Search:

Type: Posts; User: PlatinumRH

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Replies
    7
    Views
    671

    I ended up repeating the process again of...

    I ended up repeating the process again of downloading a blank file then downloading the saved file again and everything looks good now. Thanks.
  2. Replies
    7
    Views
    671

    Apparently this jace was upgraded to 3.8 without...

    Apparently this jace was upgraded to 3.8 without our knowledge which could explain the corrupt files? I'm now using 3.8 and the latest version of the Spyder tool and I can save the file to the...
  3. Replies
    7
    Views
    671

    I can't save the logic to the library either. I...

    I can't save the logic to the library either. I get the error "Could not save an application in the library due to some error".
  4. Replies
    7
    Views
    671

    Spyder Points all showing Fault

    I have a Lon Spyder that was setup by a previous contractor and integrated into a Jace. I have connected several times and have noticed no problems. However, the last time I connected I noticed all...
  5. Replies
    10
    Views
    1,225

    We tried the BACnet setup tool. The baud rate...

    We tried the BACnet setup tool. The baud rate and address were correct, nothing worked. We removed the trane stat and installed a BACnet conventional stat and it worked like a champ.
  6. Did you look for an "accumulator" object?

    Did you look for an "accumulator" object?
  7. Replies
    10
    Views
    1,225

    Trane Reliatel Integration BCI-R

    We are having trouble getting the Trane BCI-R to talk. Trane will only give us a new BCI-R card, but wants $$ to send out a tech. The unit is currently being controlled by the Trane zone sensor. ...
  8. I have done it the same way mmelillo has done it....

    I have done it the same way mmelillo has done it. Find replace also comes in very handy.
  9. Replies
    15
    Views
    2,067

    I installed the 32-bit version of workbench on my...

    I installed the 32-bit version of workbench on my Windows 7 64 bit machine and I'm able to use a USB LON adapter.
  10. When you bring a point into AX you can add...

    When you bring a point into AX you can add whatever point scaling you need directly in the point setup itself.
  11. Replies
    7
    Views
    623

    There are no software tools that I know of to do...

    There are no software tools that I know of to do it. We have done several and the speed depends on the size of the R2 database. If you have the R2 database, and re-use all of the graphics files it...
  12. I would leave them in place. The network...

    I would leave them in place. The network performance is better and the load on the jace is much less. If a BCM dies you could always put a Contemporary Controls BACnet router in it's place. It is a...
  13. Replies
    9
    Views
    913

    I agree with Jay_T. I don't have a lot of good...

    I agree with Jay_T. I don't have a lot of good experience with LON, but the JCI LX were very easy to work with and the most similar to a free programmable BACnet controller.
  14. Replies
    3
    Views
    661

    I just created a new nav file titled mobile, and...

    I just created a new nav file titled mobile, and set the start display I wanted as the home/root. I then set that as the nav file under the mobile section for the user.
  15. Replies
    3
    Views
    661

    I am replying to my own thread is case anyone...

    I am replying to my own thread is case anyone else has the same issue.

    I was able to create a mobile nav file that specifies my start display (root). This gets around the problem with the px...
  16. Replies
    3
    Views
    661

    Tridium 3.7 Mobile Px Views List

    Has anyone found a way to sort the order of the mobile px views on the first page on the px view app? For the mobile views I've created it just lists them in a random order. I would at least like my...
  17. Replies
    11
    Views
    1,497

    osiyo, I would agree with most of what you said. ...

    osiyo, I would agree with most of what you said. We are mainly a service company and we use conservative numbers and the most common parts. However, as time goes on the operation of dampers...
  18. Replies
    11
    Views
    1,497

    We use 7.5 in. lb. / sq. ft for direct and 10.0...

    We use 7.5 in. lb. / sq. ft for direct and 10.0 in. lb/ sq. ft. for linked dampers. We count linked dampers as ones being linked through a rod such as return and outside air being driven from the...
  19. Replies
    1
    Views
    393

    EBT software works a lot better if you install it...

    EBT software works a lot better if you install it on Windows Virtual PC XP Mode. You could try that.
  20. Upgraded my honeywell jar files and I am now able...

    Upgraded my honeywell jar files and I am now able to go into engineering mode and program. Thanks for pointing me in the right direction ruchc03! I did not originally install this jace and wasn't...
  21. This is a station running on an AX Jace Version...

    This is a station running on an AX Jace Version 3.6.47.9, Honeywell LonSpyder jar is 3.4.43.9.1. This error is occuring with all of the LonSpyders. I don't have any problems with configurable Hwell...
  22. Hwell Lon Spyder Engineering Mode Problem

    I have a Honeywell LON Spyder that I can't get to go into engineering mode. I get the following syntax/error. Does anyone have a clue what might be causing this?
    ...
  23. Replies
    28
    Views
    5,326

    I also recently saw a demo. Anyone tried using...

    I also recently saw a demo. Anyone tried using the DG Box to talk straight to BACnet controllers?
  24. Replies
    9
    Views
    877

    Unless you are having major performance problems...

    Unless you are having major performance problems I wouldn't do it. I've seen older computer get completely hosed up when attempting a defrag. At the very least I would back up the computer before...
  25. You would need the Alerton Envision software, and...

