Search:

Type: Posts; User: RoadRunner

Page 1 of 2 1 2

Search: Search took 0.01 seconds.

  1. Replies
    5
    Views
    1,106

    Yes there is a base setup (Macro). If this drive...

    Yes there is a base setup (Macro). If this drive is on a pump or ahu, I would bet the farm that it is set for the HVAC macro. If so, unless someone has altered some of the parameters, it will auto...
  2. Replies
    3
    Views
    604

    w~p You will have to call johnson controls for...

    w~p

    You will have to call johnson controls for the part number on this. They havent sold these Obsys dongles in quite a while and barely still support it. They are available however through the...
  3. Replies
    3
    Views
    604

    Hardlock? Are you talking about the dongle for...

    Hardlock? Are you talking about the dongle for York ISN Facility Manager?
  4. Replies
    5
    Views
    972

    That setup and wiring should work. Make sure JP56...

    That setup and wiring should work. Make sure JP56 on the Micro is set to EMS and not modem. JP58 on the Micro needs to be set to 485 and not 232 as well. Set the chiller rotary ID switch on the...
  5. Replies
    5
    Views
    972

    Is this an OptiView or a one line panel? What...

    Is this an OptiView or a one line panel? What port are you coming off the ELink to the chiller? What port and terminal's did you land to on the MicroBoard from the Elink? What port is the 3rd party...
  6. You have mail.

    You have mail.
  7. Is it a MicroGateway or an E-Link? Does the CCN...

    Is it a MicroGateway or an E-Link?
    Does the CCN talk directly to the MicroGateway/E-Link?
    If it is a MicroGateway, what is the last 3 digits in the eeprom part number?
  8. Replies
    22
    Views
    1,902

    .

    .
  9. Replies
    22
    Views
    1,902

    .

    .
  10. Replies
    22
    Views
    1,902

    The York interface you speak of will either be a...

    The York interface you speak of will either be a MicroGateway or the new version called an E-Link. Both have a QuickStart setup that has to be perfomed and then should start talking to your third...
  11. Replies
    5
    Views
    1,938

    TomT, The Pathfinder is merely a router...Just...

    TomT,

    The Pathfinder is merely a router...Just part of what I would guess, is a large network, given the fact a Pathfinder is even being used. It has no logic what so ever. How many nodes or...
  12. Replies
    5
    Views
    1,938

    I may be able to help you...you need info on the...

    I may be able to help you...you need info on the Pathfinder or ISN?

    Bill
  13. Replies
    15
    Views
    1,732

    Use nothing but 567 here...

    Use nothing but 567 here...
  14. Replies
    5
    Views
    3,373

    You have mail. Bill

    You have mail.

    Bill
  15. Replies
    5
    Views
    3,373

    Whats you e-mail and model number of the screw...

    Whats you e-mail and model number of the screw chiller?

    Bill
  16. Replies
    2
    Views
    1,014

    Mod, Lon and Bacnet protocol's are availible and...

    Mod, Lon and Bacnet protocol's are availible and are all viable options. Ascii, ISN and N2 are availible as well. Depends on what protocol your Honeywell system talks or can talk. They all send and...
  17. Replies
    2
    Views
    711

    Your best bet is to drill through the hub and...

    Your best bet is to drill through the hub and each blade where they come into the hub and put a stainless steel screw through it. I have done a bunch of these and it works fine. About a 3/16th inch...
  18. Replies
    26
    Views
    3,086

    They closed the factory store???

    They closed the factory store???
  19. Replies
    23
    Views
    2,565

    Reset the VSD?....did it, or does it have a fault...

    Reset the VSD?....did it, or does it have a fault now? What type of fault needs to be reset?
  20. Replies
    3
    Views
    1,218

    Baker Distributing (Baker Bros.) is the product...

    Baker Distributing (Baker Bros.) is the product and parts dealer here in Florida. Hope this helped!

    http://www.bakerdist.com/products/line_card_1.asp
  21. Replies
    208
    Views
    30,758

    Streetsmart, where did you hear that? I would...

    Streetsmart, where did you hear that? I would have thought that number would have been higher actually.


    Flange, what area do you work in?



    [Edited by RoadRunner on 10-09-2006 at 06:06 PM]
  22. Replies
    20
    Views
    2,288

    Is this the same design you told me about when we...

    Is this the same design you told me about when we were working together at that plant in south Georgia?
  23. Thread: Low Suction

    by RoadRunner
    Replies
    16
    Views
    2,402

    What kind of amps do you have? Actual compared to...

