    The temperatures on the graphic show up as...

    The temperatures on the graphic show up as question marks ??? but if you click on it, the graphic shows up with data reading correctly.
  2. Replies
    6
    Views
    222

    any ideas?

    any ideas?
  3. Replies
    2
    Views
    155

    What ports did you ask to be opened? Is port...

    What ports did you ask to be opened? Is port 1911 opened for a fox connection?
  4. Replies
    6
    Views
    222

    Andover Continuum Comm Issues

    I have a customer with an older Andover Continuum system that was having communication issues. There were two comm trunks coming out of the main head end controller. Both comm trunks were...
  5. Replies
    7
    Views
    517

    Digo, I think you're correct. When I got it to...

    Digo, I think you're correct. When I got it to work before back in 2011 there was an FX Server on site hosting several FX60s. On the site that I'm working on now there is no FX Server. Also, this...
  6. Replies
    7
    Views
    517

    Sorry for bumping my old thread but I'm trying to...

    Sorry for bumping my old thread but I'm trying to get this to work again and it won't for some reason. I'm trying to access an FX Jace that has a private IP address. The main FX Jace is accessible...
  7. Replies
    8
    Views
    315

    Forget the drawing this guy doesn't need to be...

    Forget the drawing this guy doesn't need to be anywhere near electricity
  8. Replies
    3
    Views
    378

    Thanks for the reply. I'm going to try this today

    Thanks for the reply. I'm going to try this today
  9. Replies
    3
    Views
    378

    Older UNT to 8.08B HVAC Pro

    I have an older UNT that I'm going to be adding a point to. I can upload it with HAVCPro at 8.08B. The thing that I'm concerned about is upgrading the controller to 8.08B. I'm afraid I'm going to...
  10. Thread: Fx60 login

    by Igotworms
    Replies
    7
    Views
    312

    Do you have FX Workbench?

    Do you have FX Workbench?
  11. Replies
    11
    Views
    865

    The new PCGs will be available in N2 soon

    The new PCGs will be available in N2 soon
  12. Replies
    13
    Views
    685

    I am able to connect to the mig with...

    I am able to connect to the mig with hyperterminal. Once I connect to it, there isn't much I can do. I can't see the vendor tables or anything, only a couple menu options. Maybe I just don't know...
  13. Replies
    13
    Views
    685

    I did try 85760430. I got that number from their...

    I did try 85760430. I got that number from their tech support but still didn't work. Thanks for all the responses
  14. Replies
    13
    Views
    685

    I contacted my local McQuay rep. The one tech is...

    I contacted my local McQuay rep. The one tech is familiar with these things and has all the software and cable to get the password. I will post the results
  15. Replies
    13
    Views
    685

    I just tried but no luck. Is there more to that...

    I just tried but no luck. Is there more to that password? that is 7 characters
  16. Replies
    13
    Views
    685

    Yeah I tried that

    Yeah I tried that
  17. Replies
    13
    Views
    685

    McQuay OPM Integration

    I know there are a few threads on this site about integrating to the OPM panels but I couldn't find an answer for finding the "Site Password Hex." I'm using an FX70 for this. Everything is licensed...
  18. Replies
    3
    Views
    372

    3.8

    3.8
  19. Replies
    3
    Views
    372

    PX Zoom In/Out

    Does anyone know how to make the viewing area of a PX larger? I'm using a scroll-pane on a PX file and I added a canvas pane under that. I can change the "viewsize" property of the canvas pane to...
  20. I've decided to get rid of the MIG and go with...

    I've decided to get rid of the MIG and go with the OPM driver. I've never used this driver before. I've read through the McQuay.doc file and it seems pretty straight forward. Has anyone else used...
  21. I was onsite all day yesterday and took a closer...

    I was onsite all day yesterday and took a closer look at what is mapped into the NCM. What is bothering me about this MIG is that about 4 or 5 heat pumps are online. The rest of them are not. I...
  22. No I don't have any other rev of the MIG. I...

    No I don't have any other rev of the MIG. I think I'm going to get the McQuay OPM driver and get rid of the MIG
  23. t-reck: How did the McQuay OPM driver work for...

    t-reck: How did the McQuay OPM driver work for you? I'm going to pitch this and see what they think since this MIG is not looking good and doesn't want to cooperate. Do you know if the OPM driver...
  24. I took some more pictures this morning. It looks...

    I took some more pictures this morning. It looks like this MIG is at revision 3.00 and the battery jumper is in the right position. Is there anything I can do to get this back to the way it was?
    ...
  25. Is there a way to manually type in the point data...

    Is there a way to manually type in the point data through hyperterminal? I still have the database from the NCM
  26. t-reck: How do you manually add in the heat...

    t-reck: How do you manually add in the heat pumps? I have the NCM database still. Can you do it through hyper terminal?

    clogic: Can you send that Technical Bulletin to me again? I added a...
  27. Here are the pictures I took. One is of the MIGs...

