
  39. Replies
    5
    Views
    495

    There are 2 ways to wire a 4-20 ma signal to the...

    There are 2 ways to wire a 4-20 ma signal to the mec, it depends on who is supplying the power for the end device. If the MEC is providing the power, then at the MEC, you connect the wires to 24vdc...
  40. Replies
    5
    Views
    1,698

    You are probably looking at an impedence issue....

    You are probably looking at an impedence issue. The SCU and the TXIO have different impedence limits on the 4-20 inputs.

    For example, consider a situation where an SCU is replaced with a PXC...
  41. Replies
    3
    Views
    906

    Just an FYI. That is a P1 converter, not a P2....

    Just an FYI. That is a P1 converter, not a P2. They are very different protocals. This converter could be used if you are taking out the Siemens main panel, the MEC, and leaving the controllers out...
  42. Replies
    3
    Views
    906

    Siemens protocal

    You are correct, it is a proprietary protocal. I know that different vendors over the years have tried to backwards engineer it with very little success. The generally wind up locking the bln up.
  43. Replies
    2
    Views
    879

    First, you would want to verify that Telnet is...

    First, you would want to verify that Telnet is enabled at the panel itself. It can be enabled and disabled on a panel by panel basis. If it is enabled, then you can either go to system profile, right...
  44. Thread: Siemens System

    by Daramoe
    Replies
    2
    Views
    596

    It depends on the equipment installed, and the...

    It depends on the equipment installed, and the version and type of datamate you have. Is it Datamate Base, or Datamate Advanced?
    At 3 years old, they could have MBCs or MECs for main field panels,...
  45. Replies
    28
    Views
    5,065

    Dingman is very close, but he has it backwards. ...

    Dingman is very close, but he has it backwards.

    When a point is being referenced in a panel in which doesn't exist, that panel will call out to the panel where the point is for the value of that...