Search:

Type: Posts; User: krac

Page 1 of 7 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    43
    Views
    1,304

    For the JCI integration we used an FX-60 because...

    For the JCI integration we used an FX-60 because we know the N2 driver is solid. Found several VMA's offline and needed to troubleshoot an N2 bus wiring issue. For the ALC we left the Langate in...
  2. Replies
    43
    Views
    1,304

    Finally over the Invensys LON learning curve (at...

    Finally over the Invensys LON learning curve (at least I hope so) Found copies of all the Workplace Tech project files which allowed us to get a handle on what is going on inside the MZ's. Discovered...
  3. Replies
    43
    Views
    1,304

    Looks like the Node Utility program only works...

    Looks like the Node Utility program only works directly connected to the local lon bus. Is there an export function that is part of LonMaker running on the server?

    One issue I am having is not...
  4. Replies
    43
    Views
    1,304

    Looks like the XIF files used for the MZ's are...

    Looks like the XIF files used for the MZ's are not on the Server. Is there a way to export the Lonmaker database into a format that Tridium could use?
  5. Replies
    43
    Views
    1,304

    The system I am working on was installed in 2005,...

    The system I am working on was installed in 2005, and the newest building is 2010. You guys are not making me feel warm and fuzzy about the system we taking over. So your saying without the source...
  6. Replies
    43
    Views
    1,304

    Now that we have the LON discovery working the...

    Now that we have the LON discovery working the last thing we need to figure out is how to program MNL-800's. This is not something we actually have to do as part of our contract, but I feel bad for...
  7. Replies
    1
    Views
    171

    Not sure but if you look at the manual on page...

    Not sure but if you look at the manual on page 2-15 they talk about installing the communications card as an option. I would bet the switches are on the card.
  8. Replies
    43
    Views
    1,304

    Found some of the xif files in a working...

    Found some of the xif files in a working directory and the backup zip file, but the Device manager property sheet shows the xif path pointing to a CD for a few devices. I will give see if I can...
  9. Replies
    43
    Views
    1,304

    All the devices discovered perfect. Looked in the...

    All the devices discovered perfect. Looked in the project folder an found hundreds of .xif files under this network. I imagine whoever did the install has a bunch of files that he/she just copies on...
  10. Replies
    43
    Views
    1,304

    Looks like entering the Domain ID did the trick....

    Looks like entering the Domain ID did the trick. I was able to discover all the devices on the Lon segment. Only problem now is for some reason the MNL-800 and 150's won't learn and don't come up...
  11. Replies
    43
    Views
    1,304

    When I run the Utility and test the RNI...

    When I run the Utility and test the RNI connnection it fails:

    Windows Sockets API: WinSock 2.0 (Running)
    xDriver Remote Network Interface: X.Default.Forbes (This is the LonMaker Network I...
  12. Replies
    43
    Views
    1,304

    Looks like LonMaker didn't like it when I took...

    Looks like LonMaker didn't like it when I took the iLon Server offline earlier. When I try to open the Network DB with LonMaker, I get a NI31 error 'Unable to change the state of the network...
  13. Replies
    43
    Views
    1,304

    I show a domain size of 1 and domain id of 19,...

    I show a domain size of 1 and domain id of 19, and the check box to randomly create domain ID is checked. Hating asking dumb questions, but does the Jace LON domain need to match the LNS Domain...
  14. Replies
    43
    Views
    1,304

    They have a single Server that runs LNS and...

    They have a single Server that runs LNS and Control Suite. The users run remote desktop to run the GUI.
  15. Replies
    43
    Views
    1,304

    Looked all over the Lonmaker drawing and and...

    Looked all over the Lonmaker drawing and and unable to find any reference to Domain size or ID. Any idea how to find the domain info?
  16. Replies
    43
    Views
    1,304

    The iLon is a LAN router back to the LNS Server. ...

    The iLon is a LAN router back to the LNS Server. We are integrating the existing Invensys system which used the iLon's into the new Tridium network. I was hoping to have both systems running next to...
  17. Replies
    43
    Views
    1,304

    Removed ilon Server and still not able to...

    Removed ilon Server and still not able to discover the other Lon devices and the points on the two devices I added manually fault when the Jace polls them.
  18. Replies
    43
    Views
    1,304

    There are two separate LonMaker network drawings,...

    There are two separate LonMaker network drawings, and as far as I can see each network is independent.



    In the device setup I see a channel and a subnet ID which I refer to as address. Yes...
  19. Replies
    43
    Views
    1,304

    The LNS server is back at the facilities building...

    The LNS server is back at the facilities building and connects to both networks using the iLon Server in this building and two iLon 600's in the other building. The LNS server is also running Control...
  20. Replies
    43
    Views
    1,304

    Looking at the network with LonMaker, the device...

    Looking at the network with LonMaker, the device configuration seems normal. The iLon Server had the same address as the Tridium LocalLonDevice, but changing that to another number didn't help. The...
  21. Replies
    43
    Views
    1,304

    Not sure what the iLon Server is doing other than...

    Not sure what the iLon Server is doing other than acting as a Ethernet router to the LNS Server. LON maker was used for both of the networks at this site. Wasn't comfortable disconnecting the iLon...
  22. Replies
    43
    Views
    1,304

    Invensys LON to Tridium conversion

    In the process of integrating an existing Invensys Lon network into a new Tridium system and having some issues. The integration method provided to me calls for installing a LON Jace on to the...
  23. Replies
    27
    Views
    2,756

    Not sure if you are joking or not. With Trane you...

    Not sure if you are joking or not. With Trane you never know...
  24. Replies
    27
    Views
    2,756

    For customers that would like to integrate their...

    For customers that would like to integrate their Trane equipment and not have to purchase a $10k BCU.
  25. Replies
    27
    Views
    2,756

    Stumbled on this device sold by Trane in Europe:...

    Stumbled on this device sold by Trane in Europe: BAS-SVX08D-E4. I am sure this is not something available in USA. Can't imagine why the Europeans don't use BCU's.
Results 1 to 25 of 172