    Here are the pictures I took. One is of the MIGs model number and revision number to the right of that, the second is the MIG ordering codes from the original job submittals.
    ...
  28. Is there a way to reset the thing? I'm not...

    Is there a way to reset the thing? I'm not convinced that the tables are deleted since the other MIGs in the building work
  29. I'm looking at the submittals now it looks like...

    I'm looking at the submittals now it looks like the part number that has the integrator tables is part number TL-SWOMIG-0
  30. I was able to connect with hyper terminal but...

    I was able to connect with hyper terminal but couldn't do much. I don't remember seeing the revision number in there
  31. Also it's a MIG that looks like an old metasys...

    Also it's a MIG that looks like an old metasys companion
  32. I think it's says rev-c next to the model number....

    I think it's says rev-c next to the model number. I will post a picture of it in a little while
  33. Sorry to bump an old thread but I'm having the...

    Sorry to bump an old thread but I'm having the same problem. I have an old mig102. Apparently there was a power failure a while back and ever since then it hasn't been able to communicate. There...
  34. Replies
    21
    Views
    1,840

    Are you having problems with the network? ...

    Are you having problems with the network? Controllers going on and offline? If not I wouldn't mess around with it. The only way I know how to change instance numbers is to change it in CCT...
  35. Replies
    6
    Views
    770

    Yes every jace has a Niagara network that can...

    Yes every jace has a Niagara network that can share data between them. It does not need a peer to peer license or any other license to do this
  36. I did Google LWC and found a few .pdf files but I...

    I did Google LWC and found a few .pdf files but I haven't seen anything about that FF diagnostic address. Ill keep looking
  37. Nick, Where did you see that document? I did...

    Nick,

    Where did you see that document? I did notice that on the LWC the address was set to FF. I tried to change it to 5 which is what is mapped into the NCM but it didn't do anything.
  38. AX Metasys MIG and McQuay Loop water contontroller

    I'm converting an existing site from a Metasys NCM to an FX70. The NCM is integrating to a few McQuay OPM panels with a MIG and also a McQuay loop water controller that also goes back into a MIG. I...
  39. Replies
    4
    Views
    555

    What kind of controller is the temp sensor wired...

    What kind of controller is the temp sensor wired to? What protocol is being used? Are any tuning policies set up?
  40. Replies
    1
    Views
    272

    I have a bunch of DX9100 accessories along with...

    I have a bunch of DX9100 accessories along with other N2 devices shoot me a PM
  41. Thread: Lon nci

    by Igotworms
    Replies
    15
    Views
    1,158

    This seems like a stupid question but I can't...

    This seems like a stupid question but I can't figure it out. How do you edit a .lnml file in the text editor? I'm able to navigate to the lnml file in my modules section of workbench on my machine,...
  42. Replies
    5
    Views
    489

    I know how to change it based on the status but...

    I know how to change it based on the status but what I'm trying to do is a little different. I have the image changing based on zone temp with no problem. But now I want to have the image change if...
  43. Replies
    11
    Views
    935

    It was a company specific module that I wanted to...

    It was a company specific module that I wanted to test out. My laptop was not licensed for it though
  44. Replies
    5
    Views
    489

    Unreliable PX Graphic

    Is there a way to change a picture on a graphic based on the status of the controller? I'm able to change the colors of the LEDs in kitPxGraphics based on zone temperature, but I would also like to...
  45. Replies
    32
    Views
    2,034

    What type of cabling do you usually use for Lon? ...

    What type of cabling do you usually use for Lon? In this building there is a 16 gauge wire ran for the comm trunk. That seems awful big for a comm trunk but the jacket of the wire specifically says...
  46. Replies
    4
    Views
    371

    What version is your jace running? Do you have...

    What version is your jace running? Do you have the same version of workbench on your pc as the jace?
  47. Replies
    2
    Views
    309

    Yes open up HVAC Pro and go to Central Plant...

    Yes open up HVAC Pro and go to Central Plant Applications. There is a Pump Leag/Lag question and answer application under that.
  48. Replies
    32
    Views
    2,034

    The very first thing I did on this job was wire...

    The very first thing I did on this job was wire the FX70 as another node on the network so there were two supervisory device online at once (The NAE and the FX70). With the NAE still online, I did a...
  49. Replies
    32
    Views
    2,034

    I got about half of the network online yesterday...

    I got about half of the network online yesterday and left it over night. I checked the alarm console this morning and had no ping alarms. I got the rest of the network online and it seems ok. I...
  50. Replies
    32
    Views
    2,034

    I think I'm finally starting to make some...

    I think I'm finally starting to make some progress with this. What I started doing is killing the power to all of the heat pumps. I turned on one breaker at a time which fed about 3 heat pumps per...