    You would need the Alerton Envision software, and a copy of Microsoft Visio to really be able to program the Alerton controllers. I don't think you'd have to have a BCM if you used the Jace as your...
  26. I second what Matrix said. Virtual XP mode is...

    I second what Matrix said. Virtual XP mode is the only way I've gotten FX Builder to work on Windows 7.
  27. Replies
    29
    Views
    5,070

    I am using gmail for my SMTP on 2 different AX...

    I am using gmail for my SMTP on 2 different AX sites with no problems. I use port 465 with SSL enabled.
  28. Histories aren't a problem if you set them up to...

    Histories aren't a problem if you set them up to archive in the Server. The ORD for the history in the Jace is the same as the ORD for the archived history in the Server. For example:...
  29. Replies
    18
    Views
    3,106

    If all you have under tools is application lookup...

    If all you have under tools is application lookup then its definitely the privileges of the account you are signing in with. The Alerton rep should be able to get in there and change that for you.
  30. Replies
    11
    Views
    1,814

    Sentry, I am pretty sure the "_" is not a special...

    Sentry, I am pretty sure the "_" is not a special character and you don't need the "$5f", just an "_"
  31. Replies
    6
    Views
    935

    I sent you an email to the address in your...

    I sent you an email to the address in your profile.
  32. Replies
    6
    Views
    935

    I don't have the Honeywell ax wizard jar. We just...

    I don't have the Honeywell ax wizard jar. We just need to pull in the points, not any programming. Do I need the wizard jar to get the points? The NVs I learned don't match what I am seeing in the...
  33. Replies
    6
    Views
    935

    Honeywell XL15C AX Object?

    Is there a Hwell XL15C shadow object/jar file in the palettes somewhere? I've looked and can't find one. When I did a discover on site it came in as a Dynamic Device with a bunch of NVs that don't...
  34. Replies
    6
    Views
    998

    Can I get the .xif file using the R2 Jace and...

    Can I get the .xif file using the R2 Jace and convert that file to an .lnml file to use with my AX station? Anyone know or done this before?
  35. Replies
    6
    Views
    998

    Yeah, it was a dynamic device in the R2 Jace...

    Yeah, it was a dynamic device in the R2 Jace also. I was hoping I was overlooking it somewhere since I could do a lot more work offline if I had the device. Thanks.
  36. Replies
    3
    Views
    540

    If there are an time delays in the program then...

    If there are an time delays in the program then you definitely need to put equipment in hand. They reset when DDC is sent to the controller.
  37. Replies
    6
    Views
    998

    Tridium AX MNL 800 Device

    Does anyone know if there is a MNL 800 device/shadow object for Tridium AX? I am upgrading a site from R2 to AX and don't see it in the LonSiebe palette or anywhere else?
  38. Replies
    9
    Views
    1,899

    Can you email me what Landis & Staefa you still...

    Can you email me what Landis & Staefa you still have, if any? Thanks.
  39. Replies
    2
    Views
    697

    Did you check to see if the points are "out of...

    Did you check to see if the points are "out of service"?
  40. Replies
    9
    Views
    2,094

    pault is correct. You would need Alerton's...

    pault is correct. You would need Alerton's Envision for Ibex software and an Alerton USB or parallel port key. You would also need a cable to connect directly to the microview.
  41. We've had sucess with export tags. This way you...

    We've had sucess with export tags. This way you can house the graphics on both the Jace and the Web Sup. If the Web Sup goes down, then you can access the Jace directly for the graphics.
  42. Replies
    203
    Views
    37,597

    xarralu, The BCM-ETH and the MS/TP controllers...

    xarralu,
    The BCM-ETH and the MS/TP controllers have different network numbers. Make sure you are scanning all networks when do the discover and that your jace network number is different.

    As...
  43. Try the PxInclude widget in the bajaui palette

    Try the PxInclude widget in the bajaui palette
  44. Replies
    10
    Views
    1,263

    frontline, check your email address that's in...

    frontline, check your email address that's in your profile
  45. When you go to first install it you should have...

    When you go to first install it you should have the option to choose the full version or the commissioning only version. Make sure you installed the full version.
  46. For anyone else with the same problem I finally...

    For anyone else with the same problem I finally found the solution. All of my AX installations were 32-bit. I tried uninstalling one version and re-installing it at 64-bit. As soon as I did this...
  47. Thread: Viso again

    by PlatinumRH
    Replies
    14
    Views
    2,430

    I am interest also! Thanks.

    I am interest also! Thanks.
  48. Replies
    203
    Views
    37,597

    jupiterj, are you trying to add them in the table...

    jupiterj, are you trying to add them in the table view? You should be able to right click at the top heading in the table view and add them.
  49. You are correct that I am running a station on my...

    You are correct that I am running a station on my laptop/localhost. I am trying to use Bacnet over Ethernet not Bacnet/IP. The system I am trying to discover is setup for BACnet/Ethernet and...
  50. Thanks. I have tried everything I could find on...

    Thanks. I have tried everything I could find on niagara-central without any luck which is why I am asking here.
Results 1 to 50 of 51