Yesterday, 08:29 AM
Thread: Object Memory Usage Concern????
by integrator- Replies
- 7
- Views
- 139
Hello, Flash memory is the same as a standard...
Hello,
Flash memory is the same as a standard PC idea. For an NAE35 or NAE45 it has allocated 12Mb (uncompressed) of flash memory from the NAEs 128Mb of flash nonvolatile memory. For the NAE55 or... -
06-17-2013, 10:25 PM
Thread: Object Memory Usage Concern????
by integrator- Replies
- 7
- Views
- 139
Hello, The CCT performs a count of obects and...
Hello,
The CCT performs a count of obects and shows this as the % at the bottom. So for example, if you have an application with 2500 objects, this gets divided by the default number of 3000 and... -
06-17-2013, 09:32 AM
Thread: Cpu Usage @100%
by integrator- Replies
- 6
- Views
- 173
Hello, If the suggestion from Chinna doesn't...
Hello,
If the suggestion from Chinna doesn't work you can do the following
From the "Expert Mode", you will have the Device Diagnostic Object. This will create a report that breaks out CPU use... -
06-14-2013, 08:55 AM
Thread: Metasys ADS Data Sharing
by integrator- Replies
- 4
- Views
- 206
Good idea. You would need to setup a schedule and...
Good idea. You would need to setup a schedule and do a pull every time you need data. The MEU comes with the ADS so no extra purchase is requried.
-
06-13-2013, 08:04 PM
Thread: Metasys ADS Data Sharing
by integrator- Replies
- 4
- Views
- 206
Hello, JCI had DDE one time to do this. I...
Hello,
JCI had DDE one time to do this. I don't know if it was only on the M stuff. The other way of doing this is with 3rd party software \ device. You could BACnet\IP from MSEA into OPC for the... -
06-12-2013, 06:14 PM
Thread: Metasys 6.0 launcher not launching?
by integrator- Replies
- 8
- Views
- 234
Try this - it worked for me If you have SCT...
Try this - it worked for me
If you have SCT installed, you will need to remove this.
Remove all your java from the add/remove programs, and delete any folder on the C drive.
Remove the... -
06-06-2013, 01:55 PM
- Replies
- 9
- Views
- 323
Hello, I've attached one that I found which (I...
Hello,
I've attached one that I found which (I think) you are wandering about. Let me know if this's correct390561
If so, this is a known issue because the Master is on a different NAE then the... -
06-05-2013, 10:04 PM
- Replies
- 9
- Views
- 323
What are the versions of the NAE \ NCE? You have...
What are the versions of the NAE \ NCE? You have added in a new NCE and the point within this NCE is not being updated by the Master which is on the original NAE. Correct
You have some else... -
06-05-2013, 09:47 PM
Thread: Johnson Controls NCE Problem
by integrator- Replies
- 6
- Views
- 192
Hello, Known issue with communication -...
Hello,
Known issue with communication - recall!!
You need to check the version of the S-Lincs board. If the S-Lincs date code is 10208 and earlier, it needs to be updated. If the S-Lincs has... -
06-01-2013, 08:41 AM
- Replies
- 9
- Views
- 323
Hello, Don't fully understand your question -...
Hello,
Don't fully understand your question - but is this what you want;
NAE-1 has a field controller with a outside air temp.
NAE-2 has a field controller BUT no outside air temp.
... -
05-29-2013, 11:56 AM
Thread: Help - Wireless Stat with LCD
by integrator- Replies
- 16
- Views
- 365
See comments
See comments
-
05-29-2013, 07:33 AM
Thread: Metasys
by integrator- Replies
- 7
- Views
- 390
What's the issue? How do you know their is a...
What's the issue? How do you know their is a problem?
If you or whoever installed the SQL as per Document their shouldn't be a problem. Is the SQL on a standard PC - what's the OS. -
05-28-2013, 11:52 PM
Thread: Help - Wireless Stat with LCD
by integrator- Replies
- 16
- Views
- 365
Hello, Viconics reqiure 24VAC, so this won't...
Hello,
Viconics reqiure 24VAC, so this won't work. Yes battery powered.
Thanks -
05-28-2013, 07:52 AM
Thread: Help - Wireless Stat with LCD
by integrator- Replies
- 16
- Views
- 365
Help - Wireless Stat with LCD
Hello,
I had posted a request on wireless stats and had great feedback. However my requirement is for a Temperature and Humidity stat that also has a LCD.
All the stats I can find either... -
05-27-2013, 08:25 PM
Thread: Audit Trail-JC
by integrator- Replies
- 1
- Views
- 133
Sorry - nope The audit trail is in the SQL. It...
Sorry - nope
The audit trail is in the SQL. It will only tell you that something has been removed. -
05-27-2013, 08:02 PM
Thread: Metasys
by integrator- Replies
- 7
- Views
- 390
What are the issues? How do you know their is a...
What are the issues? How do you know their is a problem?
Is the system a standard ADS\ADX or a split ADX?
What SQL are you using? -
05-25-2013, 05:27 PM
Thread: Metasys
by integrator- Replies
- 7
- Views
- 390
Do you have the metasys database manager...
Do you have the metasys database manager installed?
You can also look at
SQL (MSDE and SQL 2000) error log:
C:\Program Files\Microsoft SQL Server\MSSQL\LOG
SQL 2005 (Server and Express)... -
05-23-2013, 09:52 PM
Thread: Nae device id
by integrator- Replies
- 2
- Views
- 138
you need SCT
you need SCT
-
05-22-2013, 08:33 PM
Thread: NAE 5.2 error help!
by integrator- Replies
- 2
- Views
- 161
There is a known problem with trends not being...
There is a known problem with trends not being sent to the ADX at verson 5.2. What is the exact version you have 5.2.xxxx
Verson 5.2.7 and higher should fix this.
Let me know -
05-22-2013, 09:37 AM
Thread: Operational Error
by integrator- Replies
- 2
- Views
- 142
Can you take a screen shot of the error
Can you take a screen shot of the error
-
05-19-2013, 11:25 AM
Thread: Metasys NAE VERSE NCE
by integrator- Replies
- 9
- Views
- 260
I gave up the second table as it did the same...
I gave up the second table as it did the same thing.
Anyways the NCE - 32 devices, 2500 Total device objects, 1 N2/MSTP bus, and 1000 Device Objects
The NAE35 - 50 devcies, 250 total device... -
05-19-2013, 11:14 AM
Thread: Metasys NAE VERSE NCE
by integrator- Replies
- 9
- Views
- 260
Tha above table didn't tab correctly - so here...
Tha above table didn't tab correctly - so here it's again
NxE Model Devices Total Device Objects N2/MSTP Trunks Supported Total Trunk Points
25 32 ... -
05-19-2013, 11:09 AM
Thread: Metasys NAE VERSE NCE
by integrator- Replies
- 9
- Views
- 260
- On a NAE, you can choose what communication you...
- On a NAE, you can choose what communication you want - N2 or MSTP. For a NCE, you need to order the correct version.
- The NAE is about 2K more then a NCE.
- The NAE supports more N2 \ MSTP... -
05-16-2013, 07:26 AM
Thread: Help needed with JCI Metasys system
by integrator- Replies
- 7
- Views
- 442
What version of Metasys are you running?
What version of Metasys are you running?
-
05-14-2013, 06:30 PM
Thread: Can2Go stat
by integrator- Replies
- 0
- Views
- 136
Can2Go stat
Hello,
In one of my posts, this stat was reference for our requirements
http://www.can2go.com/documents/c2g-sensors_DS_STW-THW%20Sensors_91803502A.pdf
I'm looking for feedback if this is a...