Search:

Type: Posts; User: picnik

Page 1 of 4 1 2 3 4

Search: Search took 0.01 seconds.

  1. Can't see your email in your profile. I have the...

    Can't see your email in your profile. I have the V3 SDU directory which has all the files you want. Email me and I'll send them back to you.

    I wish you luck in your project. I had a similar...
  2. Replies
    8
    Views
    629

    Do you recon those floor plans were done using...

    Do you recon those floor plans were done using ASCII characters. Did a few graphics back in the day doing that.
  3. Replies
    1
    Views
    256

    What help do you need?

    What help do you need?
  4. Replies
    4
    Views
    719

    The common alarm block allows the acknowedgement...

    The common alarm block allows the acknowedgement and resetting of all alarms in the current chart and all charts below by connecting to the relevant pins to do the acknowledge or reset.

    In...
  5. Replies
    6
    Views
    1,134

    You need one big DIEPT file. Its basically one...

    You need one big DIEPT file. Its basically one file per site. You cant have seperate ones for each controller.
  6. Could be. do they have a part number on them?

    Could be. do they have a part number on them?
  7. If your using a T1 sensor (FR-T1) then the table...

    If your using a T1 sensor (FR-T1) then the table below is right. The new type of sensor you have been sent might be a Ni1000 sensor (QAA24?) which are 0C at 1000 Ohms. You can change from old to new...
  8. Replies
    2
    Views
    318

    we tend to use these guys. ...

    we tend to use these guys.

    http://www.synapsys-solutions.com/

    Seem to do a pretty good job
  9. Replies
    4
    Views
    620

    The TONN (basically a trend badged tridium...

    The TONN (basically a trend badged tridium controller) would probably take in the LON from the TAC. But I'll say that they're opening themselves up to a whole load of issues. To modify any of the TAC...
  10. Thread: Staefa Controls

    by picnik
    Replies
    16
    Views
    2,769

    I can send you a scanned in staefa service manual...

    I can send you a scanned in staefa service manual that has all that kit except the R.U22 but its 12Mb. Stick your email address in your profile and I can send it later today.
  11. Replies
    41
    Views
    5,919

    OK, so updated my java to 7 (Version 6 Build 41)...

    OK, so updated my java to 7 (Version 6 Build 41) and all seems to work fine now. Of course some stuff not implemented but as a start pretty good. Talks fine to my delta DSC1616E controller anyway. My...
  12. Replies
    41
    Views
    5,919

    Looks like a great idea. What java version do I...

    Looks like a great idea. What java version do I need as I get class version errors when I try and run

    java.lang.UnsupportedClassVersionError: Bad version number in .class file
  13. Thread: Siemens PXC3...

    by picnik
    Replies
    6
    Views
    1,119

    Sorry, was getting my part numbers mixed up. I...

    Sorry, was getting my part numbers mixed up. I stated PXC3.L but I was actually talking about a PXG3.L

    The device you are talking about is part of their Total Room Automation range and I believe...
  14. Thread: Siemens PXC3...

    by picnik
    Replies
    6
    Views
    1,119

    Theres a number of flavours of PXC3's, there the...

    Theres a number of flavours of PXC3's, there the PXC3.L which is a BACNet/LON to BACNet/UDP/IP router, the PXC3.M which is the same as PXC3.L but with added MS/TP connections, and I think there is a...
  15. Thread: Siemens PXC3...

    by picnik
    Replies
    6
    Views
    1,119

    By Schedule do you mean install/configure and...

    By Schedule do you mean install/configure and that you cant find it as a device in the drop down menu?

    I believe you need XWorks V5. They also have a stand alone program to set it up as well but...
  16. Replies
    5
    Views
    1,050

    sent a new link, but check your spam folder

    sent a new link, but check your spam folder
  17. Replies
    5
    Views
    1,050

    OK, but best remove your email from the thread....

    OK, but best remove your email from the thread. Should go in your profile...
  18. Replies
    5
    Views
    1,050

    drop me an email and I'll reply with the files. ...

    drop me an email and I'll reply with the files.

