Search:

Type: Posts; User: rlxdn10sity

Page 1 of 8 1 2 3 4

Search: Search took 0.02 seconds.

  1. Replies
    39
    Views
    6,176

    I usually wire the condensate safety switch to...

    I usually wire the condensate safety switch to break R. 99% of the time I install a stat powered by equipment x-former. In the case of an erratic float it should cause the stat delay to come into the...
  2. Poll: +1

    +1
  3. Replies
    8
    Views
    733

    Compressors are generally louder on start up than...

    Compressors are generally louder on start up than they are when running at operational speed. It is hard to say whether the noise you are hearing is normal or not without being able to hear it, but a...
  4. Replies
    30
    Views
    4,238

    Wow, that is quite unorthodox. I did not notice,...

    Wow, that is quite unorthodox. I did not notice, I guess I should have paid attention to where the lineset was routed.
  5. Replies
    30
    Views
    4,238

    Well now I can see the indoor equipment pic. of...

    Well now I can see the indoor equipment pic. of the new install.
    No wonder the HX is so ate up. I did not realize it was on the discharge side of the coil. The new transition from the filtration...
  6. Replies
    30
    Views
    4,238

    I don't see any pics of the furnace install ...

    I don't see any pics of the furnace install
    :confused:
  7. Replies
    27
    Views
    4,565

    This is the model impact driver I have:...

    This is the model impact driver I have:
    http://www.hilti.com/holcom/modules/prcat/prca_popupproductpic.jsp?OID=20395
    The SID is 1/4" hex, the SIW is 1/2" square.

    This is the model hammer...
  8. Replies
    16
    Views
    1,959

    I'm finding myself disapointed in the wireless...

    I'm finding myself disapointed in the wireless capabilities of my 556. I bought the whole setup expecting to be able to monitor liquid line temp. at the evap. coil while adjusting/checking system...
  9. Replies
    6
    Views
    536

    Thanks for correcting my impression, I'm sorry,...

    Thanks for correcting my impression, I'm sorry, I'm never very good at accurately interpreting the tone, intent or direction of dialogue in text.
    After re-reading your post it seems you are...
  10. Replies
    6
    Views
    536

    Thank you Jim for the mildly dissapointing answer...

    Thank you Jim for the mildly dissapointing answer to my question, you are the ultimate go to guy on Testo product. Does the 625 receiver display direct WB reading based on data from the same handle...
  11. Replies
    6
    Views
    536

    No, I have to ask someone why I am not getting a...

    No, I have to ask someone why I am not getting a WB reading directly on the display of this Super device. Some Super device that cannot x-reference the wet bulb calc. on its own., and cannot provide...
  12. Replies
    27
    Views
    4,565

    I got out of Dewalt a couple of years ago. I've...

    I got out of Dewalt a couple of years ago. I've used Bosch, Milwaukee, Makita, Porter Cable, and maybe another one or two. Hilti cordless impacts and drills are unmatched by anything I've ever used....
  13. Replies
    6
    Views
    536

    Testo 556 wireless kit

    Testo instructions leave much to be desired. I finally have my 556 wireless up and running, it is super awesome. I just picked up WB probe head part# 0636_9736, today that works with the wireless...
  14. Replies
    39
    Views
    2,697

    What about the 506? Supply house has a 510 and a...

    What about the 506? Supply house has a 510 and a 506. The 506 reads in W.C. out to 1000th and the 510 reads out to 100th. I like as precise a tool as I can have but I'm not sure if the 506 (other...
  15. Replies
    5
    Views
    719

    How do you go about cleaning it?

    How do you go about cleaning it?
  16. Replies
    5
    Views
    719

    JB Micron Guage

    Any opinions good or bad about the JB DV-22N Micron Guage? What micron guage do you guys find to be most reliable? Should sensor of micron guages be cleaned or serviced periodically?
  17. Replies
    41
    Views
    2,865

    Well I still have not made the purchase. I had...

    Well I still have not made the purchase. I had pretty well settled on getting the 1250. But after continuing to check out my options, I'm up in the air between them and the Testo 556. I am under the...
  18. Replies
    41
    Views
    2,865

    I'll check out the MFM300. Seems like hoses would...

    I'll check out the MFM300. Seems like hoses would be a good thing though if you need to adjust charge.
  19. Replies
    41
    Views
    2,865

    Thanks everyone. I intend to place my order...

