    There is a link near the end of the following...

    There is a link near the end of the following thread:

    http://hvac-talk.com/vbb/showthread.php?465362-Daikin-D-BACS-Interface&highlight=daikin

    Pres
  2. http://www.daikinac.com/content/assets/Controls/20...

    http://www.daikinac.com/content/assets/Controls/2012-12-04-BRC1E72-Field-Settings-Table.pdf

    Yes. Active call for cooling at SP +1 deg F assuming it is in the correct mode. Are you using...
  3. Field setting 22-2-02. 22-2-01 is +- 2 deg F....

    Field setting 22-2-02.

    22-2-01 is +- 2 deg F.
    22-2-02 is +- 1 deg F.

    Pres
  4. Replies
    13
    Views
    1,257

    31-33 points are available but none are required....

    31-33 points are available but none are required. Use whatever you want. The gateway is BTL listed so I'm pretty sure they know what ASHRAE is. Meet the current standard? That is a different story. ...
  5. If every IDU has it's own branch selector port,...

    If every IDU has it's own branch selector port, then they will all be masters. If however you have multiple IDUs on one branch selector port, they will act just like a heat pump system and one unit...
  6. Try enabling object CL_Rejection_XXX. That should...

    Try enabling object CL_Rejection_XXX. That should disable operation of the touch panel and give you more insight on whether it is interfering with operation.

    Is this a heat pump system or heat...
  7. Replies
    177
    Views
    48,042

    Set filter to BACnet. You should see a broadcast...

    Set filter to BACnet. You should see a broadcast at 64 seconds after cycling power.

    Pres
  8. Replies
    177
    Views
    48,042

    There is a link a few posts back. Pres

    There is a link a few posts back.

    Pres
  9. Replies
    14
    Views
    699

    Software tool. https://goo.gl/3uVF05 Pres

    Software tool.

    https://goo.gl/3uVF05

    Pres
  10. Replies
    14
    Views
    699

    10 outdoor units and 64 indoor units per comm...

    10 outdoor units and 64 indoor units per comm port. The gateway comes with two ports out of the box. Additional two ports can be added with expansion board.

    Pres
  11. Replies
    13
    Views
    1,257

    You can use Inneasoft BACnet Explorer free...

    You can use Inneasoft BACnet Explorer free version if you just want to verify communication (does not allow write):

    http://www.inneasoft.com/index.php/en/products/bacnet-protocol/bacnet-explorer
    ...
  12. Replies
    9
    Views
    869

    www.controlmanagement.com

    www.controlmanagement.com
  13. Replies
    4
    Views
    480

    Oops. Ok, just added it.

    Oops. Ok, just added it.
  14. Replies
    4
    Views
    480

    Will do. Thanks!! Pres

    Will do. Thanks!!

    Pres
  15. Replies
    4
    Views
    480

    VRF Niagara Stations

    Since integrating to VRF systems though gateways is typically a pain, I'm working on putting together some default stations as a starting point to help integrators. Default, all inclusive and you can...
  16. Replies
    177
    Views
    48,042

    Here you go. https://goo.gl/3uVF05 Pres

    Here you go.

    https://goo.gl/3uVF05

    Pres
  17. Replies
    3
    Views
    699

    3.8

    3.8
  18. Replies
    3
    Views
    699

    Vykon JEC-334 commissioning error

    Hello,

    I'm trying to commission this with 3.8.38 and am getting an nre-core dependency error saying I need to update. Must nre-core version match baja version?

    Pres

    579371579381
  19. Replies
    177
    Views
    48,042

    No. Just hyperterminal (old Windows XP etc.) or...

    No. Just hyperterminal (old Windows XP etc.) or some other terminal emulator like PuTTY for current versions of Windows and the cable. There really isn't any configuration of the actual gateway. No...
  20. Replies
    177
    Views
    48,042

    The Lon gateway uses a null modem cable with...

    The Lon gateway uses a null modem cable with custom pinout and hyperterminal. The cable is sold by the service department.

    Pres
  21. Replies
    177
    Views
    48,042

    Diego, See download link in previous post. ...

    Diego,

    See download link in previous post.

    Pres
  22. Replies
    7
    Views
    1,068

    Single setpoint through the gateway is a controls...

    Single setpoint through the gateway is a controls architecture limitation. The iTouch and iTouch Manager have the same limitation. To control independent setpoints they send out a new setpoint with...
  23. Replies
    0
    Views
    394

    Vykon Workplace AX 3.6

    Does anyone have the install package they can give me for 3.6? I have a temp license for 3.8 and I would like to un-FUBAR a demo JACE-6 I have.

    Pres
  24. Replies
    35
    Views
    7,811

    Does anyone know how to bind the result of a case...

    Does anyone know how to bind the result of a case block to a BACnet IP multistate output?

    Pres
  25. Replies
    177
    Views
    48,042

    Ethernet cable and computer running that...

    Ethernet cable and computer running that software. LG gateway is nice that you can commission with the LCD/buttons on the unit and built in web server.

    Pres
  26. Replies
    177
    Views
    48,042

    Latest version 6.34. Enjoy!! ...

