Search:

Type: Posts; User: klrogers

Page 1 of 20 1 2 3 4

Search: Search took 0.02 seconds.

  1. If the user does not have permissions to view the...

    If the user does not have permissions to view the ord in the value binding of the button then the Degrade feature can either disable or hide the button.
  2. Replies
    2
    Views
    165

    Not really a controls (DDC) problem, but to help...

    Not really a controls (DDC) problem, but to help you out, the outputs from the main board have snubber circuits (look that up if you need to) this means that whenever you have no load on the wire...
  3. Replies
    9
    Views
    206

    Can you post a screenshot of the Java console as...

    Can you post a screenshot of the Java console as it is trying to load?
  4. Replies
    9
    Views
    206

    Are you saying that you upgraded the FX Jace to...

    Are you saying that you upgraded the FX Jace to Niagara version 3.8? If so you probably need to install the Java unlimited security files to ALL PC's that need to access it via a browser. I will see...
  5. Replies
    3
    Views
    298

    What version is the Jace licensed for? It looks...

    What version is the Jace licensed for? It looks like you are trying to put 3.8 on a Jace that is only licensed for 3.7.

    Kevin
  6. Replies
    5
    Views
    296

    Are you aware that Chrome disables the use of...

    Are you aware that Chrome disables the use of Java, this went into effect at Chrome version 42. You can re-enable it as follows:

    In your URL bar, enter:

    chrome://flags/#enable-npapi
    Click the...
  7. Replies
    22
    Views
    1,304

    Play the Tridium Talk presentation, gives a...

    Play the Tridium Talk presentation, gives a little taste of N4

    http://www.tridium.com/tridium-talk
  8. Thread: tabbed pane

    by klrogers
    Replies
    7
    Views
    214

    It should have labelpanes under the tabbed pane...

    It should have labelpanes under the tabbed pane not canvas panes.

    module://docUser/doc/bajaui-TabbedPane.html

    Kevin
  9. Replies
    7
    Views
    302

    This might help explain the relationships ...

    This might help explain the relationships

    574071
  10. Replies
    17
    Views
    863

    While I am certainly interested in this...

    While I am certainly interested in this discussion, I don't think we should be talking numbers here in the open section of the forum. Everyone involved so far is a professional member so maybe a move...
  11. Good work, can we look forward to a Tridium...

    Good work, can we look forward to a Tridium driver for M-Net :)
  12. You have mail

    You have mail
  13. Replies
    1
    Views
    218

    Check out the "Report Service" Kevin

    Check out the "Report Service"

    Kevin
  14. I am not sure that this will work with all...

    I am not sure that this will work with all versions and manufacturers, but you can try this:

    Copy the config.bog file
    Create a dummy station on your laptop
    Copy the copied config.bog into the...
  15. Replies
    51
    Views
    2,349

    The full website address is :...

    The full website address is : "http://www.pecomanufacturing.com/assets/docs/datasheets/t180-t170-peco-data-sheet.pdf" hopefully it will not get shortened when I post this.

    I am not a "Trane" guy,...
  16. Replies
    51
    Views
    2,349

    A lot depends on your type of tenants, High end...

    A lot depends on your type of tenants, High end condo's you need to keep them happy at all times, doing the best you can with what you got. Section 8 buildings or similar, Heat Nov 15th until Mar...
  17. Replies
    51
    Views
    2,349

    Ideally the thermostats in the resident spaces...

    Ideally the thermostats in the resident spaces should know which mode the system is in, this can be done either of two ways, a communicating thermostat connected back to the control system (probably...
  18. Replies
    2
    Views
    407

    Good material for controls techs.

    Contemporary Controls has put together a book that contains various previously published articles and some updated stuff, it is titled Network Communications for Buildings, and covers in fairly fine...
  19. Replies
    2
    Views
    256

    I suggest that you ask your question in this...

    I suggest that you ask your question in this section: http://hvac-talk.com/vbb/forumdisplay.php?1-AOP-Residential-HVAC
  20. Replies
    14
    Views
    630

    Are you sure you are talking about the same...

    Are you sure you are talking about the same thing, the niagaraDriver device limit is for stations pulled in to the niagara network not Jaces on the navigation tree.
  21. Thread: EC BOS ?

    by klrogers
    Replies
    4
    Views
    231

    Or Platform Service container view

    Or Platform Service container view
  22. Replies
    8
    Views
    529

    Thanks for the links. I'm happy to help you or...

    Thanks for the links.

    I'm happy to help you or anyone out when I can, I have received help from many other members over the years and like to return the favor. Despite its occasional rants and...
  23. Replies
    8
    Views
    529

    "print index all" will give you a list of the...

    "print index all" will give you a list of the control drums

    then "p dr {drum #}" to display drum logic, I recommend capturing the output and printing it out if possible.

    You might want to "P...
  24. Replies
    8
    Views
    529

    Be careful using the edit command, you are...

