Search:
Type: Posts; User: HeatXfer
Search: Search took 0.02 seconds.
-
06-07-2011, 06:21 PM
Thread: Air Filter question(s)
by HeatXfer- Replies
- 6
- Views
- 574
A 4ton air handler will move about 1600cfm;...
A 4ton air handler will move about 1600cfm; through a 20"x25" filter that's about 460fpm. PD for a new merv 10 is about .23" to .25"wc at approx 480fpm. Typical recommended pd change point is .75"...
-
06-07-2011, 05:37 PM
Thread: Air Filter question(s)
by HeatXfer- Replies
- 6
- Views
- 574
Rhino32713: Please don't cut-n-paste Google...
Rhino32713:
Please don't cut-n-paste Google searches, it's like that joke about teaching pigs to sing.
Anyway, the closer a filter is to the fan intake, the cleaner your system will be; less... -
06-07-2011, 04:11 PM
Thread: FX20 Email Recipient Error
by HeatXfer- Replies
- 8
- Views
- 752
Did you reboot the JACE? Changes won't take if...
Did you reboot the JACE? Changes won't take if you don't reboot. Also it might be the DNS. Use the host's IP address or you can set up the JACE with a DNS server.
-
06-07-2011, 04:02 PM
- Replies
- 4
- Views
- 492
Where do you live, or want to work? What city &...
Where do you live, or want to work? What city & state?
-
06-07-2011, 03:55 PM
Thread: what am I doing wrong
by HeatXfer- Replies
- 26
- Views
- 2,024
'Yer cold
'Yer cold
-
06-07-2011, 03:27 PM
Thread: Fume Collector design questions
by HeatXfer- Replies
- 4
- Views
- 550
You can buy a new, warrantied, properly...
You can buy a new, warrantied, properly engineered Donaldson brand for anywhere from $1500 to $6,000. 'Plug-n-Play'.
You could probably wing-it, but the minute someone gets sick, and sues you and... -
07-20-2009, 04:18 PM
Thread: SIEMENS...CIS Software
by HeatXfer- Replies
- 119
- Views
- 18,432
"Hello, I'm Rick" probably would have been a...
"Hello, I'm Rick" probably would have been a better introduction. Plus:
1)What you do for a living.
2)State & City where you work?
3)What your professional experience is.
Please read THIS -
07-19-2009, 12:47 PM
Thread: oil level switch-30GX chiller
by HeatXfer- Replies
- 4
- Views
- 819
Follow Chiller Man's directions. But here's a tip...
Follow Chiller Man's directions. But here's a tip for the older (mid 90's) chillers: the first 30GXs didn't have O-rings on the oil level sensor fittings and tended to leak there (among other...
-
06-10-2009, 09:23 PM
Thread: Dirty Hot Water Coils
by HeatXfer- Replies
- 28
- Views
- 2,320
Brilliant!
Brilliant!
-
06-09-2009, 11:00 AM
Thread: Dirty Hot Water Coils
by HeatXfer- Replies
- 28
- Views
- 2,320
You've just sold me. I'm going to try SG for...
You've just sold me. I'm going to try SG for everything now.
-
06-05-2009, 12:56 AM
Thread: Dirty Hot Water Coils
by HeatXfer- Replies
- 28
- Views
- 2,320
I did a quick search and it looks like your plan...
I did a quick search and it looks like your plan to use simple green is a good one. I didn't think it would dissolve dried ink, but many people have used it with success.
I've heard "Gonzo" works... -
06-04-2009, 10:19 PM
Thread: Dirty Hot Water Coils
by HeatXfer- Replies
- 28
- Views
- 2,320
What type of ink? You'll probably need some kind...
What type of ink? You'll probably need some kind of solvent.
Nice clean removal BTW -
06-04-2009, 09:21 PM
Thread: How low can I set up a Lieber equipment?
by HeatXfer- Replies
- 7
- Views
- 689
That's very cold, even for a data center. Despite...
