Search:

Type: Posts; User: mechmike2

Page 1 of 10 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    4
    Views
    219

    Each unit now has its own OA sensor. What they...

    Each unit now has its own OA sensor. What they want is a uniform OA temp which will be the same for all units. If I pick 1 unit to broadcast its OA temp then done deal, but where I could do that on a...
  2. Replies
    4
    Views
    219

    Carrier RTU-Open Outside Air Question

    Have a customer with a few sites that each have appx. 20 Carriers with RTU-Open controllers. The units, as is, use their individual OA sensor for various control strategy's. What customer would like...
  3. Replies
    5
    Views
    275

    7.67 is latest version as far as I know

    7.67 is latest version as far as I know
  4. Replies
    0
    Views
    191

    Reliatel to AX integration issue

    Doing a Trane Reliatel integration and am having an issue where I need to be able to allow the tenant to have set point adjustment from the wall sensor but only between ranges. Sensor installed are...
  5. Replies
    2
    Views
    215

    Sent you a palette that contains a 15C for Learn...

    Sent you a palette that contains a 15C for Learn device that makes it easier to work these devices. More info. on Buildings Forum on these devices also.
  6. Replies
    1
    Views
    134

    Adding modules to FX-60

    Have to add a Lon network to an FX-60, there are no lon modules install as it came, it is licensed for lonworks. I am leary of connecting to Johnson device with my Webs workbench and transferring the...
  7. Thread: vav help

    by mechmike2
    Replies
    6
    Views
    396

    KMC has some offerings for standalone VAVs. Going...

    KMC has some offerings for standalone VAVs. Going to try out their "Simple VAV" on a box tomorrow to see how they work.

    Envirotec another option for standalone.
  8. Replies
    4
    Views
    254

    After you set up your Rapidzone system the last...

    After you set up your Rapidzone system the last tab is "Finish" in which you can save the job. After saving job a network tab opens up, if you open the network tab it brings up another screen and if...
  9. Replies
    10
    Views
    424

    I have 5.1 Tools on an older laptop, trying to...

    I have 5.1 Tools on an older laptop, trying to get the new 6.0 version because I can't get 5.1 to work on new Windows 7 computer, unsure why.
  10. Replies
    10
    Views
    424

    Sent a copy of mod stat report off to a Carrier...

    Sent a copy of mod stat report off to a Carrier controls tech I know and he noted error that stated "could not allocate mem spaces", means that board needs replacing.
  11. Replies
    10
    Views
    424

    Carrier RTU Open Question

    Have an RTU that has quit twice on a "Program Stopped Alarm". Literature rather lacking on what causes the alarm. Downloading controller rings it back for a while. Anyone seen this before?
  12. Replies
    3
    Views
    252

    That is pretty much the same way I have it set up...

    That is pretty much the same way I have it set up now, just trying to get the 1 and done included in the sequence.
  13. Replies
    3
    Views
    252

    Spyder Morning Warm Up

    I am trying to figure a way to do morning warm up in a spyder. I am stuck at keeping warm up off after Return Air reaches set point or should I say keeping warm up from re-initializing if RA should...
  14. Replies
    3
    Views
    234

    Sent you some docs. Check out 74-2958 around page...

    Sent you some docs. Check out 74-2958 around page 60 is point lists
  15. Replies
    17
    Views
    1,013

    A series fan box is a constant volume application...

    A series fan box is a constant volume application where , if balanced properly, delivers the same amount of air to the space constantly. They work OK if balanced properly. I think people complain...
  16. Replies
    6
    Views
    306

    Thanks for the info.. If a lon integration is not...

    Thanks for the info.. If a lon integration is not possible can't a TCI be installed and I could use a Comm 4 driver on Jace? From what I have been researching it seems to be a good alternative, other...
  17. Replies
    6
    Views
    306

    That would be greatly appreciated. Serial # is...

    That would be greatly appreciated. Serial # is J97H72633. Having a difficult time getting info about these units.
  18. Replies
    6
    Views
    306

    Old Intellipak integration question

    Wonder if anyone knows if all Trane Intellipak RTUs are compatible with LCI-I cards. Unit is from 1997 and design sequence is "M". Was told I may need to check #'s on boards to determine if cards...
  19. Replies
    19
    Views
    2,675

    I have a customer with a number of 1997...

    I have a customer with a number of 1997 Intellipaks and is looking to install LCI cards in them to integrate into a lon network. Does anyone know if the LCI is compatible with a the older I-Paks,...
  20. Replies
    11
    Views
    811

    I have worked with it.

    I have worked with it.
  21. Replies
    11
    Views
    811

    You may want to see if the York units are...

    You may want to see if the York units are configured correctly, that requires using their Simplicity software tool which you can get from your local York/JCI dealer, if I remember correctly there is...
  22. Replies
    11
    Views
    811

    Are your York units Intelli-Comfort with...

    Are your York units Intelli-Comfort with FieldServer bacnet gateways?
  23. Replies
    7
    Views
    393

    Did one recently with xl10s and 15cs about 250...

    Did one recently with xl10s and 15cs about 250 devices, put in 3 jaces and supervisor. Time consuming, very. All 15cs were programmed differently so couldn't make one RTU template. Vavs and Fpts...
  24. Replies
    3
    Views
    174

    Thanks for the info. Now i'm getting licensing...

    Thanks for the info. Now i'm getting licensing errors, jace won't boot. Will go by distributors shop Monday with jace in hand, license is in and valid but still dead in water. Should have waited till...
  25. Replies
    3
    Views
    174

    connecting to a new fx60

    Have a job that speced an Fx60 jace. I am a Webs user and have never hooked up to a new Fx jace. Thought all FX jaces have an embedded workbench in them and could be accessed through browser but am...
Results 1 to 25 of 243
Page 1 of 10 1 2 3 4
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event