11-14-2010, 08:15 PM
Thread: Water Treatment Questions Welcome!
by triggerhappy- Replies
- 61
- Views
- 6,532
Now that my friend is quite an impressive...
Now that my friend is quite an impressive document.
Thanks you. -
10-14-2010, 03:25 PM
Thread: Trane CVHE230
by triggerhappy- Replies
- 22
- Views
- 1,385
L99H0313M Is that serial # correct. I could not...
L99H0313M
Is that serial # correct. I could not find that #. -
10-14-2010, 02:45 PM
Thread: Trane CVHE230
by triggerhappy- Replies
- 22
- Views
- 1,385
Lift is the difference between the evap. ref....
Lift is the difference between the evap. ref. pres. and the cond. ref. pres.
-
10-14-2010, 11:13 AM
Thread: Trane CVHE230
by triggerhappy- Replies
- 22
- Views
- 1,385
I would have to guess by the size that the...
I would have to guess by the size that the machine is fairly old (don't see to many small machines being commisioned now days) Need the first three digits of the serial #.
But if it is a current... -
07-03-2010, 01:04 PM
Thread: Big Fan Bearing Argument
by triggerhappy- Replies
- 10
- Views
- 836
Good point. I hope that it was a misprint,...
Good point.
I hope that it was a misprint, because the one that I did with those instructions I called it done at 9. -
07-03-2010, 08:43 AM
Thread: Big Fan Bearing Argument
by triggerhappy- Replies
- 10
- Views
- 836
check this out.
check this out.
-
03-05-2010, 05:45 PM
Thread: RTAA Service bulletins
by triggerhappy- Replies
- 12
- Views
- 1,262
Check your email.
Check your email.
-
12-03-2009, 06:31 PM
- Replies
- 23
- Views
- 5,104
60872 Or try this you said that you are in the...
60872
Or try this you said that you are in the 8th grade??????????/
Maybe the first was a little to simple for you. -
12-03-2009, 06:23 PM
- Replies
- 23
- Views
- 5,104
60862 Check this out. If you put your email...
60862
Check this out.
If you put your email in your profile bigger things can be sent. -
10-21-2009, 02:19 PM
Thread: CVHF ???
by triggerhappy- Replies
- 15
- Views
- 1,027
Carrier Mech, I got my motor out yerterday and I...
Carrier Mech,
I got my motor out yerterday and I took some good pics. of the discharge volute flange surface that where the oring seats.
Purposely I took the pics. very big aprox. 2 meg. so that... -
10-18-2009, 07:25 PM
Thread: CVHF ???
by triggerhappy- Replies
- 15
- Views
- 1,027
Glad to hear that the job went well. It is bad...
Glad to hear that the job went well. It is bad that the kit was misleading with the extra parts.
I will have my next motor out by Wed. or Thurs. of this week and it is an 97 and I am sure that it... -
10-14-2009, 07:25 AM
Thread: CVHF ???
by triggerhappy- Replies
- 15
- Views
- 1,027
You should be able to push the motor up to the...
You should be able to push the motor up to the flange by hand if it is floating on the guide bolts. The fit is not that tight it should push up right against the flange. Expecially with that small of...
-
10-13-2009, 09:33 PM
Thread: CVHF ???
by triggerhappy- Replies
- 15
- Views
- 1,027
There is not a grove on the motor you just slide...
There is not a grove on the motor you just slide the oring over the end of the motor and there is a lip on the discharge volute that the oring goes up into.
That is to say that there is a lip that... -
10-13-2009, 09:02 PM
Thread: CVHF ???
by triggerhappy- Replies
- 15
- Views
- 1,027
From what I see this machine does in fact have an...
From what I see this machine does in fact have an oring for the motor to discharge volute.
It is # 29 in the lit. that came in the motor change out kit. There should be 2 different orings in the kit... -
10-13-2009, 12:17 PM
- Replies
- 5
- Views
- 1,113
I am not sure what you are asking. My example...
I am not sure what you are asking.
My example was with the pump off.
Still the pump only has to have the head to overcome the resistance in the loop like piping losses, coil drops, chiller drop.... -
10-13-2009, 11:50 AM
- Replies
- 5
- Views
- 1,113
For every 2.307 ft of head in the water pipe...
For every 2.307 ft of head in the water pipe equals 1 psi.
The pump is mearly overcoming the resistance in the loop.
If you turn off the pump you will get your standing static pressure.
It could... -
09-19-2009, 04:19 PM
Thread: Helium?
by triggerhappy- Replies
- 9
- Views
- 738
There are companies that you can get to rent...
There are companies that you can get to rent their equiptment and operator.
The one we use is from up north somewhere, we have used a couple of times on absorbers.
I have also seen it used on... -
09-04-2009, 06:25 AM
Thread: Need some help with CH530
by triggerhappy- Replies
- 3
- Views
- 434
It does not come standard with either Comm4 or...
It does not come standard with either Comm4 or Comm5.
It is and option and you have to select if you want the Comm module to be 4 or 5 when you order.
You can bind and program either one in.
... -
08-07-2009, 06:42 PM
Thread: RTHD Trace 530 Temp Sensor Question
by triggerhappy- Replies
- 5
- Views
- 423
That's right..... of course you can pay an arm...
That's right..... of course you can pay an arm and leg from Trane and it will have a cool little logo on it. :)
-
08-07-2009, 05:28 PM
Thread: RTHD Trace 530 Temp Sensor Question
by triggerhappy- Replies
- 5
- Views
- 423
I would suggest that you get the Literature on...
I would suggest that you get the Literature on Techview and CH530.
They will tell you step by step how to do what you want to do.
It is pretty involved if you are starting from scratch.(way to... -
08-06-2009, 03:13 PM
Thread: Trane splicer/crimping tool
by triggerhappy- Replies
- 7
- Views
- 585
I hope that what I replied was not confusing. ...
I hope that what I replied was not confusing.
The KIT07957 is the splice kit that contains two connectors, tube of glue, several end caps and about 12 inches of cable.
That is what I buy in... -
08-05-2009, 02:30 PM
Thread: Trane splicer/crimping tool
by triggerhappy- Replies
- 7
- Views
- 585
kit07957 that is the # for the kit you need to...
kit07957
that is the # for the kit you need to splice in a llid. -
08-04-2009, 01:16 PM
Thread: Frozen impeller
by triggerhappy- Replies
- 10
- Views
- 517
Wtih the $ amounts that you described. My...
Wtih the $ amounts that you described.
My suggestion would be to take it to the motor shop and let them remove the impeller. -
07-30-2009, 04:09 PM
Thread: Older CVHE with CH531
by triggerhappy- Replies
- 2
- Views
- 266
My guess is that you need to update the software....
My guess is that you need to update the software.
There was a version of software that would loose configuration and both machine start and hours along with purge pumpout time on power failure -
07-27-2009, 02:00 PM
Thread: Loop Checks & Hot Loop Checks?
by triggerhappy- Replies
- 2
- Views
- 363
I assume you are talking about this in relation...
I assume you are talking about this in relation to Commissioning of a controls job.
If so maybe you would get more response out of the Controls Forum.
Results 1 to 25 of 308