    Latest version 6.34. Enjoy!!

    http://goo.gl/3uVF05

    Pres
  27. Try port 80. Pres

    Try port 80.

    Pres
  28. Replies
    9
    Views
    1,262

    Same way. Monitor space temp and override units...

    Same way. Monitor space temp and override units on when setback setpoints are reached. Back off after a set differential.
  29. Replies
    9
    Views
    1,262

    If it uses Java then it is the old gateway. Here...

    If it uses Java then it is the old gateway. Here is the IOM:

    https://www.dropbox.com/s/fr2gccnt2jqvd4f/MFL37115823_LG%20BACnet%20Old.pdf

    Are you sure the IDUs have been discovered by the...
  30. Replies
    177
    Views
    48,042

    Ok let's see if this works. This version is three...

    Ok let's see if this works. This version is three years old so not sure if it is even current anymore. If anyone has a more current version, send it to my email and I'll setup a new link.
    ...
  31. Replies
    177
    Views
    48,042

    August posters, check your mail. Anyone else, let...

    August posters, check your mail. Anyone else, let me know.

    Pres
  32. Replies
    177
    Views
    48,042

    Version I have is 6.201. Not sure if that is even...

    Version I have is 6.201. Not sure if that is even current anymore. Haven't used it since 2011. Who wants it?!

    Pres
  33. Thread: LG V-net

    by El Presidente
    Replies
    20
    Views
    3,636

    You're welcome! Let me know if you need anything...

    You're welcome! Let me know if you need anything else.

    Pres
  34. Thread: LG V-net

    by El Presidente
    Replies
    20
    Views
    3,636

    They work. I would take the BACnet over Lon. More...

    They work. I would take the BACnet over Lon. More functionality, more capacity, and less issues. They are both monitoring and control. You can see the points lists here:
    ...
  35. Thread: LG V-net

    by El Presidente
    Replies
    20
    Views
    3,636

    What do you want to know?

    What do you want to know?
  36. Replies
    6
    Views
    1,172

    You should see just a bunch of points. The number...

    You should see just a bunch of points. The number after the object name corresponds with the address in the stat. For example StartStopCommand_000 corresponds with group address 1-00. 001 is 1-01...
  37. Replies
    11
    Views
    4,574

    What gateway firmware version? If it is 1.x you...

    What gateway firmware version? If it is 1.x you just have to have the equipment connected to see the points. If it is 2.x you must go in through the webserver and perform a discovery within the...
  38. Thread: Can2Go

    by El Presidente
    Replies
    37
    Views
    9,385

    Graphical programming is available. Pres

    Graphical programming is available.

    Pres
  39. For Daikin you have to limit the writes for...

    For Daikin you have to limit the writes for changes of value. If you write On when the unit is already on every two seconds it is fine as the gateway will not actively write to the indoor unit EEPROM...
  40. BACnet - Excellent, this got all my points...

    BACnet - Excellent, this got all my points working except for MSI, MSO, MSV. Thanks!

    Xarralu - SCL Elements confirmed Multi-states will not be available until November Firmware update.

    Pres
  41. CAN2GO UN2 - BACnet readProperty Request

    Hi all,

    I'm trying to use this controller to run simulations and trend points on my VRF system through a BACnet gateway.

    Script syntax for the request is (device instance, object type and...
  42. Tridium --> LG Lon Gateway SNVT Type Size Mismatch

    I'm trying to help out a guy integrating Tridium and LG and he says for SNVT nvoUnitStatus, his system reports “Type Size Mismatch (13bytes). LonMark says this data type (hvac_status) should be 12...
  43. Replies
    11
    Views
    4,574

    Ok, thanks anyway. Pres

    Ok, thanks anyway.

    Pres
  44. Replies
    11
    Views
    4,574

    Type Size Mismatch

    hvaccontrolsguy,

    I'm trying to help out a guy integrating Tridium and LG and he says for SNVT nvoUnitStatus, his system reports “Type Size Mismatch (13bytes). LonMark says this data type...
  45. Replies
    11
    Views
    4,574

    What was the problem and how did you solve it? ...

    What was the problem and how did you solve it?

    Pres
  46. Replies
    13
    Views
    3,874

    Have each of the indoor units been assigned a...

    Have each of the indoor units been assigned a group address? If not, do that and then cycle power on the gateway.

    Pres
  47. Replies
    177
    Views
    48,042

    C, check your mail. threefiddy, my e-mail...

    C, check your mail.

    threefiddy, my e-mail bounced back. Not sure what the problem is.

    Pres
  48. Replies
    177
    Views
    48,042

    C, add an email to your profile. Pres

    C, add an email to your profile.

    Pres
  49. Replies
    177
    Views
    48,042

    threefiddy, check your mail. Pres

    threefiddy, check your mail.

    Pres
  50. Replies
    177
    Views
    48,042

    Ok, what's the IP address of the Jace? It will...

    Ok, what's the IP address of the Jace? It will have to be 192.168.0.X if the gateway is left at default IP of 192.168.0.1 without enabling the gateway as a foreign device.

    If it is on a different...