Search:

Type: Posts; User: wireguy

Search: Search took 0.00 seconds.

  1. Replies
    7
    Views
    1,938

    This one is a TT300. And yes the refrigerant flow...

    This one is a TT300. And yes the refrigerant flow has been checked, solenoids are working.

    Earlier it did have a couple of single phase over current faults due to flooding of the evaporator. The...
  2. Replies
    7
    Views
    1,938

    The data below is typical from the fault log. The...

    The data below is typical from the fault log. The RPM is over 30000 and the back EMF is below 0.07. It certainly seems like deterioration of the magnetic strength.

    Compressor Demand% 83.20%
    Inlet...
  3. Replies
    7
    Views
    1,938

    Danfos Turbocor

    Does anyone know how to remedy the “Motor back EMF is low” fault on a Turbocor compressor?
    I understand that this fault may be because by reduced strength of the magnetic field in the rotor. Can...
Results 1 to 3 of 3

Related Forums

Plumbing Talks | Contractor MagazineThe place where Electrical professionals meet.
Comfortech365 Virtual Event