Search:

Type: Posts; User: El Presidente

Search: Search took 0.00 seconds.

  1. Replies
    3
    Views
    201

    3.8

    3.8
  2. Replies
    3
    Views
    201

    Vykon JEC-334 commissioning error

    Hello,

    I'm trying to commission this with 3.8.38 and am getting an nre-core dependency error saying I need to update. Must nre-core version match baja version?

    Pres

    579371579381
  3. Replies
    169
    Views
    37,785

    No. Just hyperterminal (old Windows XP etc.) or...

    No. Just hyperterminal (old Windows XP etc.) or some other terminal emulator like PuTTY for current versions of Windows and the cable. There really isn't any configuration of the actual gateway. No...
  4. Replies
    169
    Views
    37,785

    The Lon gateway uses a null modem cable with...

    The Lon gateway uses a null modem cable with custom pinout and hyperterminal. The cable is sold by the service department.

    Pres
  5. Replies
    169
    Views
    37,785

    Diego, See download link in previous post. ...

    Diego,

    See download link in previous post.

    Pres
  6. Replies
    7
    Views
    482

    Single setpoint through the gateway is a controls...

    Single setpoint through the gateway is a controls architecture limitation. The iTouch and iTouch Manager have the same limitation. To control independent setpoints they send out a new setpoint with...
  7. Replies
    0
    Views
    209

    Vykon Workplace AX 3.6

    Does anyone have the install package they can give me for 3.6? I have a temp license for 3.8 and I would like to un-FUBAR a demo JACE-6 I have.

    Pres
  8. Replies
    26
    Views
    4,210

    Does anyone know how to bind the result of a case...

    Does anyone know how to bind the result of a case block to a BACnet IP multistate output?

    Pres
  9. Replies
    169
    Views
    37,785

    Ethernet cable and computer running that...

    Ethernet cable and computer running that software. LG gateway is nice that you can commission with the LCD/buttons on the unit and built in web server.

    Pres
  10. Replies
    169
    Views
    37,785

    Latest version 6.34. Enjoy!! ...

    Latest version 6.34. Enjoy!!

    http://goo.gl/3uVF05

    Pres
  11. Try port 80. Pres

    Try port 80.

    Pres
  12. Replies
    9
    Views
    673

    Same way. Monitor space temp and override units...

    Same way. Monitor space temp and override units on when setback setpoints are reached. Back off after a set differential.
  13. Replies
    9
    Views
    673

    If it uses Java then it is the old gateway. Here...

    If it uses Java then it is the old gateway. Here is the IOM:

    https://www.dropbox.com/s/fr2gccnt2jqvd4f/MFL37115823_LG%20BACnet%20Old.pdf

    Are you sure the IDUs have been discovered by the...
  14. Replies
    169
    Views
    37,785

    Ok let's see if this works. This version is three...

    Ok let's see if this works. This version is three years old so not sure if it is even current anymore. If anyone has a more current version, send it to my email and I'll setup a new link.
    ...
  15. Replies
    169
    Views
    37,785

    August posters, check your mail. Anyone else, let...

    August posters, check your mail. Anyone else, let me know.

    Pres
  16. Replies
    169
    Views
    37,785

    Version I have is 6.201. Not sure if that is even...

    Version I have is 6.201. Not sure if that is even current anymore. Haven't used it since 2011. Who wants it?!

    Pres
  17. Thread: LG V-net

    by El Presidente
    Replies
    20
    Views
    2,252

    You're welcome! Let me know if you need anything...

    You're welcome! Let me know if you need anything else.

    Pres
  18. Thread: LG V-net

    by El Presidente
    Replies
    20
    Views
    2,252

    They work. I would take the BACnet over Lon. More...

    They work. I would take the BACnet over Lon. More functionality, more capacity, and less issues. They are both monitoring and control. You can see the points lists here:
    ...
  19. Thread: LG V-net

    by El Presidente
    Replies
    20
    Views
    2,252

    What do you want to know?

    What do you want to know?
  20. Replies
    6
    Views
    761

    You should see just a bunch of points. The number...

    You should see just a bunch of points. The number after the object name corresponds with the address in the stat. For example StartStopCommand_000 corresponds with group address 1-00. 001 is 1-01...
  21. Replies
    11
    Views
    3,744

    What gateway firmware version? If it is 1.x you...

    What gateway firmware version? If it is 1.x you just have to have the equipment connected to see the points. If it is 2.x you must go in through the webserver and perform a discovery within the...
  22. Thread: Can2Go

    by El Presidente
    Replies
    37
    Views
    8,058

    Graphical programming is available. Pres

    Graphical programming is available.

    Pres
  23. For Daikin you have to limit the writes for...

