03-30-2013, 01:18 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
For the JCI integration we used an FX-60 because...
For the JCI integration we used an FX-60 because we know the N2 driver is solid. Found several VMA's offline and needed to troubleshoot an N2 bus wiring issue. For the ALC we left the Langate in...
-
03-30-2013, 11:46 AM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
Finally over the Invensys LON learning curve (at...
Finally over the Invensys LON learning curve (at least I hope so) Found copies of all the Workplace Tech project files which allowed us to get a handle on what is going on inside the MZ's. Discovered...
-
03-25-2013, 06:55 AM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
Looks like the Node Utility program only works...
Looks like the Node Utility program only works directly connected to the local lon bus. Is there an export function that is part of LonMaker running on the server?
One issue I am having is not... -
03-23-2013, 11:00 AM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
Looks like the XIF files used for the MZ's are...
Looks like the XIF files used for the MZ's are not on the Server. Is there a way to export the Lonmaker database into a format that Tridium could use?
-
03-21-2013, 08:11 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
The system I am working on was installed in 2005,...
The system I am working on was installed in 2005, and the newest building is 2010. You guys are not making me feel warm and fuzzy about the system we taking over. So your saying without the source...
-
03-19-2013, 05:52 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
Now that we have the LON discovery working the...
Now that we have the LON discovery working the last thing we need to figure out is how to program MNL-800's. This is not something we actually have to do as part of our contract, but I feel bad for...
-
03-19-2013, 09:05 AM
Thread: Setting Modbus Address for a GE EPM 5100
by krac- Replies
- 1
- Views
- 171
Not sure but if you look at the manual on page...
Not sure but if you look at the manual on page 2-15 they talk about installing the communications card as an option. I would bet the switches are on the card.
-
03-16-2013, 11:48 AM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
Found some of the xif files in a working...
Found some of the xif files in a working directory and the backup zip file, but the Device manager property sheet shows the xif path pointing to a CD for a few devices. I will give see if I can...
-
03-16-2013, 09:35 AM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
All the devices discovered perfect. Looked in the...
All the devices discovered perfect. Looked in the project folder an found hundreds of .xif files under this network. I imagine whoever did the install has a bunch of files that he/she just copies on...
-
03-15-2013, 10:31 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
Looks like entering the Domain ID did the trick....
Looks like entering the Domain ID did the trick. I was able to discover all the devices on the Lon segment. Only problem now is for some reason the MNL-800 and 150's won't learn and don't come up...
-
03-14-2013, 08:19 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
When I run the Utility and test the RNI...
When I run the Utility and test the RNI connnection it fails:
Windows Sockets API: WinSock 2.0 (Running)
xDriver Remote Network Interface: X.Default.Forbes (This is the LonMaker Network I... -
03-14-2013, 07:31 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
Looks like LonMaker didn't like it when I took...
Looks like LonMaker didn't like it when I took the iLon Server offline earlier. When I try to open the Network DB with LonMaker, I get a NI31 error 'Unable to change the state of the network...
-
03-14-2013, 06:57 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
I show a domain size of 1 and domain id of 19,...
I show a domain size of 1 and domain id of 19, and the check box to randomly create domain ID is checked. Hating asking dumb questions, but does the Jace LON domain need to match the LNS Domain...
-
03-14-2013, 06:37 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
They have a single Server that runs LNS and...
They have a single Server that runs LNS and Control Suite. The users run remote desktop to run the GUI.
-
03-14-2013, 05:44 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
Looked all over the Lonmaker drawing and and...
Looked all over the Lonmaker drawing and and unable to find any reference to Domain size or ID. Any idea how to find the domain info?
-
03-14-2013, 05:41 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
The iLon is a LAN router back to the LNS Server. ...
The iLon is a LAN router back to the LNS Server. We are integrating the existing Invensys system which used the iLon's into the new Tridium network. I was hoping to have both systems running next to...
-
03-14-2013, 05:35 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
Removed ilon Server and still not able to...
Removed ilon Server and still not able to discover the other Lon devices and the points on the two devices I added manually fault when the Jace polls them.
-
03-13-2013, 06:09 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
There are two separate LonMaker network drawings,...
There are two separate LonMaker network drawings, and as far as I can see each network is independent.
In the device setup I see a channel and a subnet ID which I refer to as address. Yes... -
03-13-2013, 05:51 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
The LNS server is back at the facilities building...
The LNS server is back at the facilities building and connects to both networks using the iLon Server in this building and two iLon 600's in the other building. The LNS server is also running Control...
-
03-13-2013, 05:43 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
Looking at the network with LonMaker, the device...
Looking at the network with LonMaker, the device configuration seems normal. The iLon Server had the same address as the Tridium LocalLonDevice, but changing that to another number didn't help. The...
-
03-13-2013, 05:30 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
Not sure what the iLon Server is doing other than...
Not sure what the iLon Server is doing other than acting as a Ethernet router to the LNS Server. LON maker was used for both of the networks at this site. Wasn't comfortable disconnecting the iLon...
-
03-13-2013, 04:04 PM
Thread: Invensys LON to Tridium conversion
by krac- Replies
- 43
- Views
- 1,304
Invensys LON to Tridium conversion
In the process of integrating an existing Invensys Lon network into a new Tridium system and having some issues. The integration method provided to me calls for installing a LON Jace on to the...
-
02-18-2013, 07:23 PM
Thread: Niagara AX to Trane comm3 and comm4 advise
by krac- Replies
- 27
- Views
- 2,756
Not sure if you are joking or not. With Trane you...
Not sure if you are joking or not. With Trane you never know...
-
02-18-2013, 07:21 PM
Thread: Niagara AX to Trane comm3 and comm4 advise
by krac- Replies
- 27
- Views
- 2,756
For customers that would like to integrate their...
For customers that would like to integrate their Trane equipment and not have to purchase a $10k BCU.
-
02-18-2013, 12:42 PM
Thread: Niagara AX to Trane comm3 and comm4 advise
by krac- Replies
- 27
- Views
- 2,756
Stumbled on this device sold by Trane in Europe:...
Stumbled on this device sold by Trane in Europe: BAS-SVX08D-E4. I am sure this is not something available in USA. Can't imagine why the Europeans don't use BCU's.