Search:
Type: Posts; User: referkid
Search: Search took 0.01 seconds.
-
01-06-2012, 11:11 PM
Thread: rack breaking compressors
by referkid- Replies
- 17
- Views
- 1,128
Helical and has ben working properly oil...
Helical and has ben working properly oil teservoir never been lower than 1 st sight glass. Oil floats on all compressora at a half sight glass
-
01-06-2012, 08:48 PM
Thread: rack breaking compressors
by referkid- Replies
- 17
- Views
- 1,128
ee
Suction pressures bumped up 56# and 15# going though every coil superheat and all r sheets being revised traps on all coils .
-
01-03-2012, 02:28 PM
Thread: rack breaking compressors
by referkid- Replies
- 17
- Views
- 1,128
It wouldseem floodback none visible nor are the...
It wouldseem floodback none visible nor are the temp readings from suction trunks showing floodback temps at any point. Piping is all correct per r sheets stumped
-
01-03-2012, 12:19 PM
Thread: rack breaking compressors
by referkid- Replies
- 17
- Views
- 1,128
Breakin rods, locking up all compressors have...
Breakin rods, locking up all compressors have been replaced atleast 10 according to log books rack is four years old evaps are still original.graphs show no floodback records show people have...
-
01-03-2012, 12:13 AM
Thread: rack breaking compressors
by referkid- Replies
- 17
- Views
- 1,128
rack breaking compressors
We picked up new account today its a food processing plant 8 copeland compressors mt and lt rack common discharge seperate suctions accumalator on lt compressors. Mt suction running 42# lt at 8# ...
-
12-22-2011, 09:43 PM
Thread: New Guests going Pro?
by referkid- Replies
- 1,144
- Views
- 111,318
Sticky: Yea the asap aspect of markets is very true....
Yea the asap aspect of markets is very true. Thats another reason i like markets they understsnd the urgency of the repair so approvals are quick.
-
12-22-2011, 02:26 AM
Thread: New Guests going Pro?
by referkid- Replies
- 1,144
- Views
- 111,318
Sticky: Today i got to change an oil seperator. It had a...
Today i got to change an oil seperator. It had a turboshed and we determined it wasnt feeding all compressors off on oil failure no oil or pressure coming from the oil supply line. Couldnt be cleaned...
-
12-22-2011, 02:18 AM
Thread: New Guests going Pro?
by referkid- Replies
- 1,144
- Views
- 111,318
Sticky: I began taking hvac classes at a community...
I began taking hvac classes at a community college and found refrigeration a bit more interesting . I met a guy in class who worked in the field and i was lucky enough to get a job there. It was a...
-
12-20-2011, 12:02 AM
Thread: Acid Neutralizer
by referkid- Replies
- 25
- Views
- 2,176
Ive used acid away on every burn out job...
Ive used acid away on every burn out job haventhad a call back since on any.
-
12-19-2011, 11:54 PM
Thread: copeland semiherm troubleshooting
by referkid- Replies
- 13
- Views
- 831
I would recommend valve plate check and if this...
I would recommend valve plate check and if this is a discus its hard to see a bad valve plate load compressor up fully and bench check run into vacuum i like to see atleast10 in vac and hold
-
12-19-2011, 10:46 PM
Thread: Unknown device on rack
by referkid- Replies
- 13
- Views
- 954
Ive seen it on a costco rack which was scroll to...
Ive seen it on a costco rack which was scroll to carlyle and from watching it run it fills with liwuid andeven oil when it fills second sight glass it opens line to flow to discharge header. Im...