  1. Thread: Leak on HP

    by wildgato
    Replies
    16
    Views
    567

    I have found the that way also, in this case the...

    I have found the that way also, in this case the leak is small that I can not find anywhere, I need put something in the system to blend with the refrigerant to stop the leak,
  2. Thread: Leak on HP

    by wildgato
    Replies
    16
    Views
    567

    I found system low on R-22, put in an extra pund...

    I found system low on R-22, put in an extra pund to use my CPS leak detector, did not find the leak anywhere, I decided to fill it with nitrogen up to 200 lbs, pressure drops , like I said before at...
  3. Thread: Leak on HP

    by wildgato
    Replies
    16
    Views
    567

    Leak on HP

    Hello guys

    What product do you recomend to stop a VERY small leak on a Heat pump??
    it only looses 5 lbs of pressure every 3 hours, I can not find the leak, I have used refrigerant leak detector ...
  4. Replies
    16
    Views
    737

    We gave the building owner a price to install a...

    We gave the building owner a price to install a Liebert unit, waiting on his approval and the funds, thank for your response.
  5. Replies
    16
    Views
    737

    I agree with you 100%, we price the liebert unit...

    I agree with you 100%, we price the liebert unit for the customer, they thought it was WAY overpriced, yes he is right on the price, Liebert is the best on the market for server rooms, now he is...
  6. Replies
    16
    Views
    737

    Server room back up system

    hey guys
    What do recommend for back up cooling system, here are the details:
    We have a server room that does not have back up cooling, 2 weeks ago the 10
    TON lennox had a broken belt over the...
  7. Replies
    14
    Views
    608

    ok, I wll let you know if does not have it, thank...

    ok, I wll let you know if does not have it, thank you for the response.
  8. Replies
    14
    Views
    608

    Hello Kontrol out The Alerton space sensor that...

    Hello Kontrol out
    The Alerton space sensor that I'm looking for is Microset II, I could not find in ebay. would you happen to have it???

    Thank you very much for sharing your expertise with all of...
  9. Replies
    24
    Views
    884

    You mean replace the reversing valve also??? It...

    You mean replace the reversing valve also??? It is a good idea to swap both components , that way you do not take chances, I know the compressor is bad, thank you for your comment.
  10. Replies
    24
    Views
    884

    That is correct, it's not a digital compressor,...

    That is correct, it's not a digital compressor, thank you for taking the time to respond.
  11. Replies
    24
    Views
    884

    I will try it, to see what happens before,...

    I will try it, to see what happens before, compressor is replaced, thank you for your response, however compressor was running in the right direction before.
  12. Replies
    24
    Views
    884

    I agree madblack, the problem is, there is not a...

    I agree madblack, the problem is, there is not a pressure differential between discharge and suction, I also agree that, in order for the reversing valve to "work " there has to be pressure...
  13. Replies
    24
    Views
    884

    Nope, it is not, not even warm, but it running...

    Nope, it is not, not even warm, but it running tough, have you ever had a blower wheel come off of the motor?? Where the motor just spins and there is not air movement, same situation here, the...
  14. Replies
    24
    Views
    884

    Madblack, thank you for your unput, it makes...

    Madblack, thank you for your unput, it makes sense what you just said,I'm leaning towards the compressor but I need to be 100% certain is not the reversing valve.
  15. Replies
    24
    Views
    884

    I'm going to do this, what gets me is, that the...

    I'm going to do this, what gets me is, that the compressor is not pumping at all, even the valve was stuck in the middle, I see no pressure on my gauges, that is what leads me to believe the...
  16. Replies
    24
    Views
    884

    Rla are 17 amps, scroll compressor, line is at...

    Rla are 17 amps, scroll compressor, line is at ambient temp., since compressor is not doing any work, thank you for the response
  17. Replies
    24
    Views
    884

    Lennox Heat pump

    Hey Guys
    I went o a call today, the unit is a Lennox heat pump M/N:HP29-060-7Y,
    compressor is running but not pumping, pulling 6.9 Amps on all 3 legs, my the pressure are equalized,I know the...
  18. Replies
    14
    Views
    608

    I went back to the job today, did more...

    I went back to the job today, did more investigating above the ceiling and found the communication wire cut in two, they told me that there was work done in that areasome time ago, replaced the wire...
  19. Replies
    14
    Views
    608

    No it does not say that, thank you for taking the...

    No it does not say that, thank you for taking the time to respond ,
  20. Replies
    14
    Views
    608

    Yes, kontrol out, every unit display the NR, you...

    Yes, kontrol out, every unit display the NR, you mean between the PC and the controllers???? excuse my ignorance what is BCN and BTI stand for??? also where would I find IP/MSTP?? Thank you for...
  21. Replies
    14
    Views
    608

    Alerton controls problem

    Hi guys
    We have a building that has Alerton controls, the building has a Pool-pak,
    bolier and 2 RTU's,the software is envision 2.0, the computer does not display
    the values of any kind, all it...
  22. Replies
    9
    Views
    399

    Thank you ECtofix, just found that out about...

    Thank you ECtofix, just found that out about Hobart, again thank you for all your help,
  23. Replies
    9
    Views
    399

    Here is the update on this C44A commercial...

    Here is the update on this C44A commercial dishwaser, just like you said , it ended up being the fill valve, it failed mechanically.
    I replaced the fill valve and I also replace the LLSV just in...
  24. Replies
    9
    Views
    399

    you are correct on that , the coil might be too...

    you are correct on that , the coil might be too weak, to open the fill valve, do you know, how I can get my hands on a service manual for this particular dishwasher?????
    Thank you for taking the...
  25. Replies
    9
    Views
    399

    Thank you very much, Dakota11: I will do that in...

    Thank you very much, Dakota11:
    I will do that in the morning, that makes sense, if the machine is off and still getting water through, nothing to stop the flow, thank you again for your time to...
Results 1 to 25 of 64
Page 1 of 3 1 2 3