    Thanks everyone. I intend to place my order tomorrow.
    Bar clamp vs. spring/plier clamp seems tough to figure out though. Seems like the spring/plier syle clamp would be quick and strong connection...
  20. Replies
    41
    Views
    2,865

    Buying my first digital gauges...

    I've read a good bit here in the forums and it seems all opinions point to the Digi-Cool guage unit as being superior. Am I correct in this conclusion or have I not read everything that I need too? ...
  21. Replies
    2
    Views
    664

    I'm bidding my first commercial job and hoping...

    I'm bidding my first commercial job and hoping one or more of you guys may have experience enough to look at my numbers briefly and tell me if I've missed anything and if I need to make any...
  22. Replies
    3
    Views
    781

    I suspect they would work in conjunction provided...

    I suspect they would work in conjunction provided that the discharge of the power vents were not cumulatively greater than the air intake available from the eave vents.
  23. Replies
    3
    Views
    781

    Temperatures in vented attics commonly exceed...

    Temperatures in vented attics commonly exceed well over 100 degrees in the summer months. Power venting will reduce temp. but at a cost of electrical usage and significant noise factor. There is...
  24. Replies
    46
    Views
    6,825

    Something that apparently is very incorrect about...

    Something that apparently is very incorrect about this install is that the sight is only 5' from the compressor. Filling to full sight would require liquid for over 100' feet of lineset. Should'nt...
  25. Replies
    46
    Views
    6,825

    Mr. Fox, I'm sorry I made that statement on the...

    Mr. Fox, I'm sorry I made that statement on the first page of this thread. I believed what I was told by the distributor about charging this system, to be true.
  26. Replies
    46
    Views
    6,825

    Ok guys here are the #'s YORK Outside Unit:...

    Ok guys here are the #'s

    YORK
    Outside Unit:
    Mod# H2CE120A25A

    Indoor AHU:
    Mod# K3EU120A33B

    I have removed and repaired the condensing coil. My plan at this time is to reinstall the coil,...
  27. Replies
    46
    Views
    6,825

    To brettIn - if you'll notice I did ask...

    To brettIn - if you'll notice I did ask questions. I asked for superheat and/or subcooling charge info. and was told it was not available. I was then told to charge it the way I did by what should...
  28. Replies
    46
    Views
    6,825

    I wanna thank all of you again for your replies...

    I wanna thank all of you again for your replies to this post. There seems to be alot of suggestions but I see the majority lean toward potential compressor problems. Websy mentions that depending on...
  29. Replies
    46
    Views
    6,825

    There is no factory charge stated on the rating...

    There is no factory charge stated on the rating plate. I gather that from what I'm being told from you guys I should pursue speaking with someone at YORK about unit specific charging tables and weigh...
  30. Replies
    46
    Views
    6,825

    I called the York distributor in my area and...

    I called the York distributor in my area and asked for charging tables. The tech. support guy said that there was no charging info. available for that type of unit. He then asked me if there was a...
  31. Replies
    46
    Views
    6,825

    You do not give reasoning for diagnosis of over...

    You do not give reasoning for diagnosis of over charged. This size system is to be charged until no vapor is present in sightglass when running under stabilized conditions. Also the head pressure is...
  32. Replies
    2
    Views
    814

    You should contact the manufacturer of the unit...

    You should contact the manufacturer of the unit for the proper components to perform conversion. Typically involves changing burner orifices, regulator spring and if applicable the pilot orifice....
  33. Replies
    46
    Views
    6,825

    I looked at a 10 ton (2-5 ton comps.tandem) YORK...

    I looked at a 10 ton (2-5 ton comps.tandem) YORK commercial split system today. The sight glass showed significant vapor circulating through the liquid line. I added refrigerant until the sight was...
  34. Replies
    5
    Views
    800

    What makes you say its over charged? The head...

    What makes you say its over charged? The head presure is not high enough relevant to outdoor ambient and high suction to indicate overcharge.
  35. Replies
    85
    Views
    4,902

    The cultural sovereignty of this nation has been...

    The cultural sovereignty of this nation has been compromised and is rapidly detriorating due in large part to the illegal immigrant. It is so rampant that music, advertising, and almost every other...
  36. Replies
    5
    Views
    800

    I looked at a 10 ton (2-5 ton comps.tandem) YORK...

    I looked at a 10 ton (2-5 ton comps.tandem) YORK commercial split system today. The sight glass showed significant vapor circulating through the liquid line. I added refrigerant until the sight was...
Results 1 to 36 of 388
Page 1 of 8 1 2 3 4
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event