Search:

Type: Posts; User: Kimmer71

Search: Search took 0.00 seconds.

  1. Trane LCIR brings down AX JACE LON trunk following power fail

    I have seen this a few times. After a power outage, one or many Trane LCIR cards will "scream" on the trunk and bring everything down. To correct the problem we have to de-energize every trane unit...
  2. Replies
    4
    Views
    2,468

    Final verdict: The older R2 play-station type...

    Final verdict:

    The older R2 play-station type JACE's (and I think newer 411-545's) are capable of BACnet Ethernet using MAC addresses only. The new JACE 600's are not due to the NIC interface...I...
  3. Replies
    4
    Views
    2,468

    Trane BCU to AX Jace via BACnet Ethernet

    I'm working on a R2 to AX JACE replacement project. The R2 JACE was integrated to the Trane BCU and working fine. I can't seem to get the new AX JACE talking to the BCU. All I have is the MAC address...
  4. Replies
    0
    Views
    288

    Large Fan Inlet flow measuring stations

    I've got like 8 of these if anyone is interested. They were ordered the wrong size. I think they are around 56" long. Let me know if you are interested and I'll get the exact measurements.
  5. Replies
    2
    Views
    538

    Thank you

    Thank you Willf650. That was exactly what I was looking for. I appreciate the help.
  6. Replies
    119
    Views
    15,480

    Here is another Sedona product offering. ...

    Here is another Sedona product offering.

    http://www.pervasivedevices.com/
  7. Replies
    2
    Views
    538

    Trane Trace ZN510 nvoAlarmMessage values

    I'm looking for a list of available alarm messages on this snvt for a water source heat pump. Anyone know if such a list exists? I have looked and can't seem to find one.
Results 1 to 7 of 7