  1. Replies
    3
    Views
    803

    "@1#4231; 1 is the functional block index and...

    "@1#4231;
    1 is the functional block index and 4231 is the member number

    "&1,3,0\x80
    CP definition, but appears to be incomplete

    "~1,1,4\x80
    "$1#4316;
    These ones are proprietary I think
  2. Thread: Pyxos Nodes

    by gmha9x
    Replies
    0
    Views
    632

    Pyxos Nodes

    I noticed at LonWorld that the distributors are selling the Pyxos chips now. Has anyone seen any HVAC Pyxos nodes yet, temperature sensors or actuators? I spoke to a few of the bigger manufacturers...
  3. Replies
    10
    Views
    4,607

    0x55

    0x55
  4. Replies
    10
    Views
    4,607

    All standard properties also have a unique...

    All standard properties also have a unique identifier. There are about 200 of them, so if you can tell us which ones you are interested then we can tell you the identifiers. I do not want to type...
  5. Replies
    14
    Views
    2,115

    Honeywell does not have access to the core source...

    Honeywell does not have access to the core source code. Nor does Honeywell get any preferential treatment for getting new features into AX.
  6. Replies
    8
    Views
    3,035

    drafty888, are you using EBI BACnet server or...

    drafty888, are you using EBI BACnet server or BACnet client?
    BACnet client supports auto discovery, whereas BACnet server requires manual configuration.
    BACnet client supports intrinsic and...
  7. Replies
    13
    Views
    1,435

    Do you have access to a JACE running AX 3.2? It...

    Do you have access to a JACE running AX 3.2?
    It supports IP-852 connections, and an i.LON100e3 with IP-852 option should work with this.
  8. Thread: BACnet

    by gmha9x
    Replies
    34
    Views
    3,915

    I have attended each and every official BACnet...

    I have attended each and every official BACnet Interoperability Workshop in NAR and Germany and I would say that there are two levels to compare BACnet devices on:
    1) The application which is in the...
  9. Replies
    9
    Views
    843

    Sorry, I see that you are using Global Schedules...

    Sorry, I see that you are using Global Schedules so you must be using Excel 5000 point server. On the CD, you will have a readme.txt file which describes the limitation:

    Excel 5000 Direct...
  10. Replies
    9
    Views
    843

    Are you talking to this controller via the...

    Are you talking to this controller via the LonWorks Point Server or the Excel 5000 point server?
    If the controller status shows as OK, then you can assume that the physical communication to the...
  11. Thread: Alerton BCM-ETH

    by gmha9x
    Replies
    2
    Views
    1,850

    I think that there are some timeout problems with...

    I think that there are some timeout problems with EBT when trying to put the controller into BACnet restore mode. I found that if the download fails, then you need to wait a few minutes before trying...
  12. Replies
    6
    Views
    1,272

    I received a demonstration of WebStat, and it...

    I received a demonstration of WebStat, and it looks really easy to use. There was a huge focus on improving the usability of the user interface and making the workflow as natural as possible.
    ...
  13. Thread: SQL Server

    by gmha9x
    Replies
    5
    Views
    654

    The user is the user in the SQL database, you can...

    The user is the user in the SQL database, you can use the standard sa userr or create your own one. Either way it needs to be a user that can access the database.
  14. Thread: SQL Server

    by gmha9x
    Replies
    5
    Views
    654

    Add a rdbmsNetwork and then an SQLServerDatabase....

    Add a rdbmsNetwork and then an SQLServerDatabase. The settings should be straight forward, such as database, user etc.
  15. Replies
    11
    Views
    2,687

    I have used all three of these protocol...

    I have used all three of these protocol analyzers. Excelon is the best from a user interface perspective. LPA is fantastic for centralized monitoring (if you use Loytec routers), LonScanner needs a...
  16. Replies
    19
    Views
    3,425

    Well done!

    Well done!
  17. Replies
    19
    Views
    3,425

    Also, if you are really keen, you can make this...

    Also, if you are really keen, you can make this cable yourself. It just has a MAX233ACWP RS232 multichannel receiver/driver chip in it. Let me know if you want the pinouts.
  18. Replies
    19
    Views
    3,425

    dsirdah, It is from Honeywell which I bought my...

    dsirdah,
    It is from Honeywell which I bought my cable, and this is where I would be getting you one from. BTW, I am not likely to be in the same country as you.
  19. Thread: hw care 2.02

    by gmha9x
    Replies
    4
    Views
    546

    The project could be corrupt or could be from a...

    The project could be corrupt or could be from a later version of CARE. Are you sure it is from CARE 2.02?
  20. Replies
    14
    Views
    1,331

    I think that all of the vendors see the...

    I think that all of the vendors see the advantages of having products in both camps. Even Loytec is making BACnet products now.
  21. Replies
    19
    Views
    3,425

    Hah, Honeywell bought Alerton. You can buy this...

    Hah, Honeywell bought Alerton. You can buy this cable through your control products divison. This part number should be in the order system.
  22. Replies
    21
    Views
    4,845

    I am not quite sure what version you are...

    I am not quite sure what version you are referring to here.
    XBSi version should be around 2.X.X
    Excel Plus should be at least 15.X
    The gateway will have firmware in the communication and...
  23. Thread: hw care 2.02

    by gmha9x
    Replies
    4
    Views
    546

    Select Restore from the Project pull down menu...

    Select Restore from the Project pull down menu and then select the *.pjt file. This will restore the CARE project backup. pra is the project administration file and would be part of a controller...
  24. Replies
    19
    Views
    3,425

    where abouts are you located dsirdah

    where abouts are you located dsirdah
  25. Replies
    14
    Views
    1,331

    Back to the original post, I think that you would...

    Back to the original post, I think that you would find more training being delivered for LonWorks rather than BACnet. The same could be said for the number of product applications available as well,...