Search:

Type: Posts; User: M100 Tech

Page 1 of 3 1 2 3

Search: Search took 0.04 seconds.

  1. Replies
    15
    Views
    1,000

    No, it's not. We never setup the equipment. It's...

    No, it's not. We never setup the equipment. It's the installing contractors responsibility to prove that. I just did it because I knew how and had the software. Per our contract!
  2. Replies
    15
    Views
    1,000

    Well, its not in my scope to setup the Trane...

    Well, its not in my scope to setup the Trane Unit. Problem is I was the go to guy at Trane. I am going to pass this on the them to figure out. Its not my problem. Thanks for the help.

    Dewey
  3. Replies
    15
    Views
    1,000

    I have to wonder if I am Just thinking it is not...

    I have to wonder if I am Just thinking it is not controlling to setpoint because the compressor stages are not coming on. If I remember correctly, the 1st stage of cooling is economizer. I don't...
  4. Replies
    15
    Views
    1,000

    I am, it has a 69 deg zone temp and active zone...

    I am, it has a 69 deg zone temp and active zone temp setpoint of 65 (64 plus 1 deg offset) it's controlling to Dat setpoint which is out of service.
  5. Replies
    15
    Views
    1,000

    Next issue. This is a,single zone VAV profile. I...

    Next issue. This is a,single zone VAV profile. I can't seem to control it to zone temp.
  6. Replies
    15
    Views
    1,000

    BO-1 is enabled. I had to write a program to send...

    BO-1 is enabled. I had to write a program to send a value to the BCI-R every 3 minutes. Works like a charm.

    Thanks All!

    If I can help anyome, please ask.

    Dewey
  7. Replies
    15
    Views
    1,000

    I am not writing to the point continuously. I...

    I am not writing to the point continuously. I assume that is why I see a value and it shows failed. I know it reverts to the hard wired value after 900 seconds. But I would expect it to at least...
  8. Replies
    15
    Views
    1,000

    But it is, I have it scanned into and I can read...

    But it is, I have it scanned into and I can read all the values. It even controls to my setpoint. I have never seen this before. I have setup a lot of these of BCI's in the past at Trane.

    Dewey
  9. Replies
    15
    Views
    1,000

    BCI-R Integration

    Guys, I am about to pull my hair out. I am a former Trane Controls Service tech (15 years). I have TU and know how to use it. I am trying to integrate to a BCI-R in a voyager. Its a not DAC. I have...
  10. Replies
    29
    Views
    8,897

    BCI-I

    You "MUST" enable the points with Tracer TU with the BCI-I it is "NOT" like a BCI-C! Make Trane Come back and do it right!
  11. Replies
    13
    Views
    4,253

    BMTS and Arcnet

    Not all (actually most in my area) BMTS's have the rev 4 chip on them. You can get a device that will let you mix ARCNET and Ethernet. I have used them several times but the name escapes me right...
  12. Replies
    5
    Views
    1,740

    RTU

    Morganizer does this too with an MP581 and the CTI on the reliatel controls. The only way to tell what profile you have is to look at it with Rover or NL Util and get the prog ID! You are going down...
  13. What he said: "This chiller would be a UCP1,...

    What he said: "This chiller would be a UCP1, there's no BACnet interface available for this chiller, neither is LON for that matter. You'll need a BMTW BCU to serve you info.


    mallron
    View...
  14. Replies
    7
    Views
    2,513

    We are Native Bacnet now with a BCI-(I,C,R)

    We are Native Bacnet now with a BCI-(I,C,R)
  15. Replies
    7
    Views
    2,513

    You are refering to the Trane JCI 25 point Bacnet...

    You are refering to the Trane JCI 25 point Bacnet Template.
  16. Replies
    4
    Views
    1,007

    Webops! (nuf said)!

    1
  17. Replies
    29
    Views
    8,897

    BCI-I

    The IPAK BCI us setup for "custom" units. The BCI-C and UC800 can be changed with Tracer TU!
  18. Replies
    8
    Views
    1,776

    www.Comfortsite.com

    Everything you guys are asking for is available at Comfortsite. All you need to do is have either somenone at Trane or the Trane parts center set you up!
  19. Replies
    29
    Views
    8,897

    BCI-()

    Hold it cowboys! The BCI needs Tracer TU to properly setup. On an IPAK it is prett easy. On a CH-530 chiller, you will need the appropriate version of firmware in your device. You cannot just add a...
  20. Thread: Trane

    by M100 Tech
    Replies
    19
    Views
    3,133

    What?

    Are they Trane RTU's? If so, what are you doing writing CPL? You need to set each RTU's configuration to reference the appropriate setpoint you want to use. Never fear, BCI-R is on its way for...
  21. Thread: Carrier 19XR

    by M100 Tech
    Replies
    12
    Views
    1,548

    $1,000.00?

