Search Results - HVAC-Talk: Heating, Air & Refrigeration Discussion

Search:

Type: Posts; User: GYUR22

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. We have another device - Modbus RTU cards for...

    We have another device - Modbus RTU cards for FX14/15/16 and FX07, so it's possible to use any Modbus TS
  2. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    919

    yes you need the image files with your version

    yes you need the image files with your version
  3. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    919

    Try to reflash w NUT

    Try to reflash w NUT
  4. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    919

    smallest file ;)

    smallest file ;)
  5. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    919

    Check this:...

    Check this:
    http://files.mail.ru/77A89297009D4C509869F52DC69A8212
    p.s. I can't attach file to message
  6. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    919

    looks like security system issue, check if you...

    looks like security system issue, check if you can use remote desktop
    ps ask guys from local JCI they shoud know
  7. Replies
    1
    Views
    302

    both because consists of two independent devices

    both
    because consists of two independent devices
  8. Replies
    5
    Views
    521

    1. remove associated w nae55 files from tftp...

    1. remove associated w nae55 files from tftp directory
    2. unzip from archive all files again
  9. Thread: NCE Question

    by GYUR22
    Replies
    23
    Views
    1,072

    1. NAE part Recomended object quantity on NAE...

    1. NAE part
    Recomended object quantity on NAE part of NCE :2500objects - including network objects
    Recomended network objects per ms/tp or n2 trunk : 1000
    So for example 1000 network objects...
  10. Replies
    6
    Views
    1,623

    yes http://files.mail.ru/237EN4

    yes

    http://files.mail.ru/237EN4
  11. Thread: FX05

    by GYUR22
    Replies
    1
    Views
    441

    NO mstp on Fx05,06 only on FX07

    NO mstp on Fx05,06
    only on FX07
  12. Thread: NAE animations

    by GYUR22
    Replies
    6
    Views
    525

    You need Advanced graphics package (it's a Visio ...

    You need Advanced graphics package (it's a Visio plugin) to make your own animation
    or only standart graphic with it's animated fan only
  13. Because of FEC for NCE and it's display siting on...

    Because of FEC for NCE and it's display siting on this bus
  14. As I can understand McQuay is third party...

    As I can understand McQuay is third party equipment for MSEA.
    You should try- go to Integration
    1.Add Field bus (if you have it don't need)
    2.Then add Bacnet on Field bus
    3. Scan network
  15. Replies
    3
    Views
    460

    I think you should care about M-Authorize patch,...

    I think you should care about M-Authorize patch, file name - M_Authorize 5.4.30 Patch.EXE (I can e-mail it)

    Bad thing that you need authorize M3 again
  16. Thread: JCI M3i

    by GYUR22
    Replies
    1
    Views
    462

    I have some installations My opinion - works...

    I have some installations
    My opinion - works well
    M-Graphics - perfect
    other parts M-alarm, M-Trend, etc- not so convinient
    EDE OPC- good convinient tool
    BACnet OPC - I have not BACnet systems...
  17. Replies
    9
    Views
    1,271

    You need YES or ICE and programm file for it

    You need YES or ICE and programm file for it
  18. Thread: FX upload

    by GYUR22
    Replies
    4
    Views
    576

    controllers like - FX16X - possible to upload,...

    controllers like - FX16X - possible to upload, FX16D - NOT
    They are even different in hardware
  19. Replies
    16
    Views
    4,989

    This may help

    This may help
  20. Thread: NAE issue

    by GYUR22
    Replies
    25
    Views
    1,155

    Try to put BACnet integration with you Fieldbus...

    Try to put BACnet integration with you Fieldbus as parent then discover
  21. Replies
    5
    Views
    649

    Thank you

    Thank you
  22. Thread: MS/TP under NAE

    by GYUR22
    Replies
    20
    Views
    1,434

    I tested York CX UDC on NAE R3.1 MS/TP trunk -...

    I tested York CX UDC on NAE R3.1 MS/TP trunk - it works
    but it was only a test not serious job
  23. Replies
    12
    Views
    1,156

    Objects restrictions: NAE35,45 - 2500 NAE55...

    Objects restrictions:
    NAE35,45 - 2500
    NAE55 -5000
    This mean overall objects in NAE

    I think you better go cgproducts.johnsoncontrols.com and search docs with words like: NAE, MSEA

    ps Example...
  24. Replies
    5
    Views
    649

    ddcfreek, Salmon_king Thank you I already have...

    ddcfreek, Salmon_king
    Thank you I already have xif and profile but not shure in exact variables
    for example CurrentA and CurrentD?
  25. Replies
    12
    Views
    1,156

    I have no statistics on NAE MS/TP, only N2...

    I have no statistics on NAE MS/TP, only N2 (previous experience on MS/TP was on Connexsys controllers)
    Every thing depends on points quantity, as for me ~ 1000 points or less per trunk and router...