    It became a problem because someone commanded the...

    It became a problem because someone commanded the damper from the graphic, using the unbundled point.

    You really need to get rid of the duplicate point and put the auto-unbundled point on the...
  2. Replies
    2
    Views
    292

    Something else to check - it's possible that all...

    Something else to check - it's possible that all space temp sensors aren't attached to TEC's - depending on design, sometimes there are space temp sensors that are wired back to the panel and...
  3. I do the same as ControlTech1969~ Put graphic...

    I do the same as ControlTech1969~

    Put graphic into edit mode. Click on one of the items in the graphic. You'll see the square box "highlighting" that object you just clicked on. Now, hit the TAB...
  4. Replies
    10
    Views
    747

    Well said, I agree completely

    Well said, I agree completely
  5. Replies
    66
    Views
    1,868

    I'm with you on this jgaskin. As I was reading...

    I'm with you on this jgaskin.
    As I was reading this thread, I'm thinking, this isn't that hard of a problem. Turn the boilers back on, maybe reset the HW temp and call it good, go home.

    With...
  6. Replies
    1
    Views
    204

    Look closely, and you'll see that each point is...

    Look closely, and you'll see that each point is first saved in memory and then will be saved in the database.
  7. Replies
    10
    Views
    747

    I saw that story on Google+, and I commented...

    I saw that story on Google+, and I commented about how inefficient those systems must be, and also they mentioned that Amiga machine was doing all the scheduling? Talk about a single point of...
  8. Replies
    2
    Views
    507

    I assume you are working from the front end,...

    I assume you are working from the front end, Insight.
    Get into the auto-dial settings and disable the Automatic dial - I haven't had a modem on a BLN for quite a few years, I think you set the...
  9. Replies
    9
    Views
    1,000

    If the damper point as seen from the TEC (plug...

    If the damper point as seen from the TEC (plug directly into TEC or run TEC subpoint report) is normal, then it's just a corruption of the application at the front end.
    If this is the case, and...
  10. Thread: Vfd contactor

    by dingman
    Replies
    21
    Views
    1,616

    I just went thru another ABB class last year and...

    I just went thru another ABB class last year and they are still saying do not open the motor disconnect under load. The instructor specifically said drive damage could occur.

    And the new Siemens...
  11. Replies
    4
    Views
    432

    I haven't put my fingers on that exact TEC, but...

    I haven't put my fingers on that exact TEC, but yes, it looks like it will do what you want, in that you would be able to control the I\O's via PPCL in the panel.

    However, you will have to write...
  12. Replies
    1
    Views
    331

    Nah, it's the phone line. Test by plugging...

    Nah, it's the phone line.

    Test by plugging directly into the MMI with your laptop... the panel can't tell the difference between your laptop and the modem. If it's OK with the laptop, then...
  13. Thread: Apogee PPCL

    by dingman
    Replies
    8
    Views
    691

    heh, I've dealt with this before. I'm sure I...

    heh, I've dealt with this before. I'm sure I found the proper precedence use, but can't remember.

    Lacking that, I'd just multiply the neg values by -1, turns them into positive numbers and build...
  14. Replies
    25
    Views
    8,045

    delete

    delete
  15. Replies
    18
    Views
    1,222

    Trickery! The server thinks the panel is online...

    Trickery! The server thinks the panel is online but database transfer says not?

    First thing I'd do is remove the Extended Timeout from the panel definition, you've got a P2 BLN and the Extended...
  16. 01033 IF(A2TS .LT. 18.5) THEN RELEAS...

    01033 IF(A2TS .LT. 18.5) THEN RELEAS (@OPER,A2HTWE)
  17. Isn't that crazy, all that the automation system...

    Isn't that crazy, all that the automation system does and the customer gets wound up about the graphic printouts.

    I haven't dug into this much but found good improvement by using the printer...
  18. Replies
    2
    Views
    581

    that's the funniest thing I've heard in awhile....

    that's the funniest thing I've heard in awhile. Are you sure they weren't pulling your leg? Astounding.
  19. Replies
    8
    Views
    863

    That sounds pretty straightforward. The virtual...

    That sounds pretty straightforward. The virtual point should be controlled by a PID loop in the PPCL. Find the PID values in a unit that is working properly and copy those values into the offending...
  20. Replies
    8
    Views
    863

    The loop speed may not be the issue. Is the unit...

    The loop speed may not be the issue. Is the unit tripping off on startup or when it's been running and OA temp drops?

    Is it a new issue? Have you checked temps during trouble periods (look for...
  21. Replies
    154
    Views
    40,560

    I have saved every version since the DOS days. ...

    I have saved every version since the DOS days.

    I've already put them all out on the web, and all have nice little rootkits in them. Just run the install and don't worry about any security error...
  22. Just to be clear, PPCL doesn't need manual or...

    Just to be clear, PPCL doesn't need manual or auto-unbundling anymore.

    Graphics still do.
  23. Replies
    37
    Views
    16,274

    Full functionality via Hyperterminal. Of course,...

    Full functionality via Hyperterminal. Of course, you can't backup\restore databases.
  24. That's the ethernet ALN connection - look for the...

    That's the ethernet ALN connection - look for the MMI connection (also looks like an RJ45), plug your RJ11 in there.
  25. Well, it all sounds pretty good, sounds like...

    Well, it all sounds pretty good, sounds like you've put alot of time working into this.

    Despite being a long term tech with Siemens, you guys are above my head on this - you're at engineering...
  26. Replies
    8
    Views
    1,414

    LOL ya, it was a compliment. If you get crazy...

    LOL ya, it was a compliment. If you get crazy busy and need a well rounded, experienced tech, let me know. I could be talked into jumping ship - some great recreational activities in your area - way...
  27. This is correct.

