  1. Replies
    21
    Views
    1,471

    Crankcase heater is useful only in OFF cylcles....

    Crankcase heater is useful only in OFF cylcles.
    Actually I am talking about running the units in ON cycles in low ambient conditions.
  2. Replies
    8
    Views
    723

    Bigger size of accumulator means your system...

    Bigger size of accumulator means your system internal volume has increased. So you need to put additional refrigerant to maintain required level of superheat & subcooling.
    Correct me if i am wrong....
  3. Replies
    21
    Views
    1,471

    Actually in discharge cooled compressor(e.g. all...

    Actually in discharge cooled compressor(e.g. all rotary), in low ambient conditions there is chance of entering liquid refrigerant in the system because of lesser value of superheat.

    Once liquid...
  4. Replies
    21
    Views
    1,471

    In air conditioners, going with lesser superheat...

    In air conditioners, going with lesser superheat may be add some BTU/hr in the system but it may cause problem during low ambient conditions as the liquid refrigerant might enter into the compressor....
  5. Replies
    8
    Views
    723

    Actually it entirely depends on system design....

    Actually it entirely depends on system design. Yup you can select it .Bigger the accumulator, more refrigerant charge is required in the system.
    Just check the total charge limit should not exceed...
  6. Move the condenser units to the top. No need to...

    Move the condenser units to the top.
    No need to change the sizing the suction line,as during system design all these points like oil return,gas velocity etc.
  7. Replies
    4
    Views
    823

    300 micron is recommended for R410A applications....

    300 micron is recommended for R410A applications. As POE oil is hygroscopic in nature, so it catches moisture very easily. For R22 applications, you can go 400-500 microns
  8. Ans 1: If condenser is not precharged,then yes...

    Ans 1: If condenser is not precharged,then yes you can open all the valves. as vaccumm velocity is not that high,so it will not pull the compressor oil.

    Ans 2: Pressure will go even if TXV is ...
  9. Replies
    124
    Views
    15,430

    i am using 8 CFM vacumm pump & trying of...

    i am using 8 CFM vacumm pump & trying of vacummizing my 8.5 Tr unit having internal volume of around 1.8 cu.ft

    Ideally what should be the vacummizing time?? it is taking so long (around 7-8 hrs)...
  10. What is the static & operating superheat setting...

    What is the static & operating superheat setting for TXV??
    Again check the proper mounting & location of sensing bulb.
  11. Replies
    29
    Views
    3,041

    This is the Ask Our Pro's forum. In order to post...

    This is the Ask Our Pro's forum. In order to post a response here, you must have verified qualifications and have been approved by the AOP Committee. You may ask a question by starting a new thread....
  12. mixing two will not work,as both the refrigerants...

    mixing two will not work,as both the refrigerants are having different boiling point,critical point etc. Compressor oil is also different.As the POE oil used in R410A systems is very sensitive to...
  13. Replies
    26
    Views
    3,385

    As per me, it depends on the material you want to...

    As per me, it depends on the material you want to braze. If you want to braze two dissimilar metals(e.g. copper to brass etc), then percentage of silver content should be high.
  14. Replies
    13
    Views
    2,331

    Thank you for your favorable reply. I am also...

    Thank you for your favorable reply.
    I am also working in Air conditioning manufacturing industry,,but new to design deptt.
    pls let me know from where i have to get answers of queries like this??...
  15. Replies
    13
    Views
    2,331

    Sir the same thing i want to ask that from where...

    Sir the same thing i want to ask that from where i can get these refernce manuals & charts?
  16. Replies
    13
    Views
    2,331

    @above I am sorry sir, not getting you....

    @above

    I am sorry sir, not getting you.
    Please elaborate & help me out
  17. Replies
    13
    Views
    2,331

    Coil Size calculation

    Can anyone suggest me how to calculate size of condenser size of ductable
    unit of 8.5 tr capacity at 54.4 deg condensing temp & 7.2 deg evap temp

    I am designing a machine in which i am using...
  18. Replies
    0
    Views
    502

    Noise in orifice flow meters

    My boss has asked me to derive a method or equation for determining noise (in decibels) in orifice flow meters. I've been looking at basic principles of aerodynamic and hydrodynamic noise...
  19. Replies
    4
    Views
    565

    @ lynn comstock Thank you. I need help from...

    @ lynn comstock

    Thank you. I need help from experinced people like you.
  20. Replies
    4
    Views
    565

    @ classical Thank you so much sir for your...

    @ classical

    Thank you so much sir for your guidance.
  21. Replies
    4
    Views
    565

    Need Help

    Hi to all
    i have joined HVAC industry some time before.
    Working in R&D deptt with hitachi .
    Pls suggest me some good forums/software etc.
    e.g. coil selection/motor selction/cycle...