    Carrier charged a grand to flash the PSIO? I knew I should have kept downloader when I left Carrier. Just buy a new PSIO module!
  22. Replies
    26
    Views
    5,936

    Insulting Post

    I work for Trane and I am not Kissing Anyone's Arse!
  23. Replies
    26
    Views
    5,936

    Hit the little paper clip

    I am not going to send emails with attachemnts. I am talking about this website giving us a place to post them. :nopity::nopity:
  24. Replies
    26
    Views
    5,936

    Trane Service Bulletins

    As long as they are not CSB's (confidential) then there is no problem with anyone having it. Note to Webmaster: Can we get enough room to post pdf files of bulletins?

    dde
  25. Replies
    24
    Views
    2,568

    Be honest with yourself

    Does Microsoft give windows away? How are we supposed to recover the cost to develop the software? We (Trane) give more software away than anyone else! Have you ever heard of Tech View? It does not...
  26. Replies
    16
    Views
    2,523

    Comm 3 VAV's

    If you still need help with this email me offline! My email is in my profile!
  27. Replies
    2
    Views
    1,025

    Voyager

    DAC (Discharge Air Profile). If the unit has a VFD or inlet guide vanes it will be a DAC.

    SCC (Space Comfort Controller) If the unit is constant volume, it will be an SCC.

    You can flash either...
  28. Replies
    3
    Views
    1,454

    Comfort Site

    Each and everyone of you need to get setup on Comfort Site. All the manuals and more are there. You just need to get someone in your office or parts center to set you up!
  29. Replies
    11
    Views
    2,129

    Overrride

    Usually incoming request server is seen with a BACNET panel.
  30. Replies
    24
    Views
    2,568

    Do you have a reciept that shows you bought it?

    Do you have a reciept that shows you bought it?
  31. Replies
    24
    Views
    2,568

    Tracker 12

    Tracker software is not like Tracer Summit or Rover. It is "NOT" required that you register it. It is, however a sold product. Tech View is the Free one! You can copy Tracker 12 all day long, but it...
  32. Thread: Trane BCU

    by M100 Tech
    Replies
    20
    Views
    3,348

    They are available on Ebay

    They are available on Ebay
  33. Replies
    24
    Views
    2,568

    Tracker 12

    Guys, asking for a copy of software that is required to be purchased seems like a breach of the rules on this forum. Tracker 12 is something that is not "FREE"! If you want a copy, please purchase...
  34. Replies
    7
    Views
    2,995

    Calling Tech Support

    Guys, if you do not work for Trane, you can't just call tech support. The auth code will need to be released. It does just take a phone call but you are going to have to make a local phone call.
  35. Replies
    11
    Views
    1,043

    Stuck

    Try, clear ram and reset!
  36. Replies
    2
    Views
    1,401

    Probably not! You will find that if it is that...

    Probably not! You will find that if it is that old, several of the boards will need to be replaced.
  37. Thread: Trane Summit

    by M100 Tech
    Replies
    2
    Views
    749

    Good answer!

    Good answer!
  38. Replies
    8
    Views
    1,882

    Not supported on Windows 7 "yet"!

    Not supported on Windows 7 "yet"!
  39. Replies
    4
    Views
    753

    Yes you can!

    Yes you can!
  40. Thread: Trane BCU

    by M100 Tech
    Replies
    20
    Views
    3,348

    NIC Card

    If you actually have a BMTW (segmented display) then you can absolutely use an ethernet card. If the display shows P-, what do you intend to do with it?
  41. Replies
    5
    Views
    1,476

    BMTW Errors

    If you are "very" good with Tracer Summit then you can try this. If not, do yourself and your customer a favor and get someone who does. If you have totally lost the database, you will need to get it...
  42. Thread: TRANE

    by M100 Tech
    Replies
    4
    Views
    852

    Lon

    I have had similar problems and had to go actice with Rover and reformat the link.
  43. Replies
    5
    Views
    1,476

    Go dedicated ethernet and see if it will talk. If...

    Go dedicated ethernet and see if it will talk. If you just lost the program (database) replace the BRD1669 (standard cap card). But you would be better off just upgrading to a BMTX.
  44. Thread: Trane Comm3

    by M100 Tech
    Replies
    5
    Views
    1,726

    Well Put but not correct!

    Trane (we) are now shipping BCI's with chillers but they have to be CH-530 or UCP-3. RTAC chillers are CH530 not adaptaview. RTWD, CGAM etc... Pueblo is not moving to Adaptaview.
  45. Replies
    4
    Views
    3,568

    Its free from trane then go get a DB9 cable and...

    Its free from trane then go get a DB9 cable and you are in business. V12.1 SP2 is latest.
  46. Replies
    30
    Views
    8,518

    The Valley

    Only in the valley!
  47. Replies
    17
    Views
    3,488

    Techview is probably not your fix

    Techview will allow you to bind it. You need to make sure you have the correct .xif file for the prog ID that you are using. You may be using an extended profile or profile only. You can flash it...
  48. Replies
    8
    Views
    3,412

    Downloader Program

    You need the downloader program and not even the distributor has it. It is a very hard to get program at carrier. I have used it.
  49. Replies
    6
    Views
    1,745

    Trane parts

    Try our parts center. Ask for Brian or Walter.

    512-416-8822

    Austin, Texas
  50. Replies
    6
    Views
    1,745

    Please do not do that!

    You are not going to find one that will make you happy. I know ours is not cheap but there was a lot of engineering that went into it.

    dde
Results 1 to 50 of 103