  1. Started at 43 graduated at 47 years old. Best...

    Started at 43 graduated at 47 years old. Best decision I ever made.
  2. Thread: YSC036E issue

    by gwoner
    Replies
    28
    Views
    1,802

    Huh imagine that.

    Huh imagine that.
  3. Thread: YSC036E issue

    by gwoner
    Replies
    28
    Views
    1,802

    On a call for heat,during spark ignition,the...

    On a call for heat,during spark ignition,the spark generated by the ignition probe may cause an excessive amount of electrical noise to be induced back into the RTRM module,this noise is then passed...
  4. Thread: YSC036E issue

    by gwoner
    Replies
    28
    Views
    1,802

    I

    I
  5. Replies
    9
    Views
    710

    CTI is what u need

    CTI is what u need
  6. Replies
    20
    Views
    1,759

    Sounds like somebody cycled power and wala?

    Sounds like somebody cycled power and wala?
  7. Thread: YSC036E issue

    by gwoner
    Replies
    28
    Views
    1,802

    Install a grounding strap from board to...

    Install a grounding strap from board to structure. Problem solved
  8. Thread: Trane intelipak

    by gwoner
    Replies
    15
    Views
    1,147

    Id say its most likely a flame rod issue. What's ...

    Id say its most likely a flame rod issue. What's your flame sense at pilot pressure?
  9. Trane has what you need. Call Trane Supply

    Trane has what you need. Call Trane Supply
  10. Replies
    19
    Views
    1,052

    I agree .Sounds like your crossover slots are...

    I agree .Sounds like your crossover slots are full of rust. Use your utility knife to clean out.
  11. Replies
    4
    Views
    442

    true dat

    true dat
  12. Thread: trane , help

    by gwoner
    Replies
    6
    Views
    650

    sounds like internal check valve is stuck.Get a...

    sounds like internal check valve is stuck.Get a BFH and 2x4 and give it a whack.
  13. Replies
    1
    Views
    346

    Sounds like no one has been cleaning condensate...

    Sounds like no one has been cleaning condensate lines ever to cause such an issue to happen.
  14. Replies
    18
    Views
    2,780

    Epoxy is only a temporary repair until a new coil...

    Epoxy is only a temporary repair until a new coil is purchased
  15. Replies
    15
    Views
    2,790

    Pull the access panel off the economiser hood and...

    Pull the access panel off the economiser hood and verify actuator operation. Also red service lite should be on on uem board. When putting in test mode and nothings working, disconnect the j6 plug on...
  16. Replies
    15
    Views
    2,790

    Supply air sensor is the problem.Get new SAS or...

    Supply air sensor is the problem.Get new SAS or pull OAS and use it.
  17. Just shut down ckt 1, to dang cold out with...

    Just shut down ckt 1, to dang cold out with windchill at -17* f. Will return at end of week to investigate. Customer happy and occupants in office below condenser happy with noise gone .
  18. OROAB 5-210 R407C on Liebert Remote Condenser.

    OAT 8*. head pressure control making a loud vibrating noise. Is this a sign of internal damage to the valve or diaphram or is it common at this low of ambients
  19. Replies
    2
    Views
    927

    Use existing back support under HE, use new bolt...

    Use existing back support under HE, use new bolt that comes with new unit. Most come with inducer and gas valve if ordered. 1 guy for 4 hours, 1 guy for 8 hours.No crane needed to remove and replace,...
  20. Replies
    2
    Views
    927

    2 guys, 1 for 4 hours and 1 for 8 .No crane...

    2 guys, 1 for 4 hours and 1 for 8 .No crane needed to install , maybe to get on the roof.
  21. Replies
    22
    Views
    2,457

    Does the pilot lite? then go out. IGnition...

    Does the pilot lite? then go out. IGnition control board
  22. Replies
    14
    Views
    1,664

    I wonder if the occupants getting headaches had...

    I wonder if the occupants getting headaches had anything to do with this stupid repair. Must not own any red tags
  23. Had same problem with a unit heater. Copper...

    Had same problem with a unit heater. Copper cleaned, still wouldnt take. Picked up some Silvabrite 100 solder and wahlah, 95% tin 5% silver, problem solved. Stay away from water based flux.
  24. Replies
    2
    Views
    1,715

    Pull the J7 plug off the UCP .Check your DC...

    Pull the J7 plug off the UCP .Check your DC voltage from J7-2 and J7-9.Apply power and jumper LTB -14 TO LTB -5. Should read 2.8 VDC for heat stage 1.LTB 14 TO LTB 3 HEAT 2 should be 3.71 VDC If the...
  25. Replies
    7
    Views
    1,229

    I dont know if you meant -.2 I.W.C. , but thats...

    I dont know if you meant -.2 I.W.C. , but thats the spec on that unit.