    This is correct.
  28. Thread: Siemens node

    by dingman
    Replies
    10
    Views
    1,220

    Correct Willy, I've never found that LINK point...

    Correct Willy, I've never found that LINK point very useful. The only thing I did with it one time was to attach a light to a DO and turn it on when the panel would drop off the network. Then, people...
  29. Thread: Siemens node

    by dingman
    Replies
    10
    Views
    1,220

    I assume you are talking about TEC controllers....

    I assume you are talking about TEC controllers.
    The controllers attached to a specific panel would be available via the FLN device list. Pull that either from Insight or the panel.
  30. Replies
    8
    Views
    1,414

    hiyas air1! I'm chuckling over here, your...

    hiyas air1!
    I'm chuckling over here, your explanation is way more than the OP needed. Obviously you know your stuff, and we have an tech opening here in Iowa, you should apply. :)
    if you indeed a...
  31. Disconnect all the inputs\outputs except power....

    Disconnect all the inputs\outputs except power. If it still does it, replace the TEC. If it stops, inspect wiring\devices.
  32. Willy, doesn't it sync automatically with each...

    Willy, doesn't it sync automatically with each change?

    Seagar, you won't add the info block in Designer, you add it in the Graphics application, take your TEC graphic, and put it in edit mode, and...
  33. Replies
    6
    Views
    1,243

    Actually, one would try to avoid having to define...

    Actually, one would try to avoid having to define the graphic in each TEC definition in the system profile.

    The create-on-the-fly TEC graphics are already done and available in Insight. If there's...
  34. Replies
    6
    Views
    1,243

    Actually, one would try to avoid having to define...

    Actually, one would try to avoid having to define the graphic in each TEC definition in the system profile.

    The create-on-the-fly TEC graphics are already done and available in Insight. If there's...
  35. There's a couple of failsafe modes, where it...

    There's a couple of failsafe modes, where it won't let you command the fan.

    IIRC, both the LTD and the DA temp sensor can cause failsafe mode. Make sure LTD isn't tripped and that DA sensor isn't...
  36. This isn't an answer to your question, so pardon...

    This isn't an answer to your question, so pardon my interjection.

    Siemens TEC's have historically been very robust and quite difficult to damage. If you have more than a few that are damaged, then...
  37. Thread: Siemens Log

    by dingman
    Replies
    6
    Views
    933

    If you have access to it, there should be a...

    If you have access to it, there should be a button in the Insight main tool bar.
  38. Thread: Siemens Log

    by dingman
    Replies
    6
    Views
    933

    Yes.

    Yes.
  39. Replies
    11
    Views
    1,546

    Seems like there's a common path, not shared by...

    Seems like there's a common path, not shared by all, but by a majority.
    My path was~
    Industrial Electrician
    to
    Commercial\residential Electrician
    to
    AA in Electronics
    AA in Robotics (yea, I...
  40. Replies
    7
    Views
    1,464

    Dead JNL files are easy to check and correct. I...

    Dead JNL files are easy to check and correct. I find this less and less due to the increased reliability of networks\clients. Haven't found any dead JNL's for months now.

    However, in the last few...
  41. Replies
    10
    Views
    1,286

    Ton78, I commend you for searching out people to...

    Ton78, I commend you for searching out people to help.

    I understand you're in a tough spot, with not having adequate training for what you're working with.

    My best suggestion would be to read...
  42. Replies
    10
    Views
    1,286

    Wow, that's a darn nice post, Osiyo. Very polite,...

    Wow, that's a darn nice post, Osiyo. Very polite, well done.

    Ton78, listen to what he's saying there. I have to agree (and I could be wrong) that you appear to have little experience with this...
  43. Replies
    1
    Views
    576

    I'm not exactly sure what you're asking, but...

    I'm not exactly sure what you're asking, but you'll want to do that using the slope and intercept in the application used in the modbus controller.
    Of course, the data type and offset will need to...
  44. Replies
    8
    Views
    2,100

    540-509 Yeah, it's got more than you need... but...

    540-509
    Yeah, it's got more than you need... but there it is.
  45. Replies
    50
    Views
    2,289

    For the first time today, I've seen your...

    For the first time today, I've seen your "political" posts\threads.

    I find it a bit surprising people endevor to debate your assertions, given your attitude (belittling, deriding, name calling,...
  46. Replies
    11
    Views
    1,119

    I've had a couple of these~ Controls not...

    I've had a couple of these~
    Controls not working, blah blah blah.
    Arrive to find water on the floor. Find water in the panel, causing shorts and stuff.
    I ask custodian, did you just wash the...
  47. Yup, that second drawing is a variable primary....

    Yup, that second drawing is a variable primary.
    My advice to run away. Run far, run fast.
    (VP can work, but my experience and others also, have shown too many issues).

    Hehe, and if the bypass...
  48. Replies
    18
    Views
    3,509

    Yup, both you guys are correct. If the Insight...

    Yup, both you guys are correct. If the Insight system doesn't have the administrator account in Apogee's user list, then the owner is out of luck.
    I'm not exactly sure why the...
  49. Replies
    18
    Views
    3,509

    I agree, that is complete BS and NOT standard...

    I agree, that is complete BS and NOT standard practice.

    Stand-alone? Yeah, hack the password and be done with it.

    BTW, you need to get some backups off that PC. When it does crash, it might...
  50. Replies
    18
    Views
    3,509

    Who's PC is it anyway? Is the PC on a domain? I...

    Who's PC is it anyway? Is the PC on a domain? I highly doubt Siemens is the only admin account on the machine.

    Just get the IT guy to change the password to the Siemens account if you don't know...
Results 1 to 50 of 298