  1. did you set the bacnet instance id to a different...

    did you set the bacnet instance id to a different one before you put them on the network all spyders come with the same instance id got me the first time
    this is different than the mstp address
  2. Replies
    5
    Views
    789

    infocon makes a cbus driver that works very well...

    infocon makes a cbus driver that works very well you flash the easyio 30p and it sends the data to a jace
  3. Replies
    29
    Views
    5,421

    It is digital tone modified frequency or modem...

    It is digital tone modified frequency or modem audio
  4. Replies
    29
    Views
    5,421

    Yes it could be a big deal as long as it is comm3...

    Yes it could be a big deal as long as it is comm3 isolate ie not polarity sensitive already have driver for the comm3 non isolated ie polArity sensitive
  5. Replies
    29
    Views
    5,421

    The interface is a torroid transformer the...

    The interface is a torroid transformer the protocol is audio just as modem audio that is the data highway
  6. Replies
    28
    Views
    3,338

    i tried to email you the answer but your email...

    i tried to email you the answer but your email bounced email me at dlhvac@ptd.net
  7. Replies
    28
    Views
    3,338

    i use an infocon easyio 30p or a spyder micro

    i use an infocon easyio 30p or a spyder micro
  8. Replies
    28
    Views
    3,338

    the sensor has the output rating right on it i...

    the sensor has the output rating right on it i cannot recall offhand but the bypass damper cannot be controlled by the jace you must replace this controller with another the ccp panel previously...
  9. Replies
    28
    Views
    3,338

    yes but usually the supply house you purchase the...

    yes but usually the supply house you purchase the driver from is the first contact i use broudy supply in philadelphia, also cochrane supply in mich has the driver
  10. Replies
    28
    Views
    3,338

    worked well have done a bunch since then 12 or 13

    worked well have done a bunch since then 12 or 13
  11. Replies
    28
    Views
    3,338

    9600 8 none 1

    9600 8 none 1
  12. Replies
    3
    Views
    1,314

    broudy supply in phila has the drivers

    broudy supply in phila has the drivers
  13. Replies
    3
    Views
    1,314

    yes it is available thru maxline drivers with...

    yes it is available thru maxline drivers with infocon support for 10 years
  14. Replies
    28
    Views
    3,338

    Does the install have trane purple wire if not...

    Does the install have trane purple wire if not your on your own
  15. Replies
    28
    Views
    3,338

    Approx 80 or more points per rtu all the...

    Approx 80 or more points per rtu all the diagnostic alarms and you can also reset diagnostic faults
  16. Replies
    28
    Views
    3,338

    You can see more of the voyager and reliatel...

    You can see more of the voyager and reliatel points than with tranes software
  17. Replies
    28
    Views
    3,338

    The zoning and rtu overides are done in the jace

    The zoning and rtu overides are done in the jace
  18. Replies
    28
    Views
    3,338

    I would use a six if you are putting graphics on...

    I would use a six if you are putting graphics on it if noy jace 2 should work watch your java heap and busy time on the jace comm four is a reource hog
  19. Replies
    28
    Views
    3,338

    Sorry but i dont give away stations that ive done...

    Sorry but i dont give away stations that ive done but it is doable to integrate all that you stated
  20. Replies
    28
    Views
    3,338

    Maxline drivers owms the comm4 driver infocon...

    Maxline drivers owms the comm4 driver infocon sold the driver division go them but has a contract for 10 years to provide support
  21. Replies
    28
    Views
    3,338

    worked very well have done 12 to date

    worked very well have done 12 to date
  22. Replies
    29
    Views
    5,421

    you have to put the unit in tracer control and...

    you have to put the unit in tracer control and command the input mode
  23. Replies
    119
    Views
    16,086

    the ashrae show sent you an email

    the ashrae show sent you an email
  24. Replies
    119
    Views
    16,086

    the ashrae show

    the ashrae show
  25. Replies
    119
    Views
    16,086

    THE CONTROLLERS WILL BE OUT AT THE SHOW IN DALLAS...

    THE CONTROLLERS WILL BE OUT AT THE SHOW IN DALLAS IM BETA TESTING A PROTOTYPE