    What kind of amps do you have? Actual compared to rated. I agree with 3rdgenhvac. Sounds like it may be busted valves in the compressor.

    just my 2 cents..




    [Edited by RoadRunner on...
  24. Replies
    18
    Views
    1,909

    One in my area here, and a couple more north of...

    One in my area here, and a couple more north of me that RichardL maintains. Works really good. Chiller and engine both. There practical and reliable if thats what the facility needs or wants. However...
  25. Replies
    11
    Views
    1,123

    Form

    Call your local York Factory office then and ask them to order it for you. Order the form number from the previous post. I assure you this is valid and the correct form you need. What part of the...
  26. Replies
    11
    Views
    1,123

    ISN Manual

    Randy, call York HQ at 717-771-7890, ask for the Pulications Department. You need to order form # 450.11-CP5

    Bill
  27. Replies
    6
    Views
    899

    oh K

    Now Now Now Richard... Be nice....there job security...at least untill the customer get so pissed at the cost of said top end maintainence, that he yanks the whole chiller.


    Bill
  28. Replies
    2
    Views
    1,187

    The transducer (pigtail only) part number is...

    The transducer (pigtail only) part number is 025-29150-001

    Bill
  29. Replies
    19
    Views
    2,640

    Maxster ....just curious, do you work for York? ...

    Maxster ....just curious, do you work for York?

    Bill
  30. Replies
    20
    Views
    2,790

    My two cents...for what its worth....forget the...

    My two cents...for what its worth....forget the plates and just use straps to choke the volutes. It works great!

    Bill
  31. Replies
    23
    Views
    3,600

    It is the 100. One line blue....thanks...

    It is the 100. One line blue....thanks btexpress....If I can ever help you out let me know...especially York stuff...

    Thanks MUCH!!!
    Bill
  32. Replies
    23
    Views
    3,600

    Nope...on this machine, when it gets a call the...

    Nope...on this machine, when it gets a call the Microtech panel looks for chilled water flow to be established within 20 seconds. (which I believe is adjustabale) Else it faults on no chilled water...
  33. Replies
    23
    Views
    3,600

    Fat Eddy Was that a response, or was you...

    Fat Eddy


    Was that a response, or was you kidding? That is the most stupid response I have ever seen.
  34. Replies
    23
    Views
    3,600

    89 vintage. Specifically I am looking for a way...

    89 vintage. Specifically I am looking for a way to increase the chilled water flow sensing delay. It is set for 20 seconds now and am wondering if it is field adjustable? (Im sure passworded)I need...
  35. Replies
    2
    Views
    1,082

    Try contacting these guys...they are a Nesbitt...

    Try contacting these guys...they are a Nesbitt parts dealer so they may be able to get some info for you...

    Hope this helped!

    Bill

    http://www.dwgi.net/index.htm
  36. Replies
    16
    Views
    1,933

    Hi ya Richard...sorry to hear about that!!! The...

    Hi ya Richard...sorry to hear about that!!! The words of an ex-employer comes to mind after an accident such as yours...BUT DID YOU FINISH THE JOB BEFORE YOU WENT TO THE HOSPITAL??? Who was the...
  37. Replies
    8
    Views
    1,403

    Dont forget to order a MicroGateway so Allerton...

    Dont forget to order a MicroGateway so Allerton can talk to the YCAS.

    Bill
  38. Replies
    20
    Views
    2,499

    Well if you changed the oil filter and the...

    Well if you changed the oil filter and the pressure is still low and there was'nt metal in it, then turn up the pressure (regulater) as the ole preverbiale saying goes to 40 psi. If it makes it there...
  39. Replies
    20
    Views
    2,499

    Where is your machine (you) located? What is the...

    Where is your machine (you) located? What is the night time...evening temperatures? If you have 75 to 80 degree entering condenser water at startup you shouldnt have any trouble with system...
  40. Replies
    20
    Views
    2,499

    Check your oil filter. The oil pressure on your...

    Check your oil filter. The oil pressure on your YT should be around 40psi. 22-25 is to low. Hopefully there wont be any sparklies in it. If after you change the filter and the pressure is still that...
  41. Replies
    5
    Views
    1,934

    What style machine is it? D or F ? What is the...

    What style machine is it? D or F ? What is the chilled water temperatures in and out at these conditions and the percent load and or current reading? What is the ambient temperature? How many...
  42. Replies
    18
    Views
    3,365

    Eddie...the 3 minites your refering to is when...

    Eddie...the 3 minites your refering to is when the vent line solinoid on top of the compressor opens to vent the gearcase. When it opens the oil in the sump will foam somewhat for a few seconds and...
Results 1 to 42 of 52