That's very cold, even for a data center. Despite what the IT guys say, the best environment for electronics is a steady 70° - 72°f at about 50% RH. Too cold and you can get condensation forming...
-
06-04-2009, 08:49 PM
Thread: Noisy Exhaust Fan
by HeatXfer- Replies
- 12
- Views
- 1,337
What is the nature of the noise? Is it a 'sound',...
What is the nature of the noise? Is it a 'sound', or is it vibration felt inside the building? Is it a mechanical or an 'air' sound? Is it steady, rythmic, rattling, rumbling, thumping, whooshing,...
-
Yes to the traverse. Can you see condensation...
Yes to the traverse. Can you see condensation overflowing the pan and running down the duct, or condensation being pulled off the coil by high air velocity?
What it is design CFM and what are the... -
06-04-2009, 07:23 PM
Thread: Mcquay literature
by HeatXfer- Replies
- 6
- Views
- 498
I can never remember the exact wording of all...
I can never remember the exact wording of all those alarms, anyway, glad to you got it worked-out.
-
06-04-2009, 02:30 PM
Thread: McQuay touch screen
by HeatXfer- Replies
- 6
- Views
- 474
The software for the touch screen should be on...
The software for the touch screen should be on the cpu's flashdrive. A quick way into the system without using the touch screen is to get a regular keyboard: with either a usb or the old PS2...
-
06-04-2009, 01:37 AM
Thread: Mcquay literature
by HeatXfer- Replies
- 6
- Views
- 498
I haven't seen any lit on this either, but if...
I haven't seen any lit on this either, but if you're familiar with the machine you should be able to discern whether or not you're leaking-by by reading the line pressures at the lube box while you...
-
06-04-2009, 01:30 AM
Thread: McQuay touch screen
by HeatXfer- Replies
- 6
- Views
- 474
Drivers for the Windows CE OS touch screen can be...
Drivers for the Windows CE OS touch screen can be found here. Or you can get them from McQuay. Is your chiller a new MicroTech II or has it been upgraded with a new MicroTech II control panel with...
-
06-01-2009, 06:17 PM
Thread: Carrier 30gx oil issue
by HeatXfer- Replies
- 15
- Views
- 1,937
I don't recommend bypassing the oil level switch;...
I don't recommend bypassing the oil level switch; if there isn't enough oil to maintain lubrication the damage to an 06N can be catastrophic, and compressor replacement is inevitable. Carrier's...
-
04-22-2009, 03:10 PM
Thread: Here is a question.
by HeatXfer- Replies
- 32
- Views
- 831
Don't knock it 'till you've tried it! Originally...
Don't knock it 'till you've tried it! Originally from S.E. Ohio, just down river from Amish country.
We should really go back to the gold standard, eliminate the Federal Reserve Bank, re-institute... -
04-21-2009, 09:49 PM
Thread: Here is a question.
by HeatXfer- Replies
- 32
- Views
- 831
Depends on what you mean by "too bad"
Depends on what you mean by "too bad"
-
04-21-2009, 10:17 AM
Thread: pucker factor increases
by HeatXfer- Replies
- 123
- Views
- 2,140
Now these are all verifiable facts without the...
Now these are all verifiable facts without the rhetoric.
- Citation needed
None of the items on my list are rhetorical; he did those things. My statements manipulative? I'm certainly not trying... -
04-21-2009, 01:09 AM
Thread: pucker factor increases
by HeatXfer- Replies
- 123
- Views
- 2,140
Opinions and facts...there's an interesting thing...
Opinions and facts...there's an interesting thing about facts: everyone is entitled to learn them, but many prefer not to let them interfere with their preconceived notion of the world.
Besides,... -
04-21-2009, 12:34 AM
Thread: pucker factor increases
by HeatXfer- Replies
- 123
- Views
- 2,140
"The worst technicians are the brand bashers of...
"The worst technicians are the brand bashers of the world. Not because they are bad techs, but because they have bad attitudes.
Professional technicians have no overall problems with any brand and...
Results 1 to 25 of 130