    Is the tool you're using the new one or the old one? the new tool works best if the firmware files are saved in a certain file structure. Its a big...
  19. Replies
    6
    Views
    1,027

    here's a screen shot of the settings a colleage...

    here's a screen shot of the settings a colleage has set to get his NIC709-USB100 working with XWorks

    347391
  20. Thread: Old Staefa

    by picnik
    Replies
    89
    Views
    12,987

    You'd need to put your email address in your...

    You'd need to put your email address in your profile if you want anyone to help you on this I think.

    Also, have you tried contacting your local Staefa branch?
  21. Replies
    6
    Views
    1,027

    I can confirm this device does work fine. we have...

    I can confirm this device does work fine. we have a few people using them in the office. you need to go into advanced settings and select legacy mode. also a good idea to run it as a service
  22. Replies
    6
    Views
    1,027

    Have you ever been able to connect with this...

    Have you ever been able to connect with this interface to other PXC's or is this the first time you've tried it?

    I think I tried one of these devices previously with XWorks 2.37 and it didn't...
  23. Replies
    3
    Views
    958

    I know what you mean. I installed some wireless...

    I know what you mean. I installed some wireless sensors a while back as drilling the grade 1 listed building was out of the question. But the 2 foot think walls in places meant reception was an...
  24. Replies
    3
    Views
    958

    Wireless MBus Gateway

    Has anyone connected wireless MBus devices to a BMS? I have a solution for wired MBus but struggling a bit with wireless.

    What devices have you used to convert it into a protocol that your BMS can...
  25. Replies
    4
    Views
    1,286

    That would be a great application. Not sure about...

    That would be a great application. Not sure about setting the standard weekly schedule through it but I could see exceptions and calander events being integrated quite well.
  26. Replies
    15
    Views
    1,447

    I use this: ...

    I use this:

    http://www.blackbox.co.uk/gb-uk/sp/45256/USB-Powered-Ultra-Compact-Ethernet-Switch

    Its not a hub which is a shame, but as it can be powered by your USB port its really useful where...
  27. Replies
    10
    Views
    2,515

    What data are you looking for? They have an...

    What data are you looking for?

    They have an add on called report generator that generates reports and exports as excel or pdf;

    They do a package called ADP (Advanced Data Processing) if you...
  28. Thread: Desigo Insight

    by picnik
    Replies
    52
    Views
    10,594

    To check for interference you will need something...

    To check for interference you will need something like an oscilloscope or a protocol analyzer. I must admit I'm no expert on this so maybe read some of the other threads on this site. (Do a search...
  29. Thread: Desigo Insight

    by picnik
    Replies
    52
    Views
    10,594

    You really need an RXZ01.1 if using a star...

    You really need an RXZ01.1 if using a star topology. Try this first. If you want to use RXZ02.1's you need one at each end of the network. I'm sure you can make a bus topology network the way you...
  30. Replies
    30
    Views
    4,308

    I suppose I was just looking for something basic,...

    I suppose I was just looking for something basic, flagging up an alarm has occured and at what time. What I was thinking of was that Siemens Europe have a device called a PXM20 (a hand held device)...
  31. Replies
    30
    Views
    4,308

    The thing I've always wanted was for some clever...

    The thing I've always wanted was for some clever chap to make an alarm receiver widget. A building manager could then just have this installed on his PC and any alarms could then be sent direct to...
  32. Replies
    14
    Views
    2,766

    Well they call it a modbus explorer but not sure...

    Well they call it a modbus explorer but not sure it's as feature rich as the bacnet one

    http://www.chipkin.com/technical-resources
  33. Replies
    14
    Views
    2,766

    Chipkin do a modbus "explorer" but I havent used...

    Chipkin do a modbus "explorer" but I havent used it yet. Maybe worth a try. They have a few other bits of software that's quite useful like an Rtu parser as well.
  34. Replies
    2
    Views
    464

    Have you tried their web site? ...

    Have you tried their web site?

    http://www.multitek-ltd.com/
  35. Replies
    9
    Views
    2,080

    Sorry, I miss read the post as was reading on my...

    Sorry, I miss read the post as was reading on my phone.

    I'll try and post again
  36. Replies
    9
    Views
    2,080

    https://hit.sbt.siemens.com/HIT/fs_global.aspx?RC=...

    https://hit.sbt.siemens.com/HIT/fs_global.aspx?RC=AA&lang=en&MODULE=Catalog&ACTION=ShowProduct&KEY=BPZ:GEB..1E&TITLE=Rotary+air+damper+actuators+15+Nm%2c+without+spring+return
  37. Thread: Desigo Insight

    by picnik
    Replies
    52
    Views
    10,594

    The error looks familiar but can't think what it...