    For Daikin you have to limit the writes for changes of value. If you write On when the unit is already on every two seconds it is fine as the gateway will not actively write to the indoor unit EEPROM...
  24. BACnet - Excellent, this got all my points...

    BACnet - Excellent, this got all my points working except for MSI, MSO, MSV. Thanks!

    Xarralu - SCL Elements confirmed Multi-states will not be available until November Firmware update.

    Pres
  25. CAN2GO UN2 - BACnet readProperty Request

    Hi all,

    I'm trying to use this controller to run simulations and trend points on my VRF system through a BACnet gateway.

    Script syntax for the request is (device instance, object type and...
  26. Tridium --> LG Lon Gateway SNVT Type Size Mismatch

    I'm trying to help out a guy integrating Tridium and LG and he says for SNVT nvoUnitStatus, his system reports “Type Size Mismatch (13bytes). LonMark says this data type (hvac_status) should be 12...
  27. Replies
    11
    Views
    3,744

    Ok, thanks anyway. Pres

    Ok, thanks anyway.

    Pres
  28. Replies
    11
    Views
    3,744

    Type Size Mismatch

    hvaccontrolsguy,

    I'm trying to help out a guy integrating Tridium and LG and he says for SNVT nvoUnitStatus, his system reports “Type Size Mismatch (13bytes). LonMark says this data type...
  29. Replies
    11
    Views
    3,744

    What was the problem and how did you solve it? ...

    What was the problem and how did you solve it?

    Pres
  30. Replies
    13
    Views
    3,172

    Have each of the indoor units been assigned a...

    Have each of the indoor units been assigned a group address? If not, do that and then cycle power on the gateway.

    Pres
  31. Replies
    169
    Views
    37,785

    C, check your mail. threefiddy, my e-mail...

    C, check your mail.

    threefiddy, my e-mail bounced back. Not sure what the problem is.

    Pres
  32. Replies
    169
    Views
    37,785

    C, add an email to your profile. Pres

    C, add an email to your profile.

    Pres
  33. Replies
    169
    Views
    37,785

    threefiddy, check your mail. Pres

    threefiddy, check your mail.

    Pres
  34. Replies
    169
    Views
    37,785

    Ok, what's the IP address of the Jace? It will...

    Ok, what's the IP address of the Jace? It will have to be 192.168.0.X if the gateway is left at default IP of 192.168.0.1 without enabling the gateway as a foreign device.

    If it is on a different...
  35. Replies
    169
    Views
    37,785

    De nada and you're welcome.

    De nada and you're welcome.
  36. Replies
    169
    Views
    37,785

    amigo, check your mail. Pres

    amigo, check your mail.

    Pres
  37. Replies
    169
    Views
    37,785

    What IPs for the jace and the gateway? I'll send...

    What IPs for the jace and the gateway? I'll send you the setup tool.

    Pres
  38. Replies
    169
    Views
    37,785

    Stan, Can you ping the gateway but not...

    Stan,

    Can you ping the gateway but not discover points? Are you on a different subnet than the gateway? If so the gateway might have to be setup as a foreign device.

    Pres
  39. Ok, thanks. Pres

    Ok, thanks.

    Pres
  40. Replies
    3
    Views
    2,614

    You're welcome. Pres

    You're welcome.

    Pres
  41. Replies
    3
    Views
    2,614

    That is correct. The P1-P2 (remote controller)...

    That is correct. The P1-P2 (remote controller) communications bus can handle two remote controllers max, a main and a sub. The KRP4A acts like the sub.

    Pres
  42. Reliable Controls Autodiscovery Pulls in MI from Daikin GW as Open/Closed

    Reliable Controls communicating BACnet IP to a Daikin gateway. Mode status point should have a Present Value of 1, 2, or 3 for Cooling, Heating, or Fan respectively. The point is pulled in as...
  43. Replies
    7
    Views
    2,493

    I believe event notification has to be enabled...

    I believe event notification has to be enabled with the setup tool. Ill double check when I get back from vacation.
  44. Replies
    48
    Views
    21,702

    That depends on your expectations. The ASHRAE HQ...

    That depends on your expectations. The ASHRAE HQ Renovation done recently was ALC with WebCTRL and turned out pretty good.

    How about you describe what issues you are having with the Mitsubishi...
  45. Replies
    48
    Views
    21,702

    The Daikin VRV does! :D

    The Daikin VRV does! :D
  46. Replies
    169
    Views
    37,785

    You're welcome.

    You're welcome.
  47. Replies
    169
    Views
    37,785

    There is no point configuration in the gateway....

    There is no point configuration in the gateway. The excel file is for generating a points list including object IDs and instance numbers. This is typically useful for integrators who cannot...
Results 1 to 47 of 47

Related Forums

Plumbing Talks | Contractor MagazineThe place where Electrical professionals meet.
Comfortech365 Virtual Event