  1. New LIEBERT discharge service valve hard to turn.

    I have a discharge service valve for a 06D semi comp to replace. The new one is very hard to turn with a service valve wrench. I want to be sure this is normal before installing it, in case the...
  2. Replies
    0
    Views
    655

    LIEBERT hot gas reheat coil

    I have 10 LIEBERT deluxe 3's with systems 00 & 01 control boards (no longer available). I'm looking for info on the first stage hot gas reheat system. Anyone heard of ellimiating this first stage and...
  3. Replies
    5
    Views
    1,080

    refrigerant HFO-1234yf

    Just heard of new ref. approved for new motor vehicles by EPA. They say it won't deplete the ozone layer. It's called HFO-1234yf. Anybody heard about it? Other than EPA's claim about the ozone,...
  4. never mind?

    What do you mean? Disregard your post?
  5. EDPAC 1speed compressor replace with 2speed

    We have a EDPAC 7.5 ton AC stand alone. Compressor failed; windings short to ground. Got a replacement compressor from Layton Ind. NY. The old one is single speed, the new one is 2 speed. They sent...
  6. Replies
    9
    Views
    1,104

    oil level / extreme vibe. comp.

    The oil level in the sight glass is inconclusive...all grey & no sign of motion?? Maybe overfilled?
  7. Replies
    9
    Views
    1,104

    compressor extreme vibration

    I have a DATA-AIR machine in a server rm. Found one of 2 CARLYLE compressors dumped it's charge & oil from a hole in elbow coming from suction service valve going to accumulator. Replaced valve,...
  8. Replies
    21
    Views
    2,180

    Appreciate the comments, but some may have...

    Appreciate the comments, but some may have misunderstood. I'm just sharing a useful tip that may help rule out the obvious before breaking out the leak detector.
  9. Replies
    21
    Views
    2,180

    Leaking schrader valve? Spit on it!

    Here is an easy way to discover if a schrader is leaking. Try spitting on your finger and rub it into the port. It'll bubble up just like soap solution, and it's right at hand.
  10. Replies
    9
    Views
    1,187

    Thanks to all,for all the input.

    Thanks to all,for all the input.
  11. Replies
    9
    Views
    1,187

    still learning

    Im 60 years old, this is my third career. I've been at it about 8 years. If I can learn something new each day I'm happy. Thanks for the help.
  12. Replies
    9
    Views
    1,187

    reusing recovered gas

    I want to reuse gas (R22) recovered from a unit in a new 50 lb. drum. It's going back into the same unit it came out of. I want to charge it in liquid form. After I pull a deep vacuum, do I need to...
  13. Replies
    16
    Views
    1,115

    responses appreciated

    I appreciate everyones advice on this matter. I've yet to get back to this unit, but will keep all informed. For now I know it is 3 heads (6 cyl); I don't know how much R22 may have been added....
  14. Replies
    16
    Views
    1,115

    more info

    This is a DATA-AIRE unit with electric unloader
  15. Replies
    16
    Views
    1,115

    06D breakdown; mixed refrigerant?

    There is a computer room a/c unit with two Carlyle 06D's using R407C; Recently one lost first stage cylinders; It will run second stage when loader kicks in. I'm told that a previous tech may have...
  16. Replies
    11
    Views
    1,193

    thanks for input, and questions; here's more

    The water pump is new; Recent notes show EWT-66 deg / LWT-71 deg. with a pressure of 173/50 psi; That gives me an approach temp of 20 deg.
    (shouldn't it be closer to 10 deg?) Temperatures measured:...
  17. Replies
    11
    Views
    1,193

    Penn water valve? plugged coax coil? or both?

    I have a 5ton server room AC with glycol drycooler that has been cutting out on high head pressure; If I open the Penn valve wide open & run the drycooler pump continuously the ac works fine. When...