    The error looks familiar but can't think what it definatly is. Was the project upgraded from a 2.37 project. I sometimes find the upgrade process is not always perfect and old version blocks are left...
  38. Thread: Desigo Insight

    by picnik
    Replies
    52
    Views
    10,594

    Sed2's are not my specialty. I'd recommend you...

    Sed2's are not my specialty. I'd recommend you start a new thread on the forum and ask the other guys on here
  39. Thread: Desigo Insight

    by picnik
    Replies
    52
    Views
    10,594

    The reason I asked what firmware version for 2.37...

    The reason I asked what firmware version for 2.37 was I heard that new PXC's were coming out with new chips in them that were not compatible with the 420 firmware.

    I received a bulletin last...
  40. Thread: Desigo Insight

    by picnik
    Replies
    52
    Views
    10,594

    What firmware did you download to it? is it V4 or...

    What firmware did you download to it? is it V4 or downgraded to V2.37?

    did you use PXC_CMP12-22 V2.20.424.dwz or PXC_CMP12-22 V2.20.420.dwz if downgraded?
  41. Thread: Desigo Insight

    by picnik
    Replies
    52
    Views
    10,594

    Can you confirm that the correct buttons are...

    Can you confirm that the correct buttons are being pressed

    http://www.big-eu.org/catalog/siemens/023_PXC..D_CM1N9215en_08.pdf

    Have a look on page 7.

    Also check that the AA battery is healthy...
  42. Thread: Desigo Insight

    by picnik
    Replies
    52
    Views
    10,594

    Looks like your controller might be faulty. There...

    Looks like your controller might be faulty. There are some commands that can be used on the controller while using the firmware download tool if its in "Coma" mode but I don't have the documentation...
  43. Thread: Desigo Insight

    by picnik
    Replies
    52
    Views
    10,594

    Seems an interesting problem. The only thing I...

    Seems an interesting problem.

    The only thing I ever had close to this was when I needed to do some work on a PXC00-U doing RXL's. I tried downloading the firmware but it wouldn't take the download...
  44. Replies
    13
    Views
    2,316

    From what I've seen of crestron its not so much...

    From what I've seen of crestron its not so much what the system can do but the fact its almost a fashion accessory for the rich.

    I've only really seen it in posh private houses and its an absolute...
  45. Replies
    1
    Views
    937

    I have done some ABB's via mstp using a Delta...

    I have done some ABB's via mstp using a Delta DSM-RTR to get them on BACNet/IP (would probably use the contemporary controls router now as cheaper). I did find them a bit slow to update but this...
  46. Replies
    7
    Views
    2,247

    If you put your email in your profile I can send...

    If you put your email in your profile I can send you some documents that might help a bit.

    Can you not edit it from the object viewer of desigo insight like putting in B=MS01 or B=[desigo device...
  47. Thread: Desigo Insight

    by picnik
    Replies
    52
    Views
    10,594

    Not sure what field device your using, but I had...

    Not sure what field device your using, but I had the same problem when using RXL's via PXC00-U. Turns out I set it up as a 3 speed fan instead of single speed. Also check the behaviour when the...
  48. Thread: Desigo Insight

    by picnik
    Replies
    52
    Views
    10,594

    With regard the PXC64U, without a resistor...

    With regard the PXC64U, without a resistor (RXZ01.1 or RXZ02.1) it is possible for the node setup to read the device as unconfigured and then when trying to configure it fails on the setting of the...
  49. Thread: Desigo Insight

    by picnik
    Replies
    52
    Views
    10,594

    Its probably knackered!! ;) Is this BACNet...

    Its probably knackered!! ;)

    Is this BACNet over LON or BACNet over UDP/IP??

    I'll assume LON and that you've done a node setup and you have the correct end of line resistor on the comms...
  50. Replies
    12
    Views
    883

    Try setting address 300 to address 1000 and see...

    Try setting address 300 to address 1000 and see what happens. I had a controller that refused to be address 700. I made it 900 and everything worked OK. dont know why to this day. I even used a new...
Results 1 to 50 of 151