Search:

Type: Posts; User: climpro

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Replies
    7
    Views
    1,675

    http://www.trane.com/Commercial/LiteratureSearchLi...

    http://www.trane.com/Commercial/LiteratureSearchList.aspx
  2. Replies
    6
    Views
    1,421

    its cvhf-091 s\n L -02d0620651, ch-530...

    its cvhf-091 s\n L -02d0620651, ch-530 panel,leak tested thursday,recovery 1800 lbs R-123,changed elbow o-rings (RNG-1056,RNG-1107) and economiser flat gasket ( GKT-1925) just finished job...
  3. Replies
    6
    Views
    1,421

    trane cvhf-091 suction elbow leak

    leak = flanche suction elbow to evap, removed loctite , rust with fiber disk and acetone. what s best sealant,loctite 515 ,dowcorning 111, or gortex? I know no loctite 515 suction elbow...
  4. Replies
    23
    Views
    2,463

    call benshaw canada tech support = 1-519 291...

    call benshaw canada tech support = 1-519 291 5112 damn good support! http://www.benshaw.com/benshaw_canada.asp
  5. R-123 is HCFC , OEM phase-out = 01-01-2010...

    R-123 is HCFC , OEM phase-out = 01-01-2010 ?? what,s the future of R -123 ??????
  6. trane centravac chiller best-of the best award ??

    EPA has selected TRANE hcfc-123 centravc chiller for contribution to the protection of the ozone layer and climate changes ...
  7. Replies
    11
    Views
    910

    abs could you send me a copy my email is in my...

    abs could you send me a copy my email is in my profile

    thanks

    clim
  8. Replies
    16
    Views
    5,235

    BBusby i have a pdf copy 160.55-m1 form ...

    BBusby i have a pdf copy 160.55-m1 form optiview service instruction
  9. Replies
    58
    Views
    13,872

    esornivram I wanna installed txs on voyager...

    esornivram


    I wanna installed txs on voyager , send me youre jpgs and
    info my email is in my profile

    thanks

    clim
  10. Replies
    58
    Views
    13,872

    abs, I need your york tech support email and...

    abs,

    I need your york tech support email and phone .My email is in my profile

    Thanks

    Clim
  11. Replies
    17
    Views
    4,120

    deal

    deal
  12. Replies
    17
    Views
    4,120

    this service M manual isn,t available on www...

    this service M manual isn,t available on www york. com
  13. Replies
    0
    Views
    1,006

    york optiview 160.81-M1

    i need a pdf copy of this service teck manual =160.81-m1 ,it,s not available on www .YORK. com would you send my email is in my profile

    thanks

    clim
  14. Replies
    17
    Views
    4,120

    it,s rotary screw liquid chiller model=...

    it,s rotary screw liquid chiller model= yrbwbat2-53as s/n=snnm580292 , optiview controler ,solid state starter
  15. Replies
    17
    Views
    4,120

    optiview service manual

    Hey out there
    I have missed place my copy of service instruction 160.81-mi optiview service teck manual does any one have this in pdf
    let me know my email

    Climpro

    Thanks
  16. Replies
    13
    Views
    4,670

    scott 123 you,re Bolan trane guys?????

    scott 123

    you,re Bolan trane guys?????
  17. Replies
    14
    Views
    1,527

    pressure drop thru trane condensor coil is 30-50...

    pressure drop thru trane condensor coil is 30-50 psi (subcooling coil )higher amb temp +higher comp load=higher press drop
  18. mc1647 after youve changed oil filter got diag...

    mc1647 after youve changed oil filter got diag oil press transducer,set net oil pressure =22psid if transducer see 30psi youll get this diag , u need service bulletin cvhe-sb -32a ask copy...
  19. Thread: RTAC185

    by climpro
    Replies
    15
    Views
    1,631

    log teckview ,configuration window,starter,...

    log teckview ,configuration window,starter, desable test integrity and load configuration
  20. Replies
    8
    Views
    1,258

    LON card for ucp-2 rthb chiller isnt avalable ...

    LON card for ucp-2 rthb chiller isnt avalable from trane ,you must retrofit with ch-530 controls,this is the answer from factory trane pueblo ,i have same problem,expensive answer$$$$$$ stay with...
  21. Replies
    4
    Views
    1,680

    belimo parts =lf24-3r us ,it must be a 90 sec...

    belimo parts =lf24-3r us ,it must be a 90 sec opening motor
  22. Replies
    37
    Views
    4,086

    outside rep call Roger Richmond Smith...

    outside rep


    call Roger Richmond Smith ,Danfooss-Turbocor inc in Montreal phone= 1-514-421-0523,you,il know truth
  23. Replies
    37
    Views
    4,086

    I dont hav more info talk of town in LAX

    I dont hav more info talk of town in LAX
  24. Replies
    37
    Views
    4,086

    outside rep do you know why Multistack stop...

    outside rep


    do you know why Multistack stop production of Turbo-core on there chillers ????????
  25. Replies
    2
    Views
    1,233

    tigger i have 2 trane chiller model cckc-040 ...

    tigger
    i have 2 trane chiller model cckc-040 heat recovery with w-7100g controler,it,s old technology ,i had tried reset , problems oil return ,oil lost ,lock-out guard-pack , dont know...
Results 1 to 25 of 50
Page 1 of 2 1 2
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine