    Why can’t you download the I/NET 2000 bin file to...

    Why can’t you download the I/NET 2000 bin file to the new PCU? They are backwards compatible.
  2. I believe the last flash file is v4.500064.

    I believe the last flash file is v4.500064.
  3. In IgraphW if you got to Settings > Ports, you...

    In IgraphW if you got to Settings > Ports, you will be able to select your PC com port and baud rate. It is like setting up a HyperTerminal session. I believe you can use an RS-232 direct connect...
  4. Do you know what type of fan powered box it is,...

    Do you know what type of fan powered box it is, parallel or series? On a parallel box the fan is typically used as first stage heat and will cycle on/off. On a series box the fan is not intermittent...
  5. Are you using the IgraphW software?

    Are you using the IgraphW software?
  6. Replies
    3
    Views
    648

    As TLP said we usually purchase them from our...

    As TLP said we usually purchase them from our vendors we use for Security/Access Controls/CCTV. I have bought a few different ones. Most of the time they are for projects with chilled beams or...
  7. Replies
    13
    Views
    1,610

    I cannot think of anything that would cause that....

    I cannot think of anything that would cause that. I will have to give it some more thought. Is there anything attached to those points like an event or another point extension?
  8. Those sound like old SFHC units. When I worked...

    Those sound like old SFHC units. When I worked for Trane we did a few jobs where we converted those units from Honeywell W7100's to PCM’s. I recall it was quite the brain swap. Do the units you are...
  9. Replies
    3
    Views
    687

    We have used them a bunch of times as mentioned...

    We have used them a bunch of times as mentioned above, usually in chiller plants on condenser water and chilled water piping with Keystone and Bray valves and never had any problems. If I remember...
  10. Replies
    2
    Views
    693

    Are there any lookup tables on those input...

    Are there any lookup tables on those input points? Also is the range and counts (resolution) setup?
  11. Replies
    13
    Views
    1,610

    Could be a few different things causing it. ...

    Could be a few different things causing it.

    Just a few basic comments;

    1) Are you using low cap 22 or 24 gauge wire on the B Channel?

    2) Are the shields bonded continuous throughout the B...
  12. Replies
    1
    Views
    481

    If you are in Boston, did you try Interstate HVAC...

    If you are in Boston, did you try Interstate HVAC Controls or F.W. Webb? They both rep the FX line and I would think have some training materials you could use. For regular Tridium Niagara stuff, we...
  13. Replies
    11
    Views
    1,447

    You may want to look at Veris. I am doing a...

    You may want to look at Veris. I am doing a project now using their meters on a Modbus integration. I am using the E50C2. There are several models to choose from. Modbus and BACnet are standard with...
  14. Replies
    15
    Views
    2,778

    techbas, I just emailed it to you.

    techbas,

    I just emailed it to you.
  15. Replies
    11
    Views
    1,347

    If you look at the LED’s (U22) on the 7798B...

    If you look at the LED’s (U22) on the 7798B I/SITE are TXA1 and RXA1 flashing? Those LED’s indicate transmit data to the Sub-LAN port and receive data from the Sub-LAN port.
  16. Replies
    11
    Views
    1,347

    Here are the attachments

    Here are the attachments
  17. Replies
    11
    Views
    1,347

    The 7798 and the SCU are full wave devices. Check...

    The 7798 and the SCU are full wave devices. Check and make sure your grounding is correct on the line side. See attached bit map.

    The double address mode is supported on the SCU1200 only.

    For...
  18. Replies
    25
    Views
    6,021

    I have contacts by region, however without...

    I have contacts by region, however without knowing where you are located I would not know who you should contact.

    Here is a link to their website. Click on contact and leave them a message. Be...
  19. Replies
    25
    Views
    6,021

    Your best bet if you are interested in upgrading...

    Your best bet if you are interested in upgrading this system is to contact your local Schneider Electric branch office or authorized partner.

    If you are upgrading from I/NET 2000, it will...
  20. Replies
    6
    Views
    1,405

    I have a large information vault……. And I had to...

    I have a large information vault……. And I had to go deep inside to find these.

    Funny thing is that these VAV boxes were made in the mid 1970’s. I was probably in Kindergarten when those documents...
  21. Replies
    6
    Views
    1,405

    Those look like some very old boxes. Checkout the...

    Those look like some very old boxes. Checkout the pdf’s I have hopefully they will have what you are looking for.
  22. Replies
    25
    Views
    6,021

    Just a quick comment; you responded to a 7 year...

    Just a quick comment; you responded to a 7 year old thread why not start a new thread specific to your issue.

    As azzad said the product is still supported and available, however the hardware and...
  23. That's pretty funny.

    That's pretty funny.
  24. Replies
    3
    Views
    531

    You might want to look at the wireless pneumatic...

    You might want to look at the wireless pneumatic thermostat from Cypress Envirosystems. The last time I estimated a project with their product they only offered a BACnet interface. Their rep did tell...
  25. Replies
    22
    Views
    3,904

    Sure seen a lot of those in their day. ...

    Sure seen a lot of those in their day.

    Schneider Electric issued a product announcement back in 2010 that the System 8000 products were being discontinued. That included the TP-8x series...