02-28-2012, 08:25 PM
Thread: case fan spinning backward?
by pepeLePew- Replies
- 19
- Views
- 834
ECM motors cost twice as much and last half as...
ECM motors cost twice as much and last half as long--but they save money ??
If I find 1 running backwards I always change it. Mark it as "runs backwards" and throw it in the "emergency only" parts... -
02-23-2012, 09:35 PM
Thread: out of my realm
by pepeLePew- Replies
- 43
- Views
- 2,272
not to hijack but what is y'alls favorite leak...
not to hijack but what is y'alls favorite leak detector for R404a ??
-
08-21-2010, 02:36 AM
Thread: Trane Low Suction Pressure
by pepeLePew- Replies
- 33
- Views
- 4,030
Is there a way to display these theads in...
Is there a way to display these theads in chronological order?
-
08-21-2010, 12:13 AM
Thread: Trane Low Suction Pressure
by pepeLePew- Replies
- 33
- Views
- 4,030
long saga and it still continues but that was...
long saga and it still continues but that was surely the biggest problem!
thanx for all the help
y'all be safe out there -
07-27-2010, 05:45 AM
Thread: Trane Low Suction Pressure
by pepeLePew- Replies
- 33
- Views
- 4,030
Thank you for the replies! Change filters,etc....
Thank you for the replies!
Change filters,etc. has been proposed to the customer.
TBC -
07-23-2010, 05:27 AM
Thread: Trane Low Suction Pressure
by pepeLePew- Replies
- 33
- Views
- 4,030
Thank you for the reply. sub cooling #2=40degF...
Thank you for the reply.
sub cooling #2=40degF
return air=77degF
pleated filters are a little dirty
evap coil was very dirty with stubborn dirt. Cleaned
Condenser is clean
I will definitely... -
07-23-2010, 01:16 AM
Thread: Trane Low Suction Pressure
by pepeLePew- Replies
- 33
- Views
- 4,030
Trane Low Suction Pressure
60 ton split.2 circuits. both have high head and low suction. circuit 1 300#hp-35 suction. circuit 2 325 head-38 suction. R-22. fan belt is tight. evap is clean. both circuits flashing at sight...