  1. Replies
    1
    Views
    125

    That is a Comfort Controller 1600, you will need...

    That is a Comfort Controller 1600, you will need Network Service Tool V to access it.
  2. Replies
    8
    Views
    180

    Trane Tracker talks Trane Comm3/Comm4 to the RTU....

    Trane Tracker talks Trane Comm3/Comm4 to the RTU. You will not talk to a Carrier Open RTU. Your only option is to add the RTU card to the Tracker panel. This will allow R,G,Y,W to the RTU.
  3. Replies
    3
    Views
    102

    If the chiller has the CH530 controls you will...

    If the chiller has the CH530 controls you will need Trane's chiller software as the Comm Cards need to be added before you will get data.
  4. Thread: Service tool 5

    by Balibe
    Replies
    4
    Views
    235

    These part numbers are for older NST and...

    These part numbers are for older NST and obsolete. For NSTV the part number is 33CNNSTKIT-01.
  5. Thread: ivu 6 ccn

    by Balibe
    Replies
    4
    Views
    207

    That driver is the original fix in IOB14003, I...

    That driver is the original fix in IOB14003, I would apply that driver. Carrier just released a new fix yesterday [03/18/2014] in IOB14003A. It is the same driver but has another step to the...
  6. Replies
    5
    Views
    327

    Which version are you installing? If v2.0 or...

    Which version are you installing? If v2.0 or v2.1, believe you will need to upgrade to v2.2 for Windows 7. There is an v2.2 update .exe on havcpartners.com. If you have an older usb converter at...
  7. Replies
    9
    Views
    414

    According to the picture, your MSTP address is 70...

    According to the picture, your MSTP address is 70 and the baud rate is 19.2k. Did you power cycle the UPC after setting the address and baud rate?

    They are field programmable but should have been...
  8. Replies
    3
    Views
    242

    The OP stated v4.2 in the title, that is CCN so...

    The OP stated v4.2 in the title, that is CCN so SNAP wont work as it for v5.0 & higher. In v4.2, the *.equips just expose the CCN points to I-Vu. ApplicationBuilder is the program used to edit the...
  9. It is a PCT UI bug, I had the same issue and...

    It is a PCT UI bug, I had the same issue and contacted JCI back in November. JCI is aware of this issue. Now that 10.0 is out, it should be resolved. I received v10.0.1 last week and will be testing...
  10. Replies
    6
    Views
    358

    Do you have Windows Restore backing up the...

    Do you have Windows Restore backing up the machine? If so go back a week or two, I resolved this issue before this way. Worth a shot .....
  11. Not sure why Carrier stated this, the bridges...

    Not sure why Carrier stated this, the bridges will not bottleneck traffic or restrict trending if they are working correctly. They basically work like a repeater. I have a lot of i-Vu's with bridges...
  12. Replies
    17
    Views
    592

    The Network Visible will be found on the BACnet...

    The Network Visible will be found on the BACnet Tab, which his access doesn't have. Think he will need installers access to see that tab.
  13. Thread: i-Vu 6.0

    by Balibe
    Replies
    5
    Views
    334

    We have upgraded a few to v6.0, but none of them...

    We have upgraded a few to v6.0, but none of them were on the same IP that would show your issue.

    There are two patches recently issued that fixes over 25 UI issues but doesn't list your issue.
    ...
  14. Replies
    9
    Views
    466

    It also communicates MSTP/N2/ModBus. Have you...

    It also communicates MSTP/N2/ModBus. Have you check the dip switch's on the RTU-Open and verified them for Lon? I have attached the Carrier's RTU-Open Integration Guide, it shows the dip switch...
  15. Replies
    9
    Views
    466

    I have never dealt with the LON option either....

    I have never dealt with the LON option either. Appears the LON Card is good as it responds to the service pin.

    Have you checked the RTUOpen? There are dip switch's that need to be set for the...
  16. Replies
    30
    Views
    4,028

    If you order the part with the number on the...

    If you order the part with the number on the board it will come blank. If you order the board with the model and serial of the equipment it should come programmed for your specific equipment.

    Just...
  17. Replies
    33
    Views
    2,150

    Dapper is correct, even with TGP licensed you can...

    Dapper is correct, even with TGP licensed you can only run it when connected to a MP581. If you to start is in Rover before connecting, you will get the error. I have even attempted to start it...
  18. NSTV works on XP, we have it running on several...

    NSTV works on XP, we have it running on several XP laptops at our office. AFAIK only Windows 8 is an issue with NSTV.

    Sound like you have a defective adapter. As 381 suggested, try the adapter on...
  19. Replies
    10
    Views
    638

    Have to tried RAM Flushing the bad controller? It...

    Have to tried RAM Flushing the bad controller? It will reset it to how it is shipped from the factory. Pull power, short Com1 & Com2, reapply power, the pull the jumper after 10-15 seconds. This...
  20. Replies
    1
    Views
    247

    It is probably a 6-pin RJ-25 jack and not 8-pin...

    It is probably a 6-pin RJ-25 jack and not 8-pin RJ-45 jack (Ethernet). It should be marked Service.

    You can plug into the jack with a standard 4 conductor phone cord and connect to the CCN bus,...
  21. Replies
    17
    Views
    1,288

    I have had the same issue, it appears if you...

    I have had the same issue, it appears if you don't periodically log into the account it is turned off. Once you login, it is reactivated and works again. I believe the time frame is about 60 or 90...
  22. Not with v5.1 ..... v6.0 is supposed to have this...

    Not with v5.1 ..... v6.0 is supposed to have this ability for a lot of the canned programs but not all of them. v6.0 has been announced and should be available by the end of the month
  23. Replies
    11
    Views
    673

    I have had this odd issue also on FX-40's, to...

    I have had this odd issue also on FX-40's, to release I put an Emergency level override then Emergency Auto to clear it. Try that and see if it works.
  24. Replies
    11
    Views
    790

    You will need Summit to check the BCU, looks like...

    You will need Summit to check the BCU, looks like you have it on site already. Hopefully you full access. Make sure you look for any CPL that might be in the BCU to be safe.

    I have integrated a...
  25. Replies
    4
    Views
    359

    Your FX Workbench is not a yearly license? If it...

    Your FX Workbench is not a yearly license? If it is, it should already be licensed. Mine states the following, which I am able to use the Echelon USB TP/FT-10 that came with Trane Rover 7.
    ...