  1. Replies
    7
    Views
    139

    Hello, Flash memory is the same as a standard...

    Hello,

    Flash memory is the same as a standard PC idea. For an NAE35 or NAE45 it has allocated 12Mb (uncompressed) of flash memory from the NAEs 128Mb of flash nonvolatile memory. For the NAE55 or...
  2. Replies
    7
    Views
    139

    Hello, The CCT performs a count of obects and...

    Hello,

    The CCT performs a count of obects and shows this as the % at the bottom. So for example, if you have an application with 2500 objects, this gets divided by the default number of 3000 and...
  3. Replies
    6
    Views
    173

    Hello, If the suggestion from Chinna doesn't...

    Hello,

    If the suggestion from Chinna doesn't work you can do the following

    From the "Expert Mode", you will have the Device Diagnostic Object. This will create a report that breaks out CPU use...
  4. Replies
    4
    Views
    206

    Good idea. You would need to setup a schedule and...

    Good idea. You would need to setup a schedule and do a pull every time you need data. The MEU comes with the ADS so no extra purchase is requried.
  5. Replies
    4
    Views
    206

    Hello, JCI had DDE one time to do this. I...

    Hello,

    JCI had DDE one time to do this. I don't know if it was only on the M stuff. The other way of doing this is with 3rd party software \ device. You could BACnet\IP from MSEA into OPC for the...
  6. Replies
    8
    Views
    234

    Try this - it worked for me If you have SCT...

    Try this - it worked for me

    If you have SCT installed, you will need to remove this.

    Remove all your java from the add/remove programs, and delete any folder on the C drive.

    Remove the...
  7. Hello, I've attached one that I found which (I...

    Hello,

    I've attached one that I found which (I think) you are wandering about. Let me know if this's correct390561

    If so, this is a known issue because the Master is on a different NAE then the...
  8. What are the versions of the NAE \ NCE? You have...

    What are the versions of the NAE \ NCE? You have added in a new NCE and the point within this NCE is not being updated by the Master which is on the original NAE. Correct

    You have some else...
  9. Replies
    6
    Views
    192

    Hello, Known issue with communication -...

    Hello,

    Known issue with communication - recall!!

    You need to check the version of the S-Lincs board. If the S-Lincs date code is 10208 and earlier, it needs to be updated. If the S-Lincs has...
  10. Hello, Don't fully understand your question -...

    Hello,

    Don't fully understand your question - but is this what you want;

    NAE-1 has a field controller with a outside air temp.

    NAE-2 has a field controller BUT no outside air temp.
    ...
  11. Replies
    16
    Views
    365

    See comments

    See comments
  12. Thread: Metasys

    by integrator
    Replies
    7
    Views
    390

    What's the issue? How do you know their is a...

    What's the issue? How do you know their is a problem?

    If you or whoever installed the SQL as per Document their shouldn't be a problem. Is the SQL on a standard PC - what's the OS.
  13. Replies
    16
    Views
    365

    Hello, Viconics reqiure 24VAC, so this won't...

    Hello,

    Viconics reqiure 24VAC, so this won't work. Yes battery powered.

    Thanks
  14. Replies
    16
    Views
    365

    Help - Wireless Stat with LCD

    Hello,

    I had posted a request on wireless stats and had great feedback. However my requirement is for a Temperature and Humidity stat that also has a LCD.

    All the stats I can find either...
  15. Replies
    1
    Views
    133

    Sorry - nope The audit trail is in the SQL. It...

    Sorry - nope

    The audit trail is in the SQL. It will only tell you that something has been removed.
  16. Thread: Metasys

    by integrator
    Replies
    7
    Views
    390

    What are the issues? How do you know their is a...

    What are the issues? How do you know their is a problem?

    Is the system a standard ADS\ADX or a split ADX?

    What SQL are you using?
  17. Thread: Metasys

    by integrator
    Replies
    7
    Views
    390

    Do you have the metasys database manager...

    Do you have the metasys database manager installed?

    You can also look at

    SQL (MSDE and SQL 2000) error log:
    C:\Program Files\Microsoft SQL Server\MSSQL\LOG

    SQL 2005 (Server and Express)...
  18. Replies
    2
    Views
    138

    you need SCT

    you need SCT
  19. Replies
    2
    Views
    161

    There is a known problem with trends not being...

    There is a known problem with trends not being sent to the ADX at verson 5.2. What is the exact version you have 5.2.xxxx

    Verson 5.2.7 and higher should fix this.

    Let me know
  20. Replies
    2
    Views
    142

    Can you take a screen shot of the error

    Can you take a screen shot of the error
  21. Replies
    9
    Views
    260

    I gave up the second table as it did the same...

    I gave up the second table as it did the same thing.

    Anyways the NCE - 32 devices, 2500 Total device objects, 1 N2/MSTP bus, and 1000 Device Objects
    The NAE35 - 50 devcies, 250 total device...
  22. Replies
    9
    Views
    260

    Tha above table didn't tab correctly - so here...

    Tha above table didn't tab correctly - so here it's again


    NxE Model Devices Total Device Objects N2/MSTP Trunks Supported Total Trunk Points
    25 32 ...
  23. Replies
    9
    Views
    260

    - On a NAE, you can choose what communication you...

    - On a NAE, you can choose what communication you want - N2 or MSTP. For a NCE, you need to order the correct version.

    - The NAE is about 2K more then a NCE.

    - The NAE supports more N2 \ MSTP...
  24. Replies
    7
    Views
    442

    What version of Metasys are you running?

    What version of Metasys are you running?
  25. Thread: Can2Go stat

    by integrator
    Replies
    0
    Views
    136

    Can2Go stat

    Hello,

    In one of my posts, this stat was reference for our requirements
    http://www.can2go.com/documents/c2g-sensors_DS_STW-THW%20Sensors_91803502A.pdf

    I'm looking for feedback if this is a...