Search:

Type: Posts; User: Chinna

Page 1 of 2 1 2

Search: Search took 0.02 seconds.

  1. Replies
    9
    Views
    584

    sorry that i forgot, sometimes during this...

    sorry that i forgot, sometimes during this process, the engine password is getting messed up if you are using NAE of version "6.0.0.9100" and above....check the document once if you are at this...
  2. Replies
    9
    Views
    584

    Remote into NAE, in the command prompt type...

    Remote into NAE,

    in the command prompt type "changemodel" and enter....it will show a message that previous model was NAE55xx and current model is NIE55xx and will reboot automatically....
  3. Replies
    2
    Views
    595

    Windows 8 was tested with Metasys release 6.1,...

    Windows 8 was tested with Metasys release 6.1, which version of controller were you browsing ?
  4. Replies
    14
    Views
    804

    I was running wireshark in the site director...

    I was running wireshark in the site director server to figure the problem out
  5. Replies
    14
    Views
    804

    I was having a problem of similar kind and when...

    I was having a problem of similar kind and when looked at closely it happened to be a BACnet device which was broadcasting time once in a while which makes them to try to sync their time with the...
  6. Replies
    16
    Views
    1,293

    I use SA-T, OA-T, OA-H, SF-S, SF-C, RF-C, RA-T...

    I use SA-T, OA-T, OA-H, SF-S, SF-C, RF-C, RA-T etc.....
  7. Replies
    4
    Views
    408

    Insert Control System and create your Logic after...

    Insert Control System and create your Logic after that.
  8. Replies
    4
    Views
    408

    You nailed it :)

    You nailed it :)
  9. Replies
    3
    Views
    558

    Hello Stan MEU 5.1 version will work on...

    Hello Stan

    MEU 5.1 version will work on Windows 7 64 bit with no problem. Post the error message if you are getting something...

    Chinna
  10. Replies
    5
    Views
    538

    this is strange....have never seen like that...

    this is strange....have never seen like that before...probably a screenshot may help to understand ??
  11. Replies
    5
    Views
    538

    NCE has more IO points than a FEC 2611, more over...

    NCE has more IO points than a FEC 2611, more over it was recommended for Central plant application by JCI...

    there is no object count limit for the FEC but depends upon the system capacity of...
  12. Thread: NCE Question

    by Chinna
    Replies
    23
    Views
    1,350

    COV happening for the points in NCE, you can...

    COV happening for the points in NCE, you can check it at the "Diagnostics" tab of NCE....find out the value COV/min..
  13. Replies
    19
    Views
    2,715

    ::DD:

    ::DD:
  14. Thread: NCE Question

    by Chinna
    Replies
    23
    Views
    1,350

    You got it !

    You got it !
  15. Thread: NCE Question

    by Chinna
    Replies
    23
    Views
    1,350

    so, you haven't used JCI literature...

    so, you haven't used JCI literature repository...i mean the product documentation website ?

    i can send a private message of that URL to you...but i don't see an option to send PM :(
  16. Replies
    6
    Views
    492

    There is a attribute in NAE called "Last Archive...

    There is a attribute in NAE called "Last Archive date" there you can see it....and also i think if you remote into the NAE the next morning, the archive.MOI file may have the updated time ( i mean...
  17. Thread: NCE2566 Metasys

    by Chinna
    Replies
    6
    Views
    651

    Hmm, it appears your FEC has more points which i...

    Hmm, it appears your FEC has more points which i believe is the reason for your problem.....check the system capacity if you can open the FEC caf file in CCT...
  18. Thread: NCE2566 Metasys

    by Chinna
    Replies
    6
    Views
    651

    All the NCE's are a supervisory device +...

    All the NCE's are a supervisory device + FEC.........

    i think you have the same question in almost all the threads......please send me your archive...i would like to see....may be able to answer...
  19. Thread: Urgent NCE?

    by Chinna
    Replies
    2
    Views
    327

    after you add any field device to NCE, the Object...

    after you add any field device to NCE, the Object count increases.....so the CCT objects are called as "mapped objects" in NCE...

    please post a screen shot for better understanding :cool:
  20. Thread: NCE Question

    by Chinna
    Replies
    23
    Views
    1,350

    Are you a customer of JCI or field engineer ?

    Are you a customer of JCI or field engineer ?
  21. Thread: JC Tech Support

    by Chinna
    Replies
    14
    Views
    972

    to the FX questions....i think that is the...

    to the FX questions....i think that is the communication channel :o
  22. Thread: Cpu Usage @100%

    by Chinna
    Replies
    16
    Views
    1,053

    Is there a way you can send me your archive, I...

    Is there a way you can send me your archive, I ain't no third party vendor....so u can trust me on privacy.....I am JCI employee only....
  23. Thread: JC Tech Support

    by Chinna
    Replies
    14
    Views
    972

    JCI has introduced something called "Connected...

    JCI has introduced something called "Connected Community" with Panoptix...i think that is more like online chat/forum kind :D , not sure is it available with Metasys or not ? :notme:
  24. Replies
    30
    Views
    5,030

    I would appreciate a copy as well, thanks. E-mail...

    I would appreciate a copy as well, thanks. E-mail is in my profile.

    Chinna
  25. Replies
    7
    Views
    485

    hmm, it is not really right in top of my head, i...

    hmm, it is not really right in top of my head, i would first start looking at the device (FEC)....if not, then at the integration object....

    i will let you know in a while
Results 1 to 25 of 50