    Be careful using the edit command, you are working on a live program :)
  25. Replies
    8
    Views
    529

    564511 See if this helps, thats from H...

    564511

    See if this helps, thats from H (Return)

    usually use something like "Print Drum 150" which can be shortened to "P DR 150"
  26. Replies
    7
    Views
    544

    Most FX-60's have the embedded WB, with that you...

    Most FX-60's have the embedded WB, with that you can do 90% of what you can do with the PC version.

    Kevin
  27. I have to agree with MatrixTransform the layout...

    I have to agree with MatrixTransform the layout of your stations is very important. I have though experience found that the time spent designing the stations before you even start building a station...
  28. Replies
    16
    Views
    720

    Jace ports might be changed from default

    Jace ports might be changed from default
  29. Turn on FTP (by shell access if needed), and FTP...

    Turn on FTP (by shell access if needed), and FTP in. Still need platform user and password but if you are in shell easy enough to reset.

    Kevin
  30. Replies
    17
    Views
    1,917

    If you want to get away from the JAVA issues use...

    If you want to get away from the JAVA issues use Hx or mobile app pages, either of these use JAVA.

    Kevin
  31. Replies
    4
    Views
    742

    Sounds like the perfect application for you to...

    Sounds like the perfect application for you to write a program object for :) It certainly can be done on a wire sheet but a PO would be much better and re-usable.
    There are some examples of PO's...
  32. If the set point editor is changing the "date...

    If the set point editor is changing the "date range" in the source node I would say that that part is probably working OK. I have attached screenshots of:
    1) Wiresheet with OAT source node property...
  33. One quick thought, do you have ALL the date...

    One quick thought, do you have ALL the date ranges on all the source nodes linked together? They all need to be on the same date range.
  34. Look at bit different this week ;) 555771:)

    Look at bit different this week ;)


    555771:)
  35. See if these help, I throw together a px page...

    See if these help, I throw together a px page using an existing seriesTranform set. When I change the date range, save and then hit refresh the graph updates. Now I know it would be better for it to...
  36. Replies
    6
    Views
    430

    You could something with the "alarmCountToRelay"...

    You could something with the "alarmCountToRelay" module in kitControl. Or something using a BQL statement.

    Kevin
  37. 550691 set point field editor from kitPx, this...

    550691

    set point field editor from kitPx, this screenshoot should help you see how it is attached to the transform graph. I don't now how you would use the "time range" choice, that would need to...
  38. You have to use the composite editor to expose...

    You have to use the composite editor to expose the time range slot, link the slots together so they all change, and use a "set point field editor" in your px view to change the time range on the...
  39. If you can upgrade to 3.7 it makes what you are...

    If you can upgrade to 3.7 it makes what you are trying to do much more practical, using a new module call seriesTranform.

    Kevin
  40. Thread: Fx60 login

    by klrogers
    Replies
    7
    Views
    334

    Resetting username/password in serial shell only...

    Resetting username/password in serial shell only changes the Platform username/password not the station username/password.

    I can't say much more on this open forum, particularly to a new member....
  41. Replies
    16
    Views
    1,642

    I can't believe that this post is getting so much...

    I can't believe that this post is getting so much attention, the PO is probably a DIY home owner ;)
  42. Replies
    9
    Views
    491

    Try here: 536791 Never really found a use...

    Try here:


    536791

    Never really found a use for a pie chart on a single history :)
  43. Replies
    11
    Views
    1,417

    That's a short sighted and old school quote from...

    That's a short sighted and old school quote from your office, unfortunately many customers are not informed enough about building automation and are blindsided into accepting such changes to THEIR...
  44. Honeywell Gray Manual is excellent for control...

    Honeywell Gray Manual is excellent for control strategies, but this http://www.enerlon.com/?wpsc-product=building-automation-control-devices-and-applications-hardcover-duplicate covers the more...
  45. Thread: Jace and SMS

    by klrogers
    Replies
    0
    Views
    264

    Jace and SMS

    Anyone using and can recommend a good external serial GPRS modem for use with a Jace to send SMS messages? We are currently using the Tridium supplied internal modem with a wireless SIM card and high...
  46. 522421Set up an alarm class lets say...

    522421Set up an alarm class lets say "BoilerFailAlarmClass", then route that to your email recipient (and console recipient usually). Use this new class it the set up of your alarm extension.
  47. +1, pity we can't do N2 tunnelling ;)

    +1, pity we can't do N2 tunnelling ;)
  48. You have to create identical alarm classes in...

    You have to create identical alarm classes in both the Jace and the Supervisor to use 'use existing'
  49. Do you have %alarmData.msgText% in the body of...

    Do you have %alarmData.msgText% in the body of your email recipient?

    Kevin
  50. Thread: HVAC Pro

    by klrogers
    Replies
    44
    Views
    3,791

    Get the B&B USOPTL4 and you can then connect...

    Get the B&B USOPTL4 and you can then connect directly on the N2 network, you should disconnect any other supervisory controls from the network, i.e. N30, FX60 etc. If you want to connect using the...