Search:

Type: Posts; User: MaxBurn

Page 1 of 20 1 2 3 4

Search: Search took 0.02 seconds.

  1. Replies
    9
    Views
    397

    Some of the OEM's don't even download source...

    Some of the OEM's don't even download source files for the same reason.
  2. Replies
    5
    Views
    264

    RC642D is still available but I hesitate to...

    RC642D is still available but I hesitate to mention it because you need ALC tools to program it. There is some modes where they can be set up with dip switches but not sure how useful that is on...
  3. Replies
    5
    Views
    264

    I had a big problem with an OEM KMC FlexStat and...

    I had a big problem with an OEM KMC FlexStat and as such I wouldn't recommend it.
    We didn't get into programming the stat at all though, used it as Bard supplied. They would all start...
  4. Replies
    5
    Views
    264

    I had a big problem with an OEM KMC FlexStat and...

    I had a big problem with an OEM KMC FlexStat and as such I wouldn't recommend it.
    We didn't get into programming the stat at all though, used it as Bard supplied. They would all start...
  5. Replies
    3
    Views
    345

    On the LGR properties page there is a modstat...

    On the LGR properties page there is a modstat button, below that button there is a "show bindings" button. Hit that and give us the results here. If you don't have bindings you aren't going to be...
  6. Replies
    20
    Views
    718

    On the ALC WebCTRL side of things the batteries...

    On the ALC WebCTRL side of things the batteries on older modules seem to be good for 8+ years with the 2330 or 2325 button batteries. The newer modules with the CR123 can go quick if it sees a lot of...
  7. Bard OEM KMC BACnet stat and Dehumidification

    We have three wings of Bard units with OEM KMC stats all running on BACnet MS/TP. Just noticed a problem with their dehumidification sequence. Or a problem with my understanding on how to run it.
    ...
  8. Replies
    6
    Views
    256

    Good point, I forgot about that. Do you know what...

    Good point, I forgot about that. Do you know what linux distro they are using on that box?
  9. Replies
    6
    Views
    256

    This is for the black box server that i-Vu comes...

    This is for the black box server that i-Vu comes on right? Seems a little under specc'd to me, for WebCTRL I've been recommending a minimum of 4gb ever sense 7 shipped and a little before honestly....
  10. Replies
    17
    Views
    1,054

    Thank you, my email is in my profile here, just...

    Thank you, my email is in my profile here, just click on my name.
  11. Replies
    17
    Views
    1,054

    Nope.

    Nope.
  12. Replies
    17
    Views
    1,054

    Regarding the KMC flex stats does anyone have a...

    Regarding the KMC flex stats does anyone have a BACnet point list for them? Something with point descriptions?

    We worked from a discovery and seemed to get things working after adding a couple...
  13. Replies
    6
    Views
    347

    Is this for WebCTRL? ALC does tend to lag in...

    Is this for WebCTRL? ALC does tend to lag in getting a patch out after finding some new java update breaks something for 5.5 and lower.

    Your dealers service dept should be able to send you the...
  14. Replies
    6
    Views
    347

    Constant annoyance, I'm so glad we don't need...

    Constant annoyance, I'm so glad we don't need java anymore with the latest version.
  15. Replies
    29
    Views
    1,473

    I have a couple of these, one for the laptop and...

    I have a couple of these, one for the laptop and one for me. They fit in my backpack. About $9.

    http://www.dickssportinggoods.com/graphics/product_images/pDSP1-10886923p275w.jpg

    I must admit...
  16. Replies
    3
    Views
    317

    That driver suggests that you are looking at an...

    That driver suggests that you are looking at an integration already, to a Dataguard system. You will likely find something between 200 and 1000 points of integration under that LGR. The points in the...
  17. Sounds like you need a local account added to...

    Sounds like you need a local account added to that computer so you can login to it with no network access. If it's normal for it to not have network access than that's not really optional.
  18. Replies
    3
    Views
    250

    Depending on what version of software the LGE was...

    Depending on what version of software the LGE was used under there are two different ways to put the IP in.

    If it is "legacy" exec 6 it needs to be programmed with supervision or webctrl as a...
  19. Replies
    9
    Views
    1,153

    It might already depending on how it was...

    It might already depending on how it was programmed.

    Turn it off and move the ARCnet/9600/38400 jumper to the 9600/38400 side and turn dip switch 1 on for 38,400 or off for 9600. Wire your MS/TP...
  20. Replies
    8
    Views
    618

    Thanks for sharing! Wonder how many hours of...

    Thanks for sharing!

    Wonder how many hours of programming went into that thing? Each one had to be a one off production I bet.
  21. Replies
    4
    Views
    327

    Yes just some basic due diligence before you call...

    Yes just some basic due diligence before you call them back but it does seem to be that device that's the issue.
  22. Replies
    4
    Views
    327

    Does your module work right next to the device...

    Does your module work right next to the device you are reading?

    Do the other usual wire checks, ohming to each other and each to ground etc.

    Can you get modscan and a communication adapter to...
  23. If you are concerned with the wall contaminating...

    If you are concerned with the wall contaminating the temp reading of the stat I don't think you need a new stat, just add some insulation behind the stat. Should be a foam wall plate backing...
  24. Replies
    21
    Views
    1,390

    I'm now carrying a fluke 376 with integrated amp...

    I'm now carrying a fluke 376 with integrated amp clamp and back light, I've taken a real liking to it. For ages I've carried the various versions of the fluke 77 and I still have one but that's...
  25. Replies
    8
    Views
    286

    Seconded, I ran into this as well. The new ZN...

    Seconded, I ran into this as well. The new ZN modules are shipping with updated hardware which requires a 6.xx.xxx module driver.

    Basically the stance of ALC is always use the latest module...