    You are right. I should have clarified my...

    You are right. I should have clarified my remarks with adding Win 7 64-bit!:angel:
  2. Replies
    3
    Views
    341

    skidoox800, I think the world is still waiting...

    skidoox800,

    I think the world is still waiting for the version that works with Windows 7. So don't hold your breath!

    Actually I don't think it is possible, it has to do with the fact that...
  3. Replies
    12
    Views
    851

    I have a very similar problem. I have a ADX...

    I have a very similar problem. I have a ADX site. On one of the customers remote sites, they have an Alerton BCM array with Envision 2.01. I have gone in hyperterminal and enabled Bacnet/IP in the...
  4. Delta Controls integrate to Metasys ADS

    I am having issues pulling in the points to my NAE from a Delta controls server.

    I have pulled in the Delta server via a bacnet/IP integration. However, I cannot see the devices underneath the...
  5. Replies
    3
    Views
    628

    Thanks! The first response got the job done.

    Thanks! The first response got the job done.
  6. Replies
    3
    Views
    628

    JCI NCE stuck in startup

    An NCE has two sides to it, one is the NAE side and other is the field controller side. The field controller side (CCT) is stuck in startup, I cannot download, upload it or commission it-I have...
  7. Replies
    4
    Views
    438

    That is the rule of thumb-but beware the old...

    That is the rule of thumb-but beware the old school VMAs (1420), if use a bunch of those on one trunk >35ish you will need to change the COVs for your AIs to 0.5.