  1. Replies
    17
    Views
    710

    I'm not 100% sure that this is relevant here, but...

    I'm not 100% sure that this is relevant here, but if the points are coming from the maintenance or service tables, you can't see them in AX unless you have the enhanced CCN driver. And, supposedly...
  2. Replies
    11
    Views
    860

    One more interested - email in profile. Thanks!

    One more interested - email in profile.

    Thanks!
  3. I don't know if this is related to this or not,...

    I don't know if this is related to this or not, but for what it's worth - I couldn't get my U10 to work in VMware once I upgraded laptops until I put a USB hub between the laptop and U10. It worked...
  4. Replies
    44
    Views
    5,286

    I think a lot of the issues you experienced are...

    I think a lot of the issues you experienced are more related to Sedona than EasyIO... But you're right - until you get the hang of it, copying the kit and manifest files is a pain.
  5. To skwsproul's point, MOV may be the way to go. ...

    To skwsproul's point, MOV may be the way to go. There were several end users in the class I attended, and while they were ineligible for certification, they got the exact same training as the rest...
  6. I know you said Wifi was almost a must, but if...

    I know you said Wifi was almost a must, but if you can get around that, the KMC FlexStats will do exactly what you want. Pull a Cat5/6 drop to each stat, it talks BACnet/IP natively, and is fully...
  7. Thread: Html code

    by USC Anteater
    Replies
    4
    Views
    529

    You'll need some JavaScript for that piece...

    You'll need some JavaScript for that piece...
  8. Replies
    1
    Views
    366

    It started out as just a naming standard, but the...

    It started out as just a naming standard, but the REST API was added more recently to address some limitations in oBIX, and some bugs in Tridium's oBIX implementation.
  9. I'm not sure if this is the exact same issue or...

    I'm not sure if this is the exact same issue or not, but I had a cooling setpoint failure message this week from a Reliatel with LCI-R. My setpoints are all written over the network, so there are no...
  10. Replies
    5
    Views
    773

    Can you discover the CCN device from NST? Baud...

    Can you discover the CCN device from NST? Baud rates the same? And when I said network and node, I meant bus and element, but you caught that... :)
  11. Replies
    5
    Views
    773

    I have used it without issue with both 3.6 and...

    I have used it without issue with both 3.6 and 3.7. Make sure you set the network number for the network you are joining, and set a unique node address. Outside of that, discovery should just work.
  12. Replies
    2
    Views
    1,008

    The AX Infinity driver uses a RS-232 connection...

    The AX Infinity driver uses a RS-232 connection to the NetController...

    http://resources.lynxspring.com/index.php/jenesys-home/jenesys-drivers?task=document.viewdoc&id=86
  13. Replies
    6
    Views
    1,066

    If all you need are sunrise and sunset times, I...

    If all you need are sunrise and sunset times, I believe you can use the SunPosition object under the Weather palette without a dependency on the weather service. You input the latitude and...
  14. I'm not sure if you can do this with a 403 or...

    I'm not sure if you can do this with a 403 or not, but on the 600, you can enable an FTP server from the serial shell, and then get the license file via FTP. Gets you around any brand restriction to...
  15. Replies
    3
    Views
    578

    I'm not aware of any performance differences...

    I'm not aware of any performance differences between desktop versions of VMware. As you mentioned - RAM is key...
  16. Replies
    1
    Views
    450

    Did you forward UDP port 1876? If I recall...

    Did you forward UDP port 1876? If I recall correctly, it needs UDP 1876 instead of TCP 1876. Also, this is assuming you are using Sedona connectivity instead of the TCOM driver...
  17. Replies
    6
    Views
    766

    http://www.ddc-online.org/

    http://www.ddc-online.org/
  18. Replies
    281
    Views
    40,704

    Vitinrj - can I get in on that action also?

    Vitinrj - can I get in on that action also?
  19. Replies
    2
    Views
    538

    http://controltrends.org

    http://controltrends.org
  20. Replies
    6
    Views
    1,111

    As a worst-case scenario, could you use a...

    As a worst-case scenario, could you use a NetController II to convert from InfiNet to BACnet? I saw worst case because I'm guessing that thing is not cheap...
  21. Replies
    2
    Views
    716

    Those look like OEMed KMC controllers. Not sure...

    Those look like OEMed KMC controllers. Not sure if Honeywell has it locked down or not, but if it is an unmodified KMC controller, you'd use KMC BACStage.
  22. Replies
    5
    Views
    860

    You have to use the tags to do anything. As far...

    You have to use the tags to do anything. As far as data goes, it will take however much or little that you have as far as different points go. All of the points you mentioned would definitely be...
  23. Replies
    5
    Views
    860

    This is definitely hotter than hot in the...

    This is definitely hotter than hot in the marketplace. We are using SkySpark from SkyFoundry to do similar stuff.
  24. Replies
    2
    Views
    427

    I ran into the same issue a couple of months ago....

    I ran into the same issue a couple of months ago. IIRC, the BCP service was referencing c:\LonWorks, but all of the files were in c:\Program Files\LonWorks. I changed the reference under the BCP...
  25. Replies
    119
    Views
    14,847

    Assuming that the EasyIO FG controllers you...

    Assuming that the EasyIO FG controllers you mentioned are what they are referring to as "The Beast", they are supposed to be about 30% more than the 30Ps. Last I heard was that they are supposed to...