    timj772 you are the man! Adding the folder with...

    timj772 you are the man! Adding the folder with the version number worked
  2. Replies
    8
    Views
    322

    Yes the jar file is in the modules folder of FX...

    Yes the jar file is in the modules folder of FX Workbench, its not on a jace only on my laptop. I also used the import from files function but that didn't work either
  3. Replies
    8
    Views
    322

    Yes it has been copied into the modules folder...

    Yes it has been copied into the modules folder and I restarted workbench and my laptop. I'm using workbench 6.0 most of the modules are at Tridium 3.8.38. The module that I'm trying to install is...
  4. Replies
    8
    Views
    322

    Module not available locally

    I'm trying to add a new module to my FX Workbench module directory locally on my laptop. When I open up the software manager in workbench locally on my laptop, I can see all of the modules including...
  5. Replies
    5
    Views
    175

    They are all McQuay heat pumps. I have workbench...

    They are all McQuay heat pumps. I have workbench with all of the XIF files. I'm just not really sure how to set up my lon network offline (like domain length and all that stuff). I know how to add...
  6. Replies
    5
    Views
    175

    Anyone?

    Anyone?
  7. Replies
    5
    Views
    175

    NAE Lon to FX

    I'm going to be integrating to an existing Lon trunk that currently ties back into an NAE. This is my first Lon integration and was wondering what the best way to do this is. I have FX workbench...
  8. Replies
    8
    Views
    300

    Oh Ok I know where to find that in HVAC Pro I...

    Oh Ok I know where to find that in HVAC Pro I thought it was something you do in PMI if it was at an older version like that. The version of the AHU controller is at 3.03. If I try to upgrade the...
  9. Replies
    8
    Views
    300

    I did a search for *.AHO on the workstation. The...

    I did a search for *.AHO on the workstation. The files are on there but I don't know what to do with them. Where is the upgrade option? and if I do that will it erase the logic in the controller?
  10. Replies
    8
    Views
    300

    Uploading AHU Controller

    I'm trying to upload a JCI AHU controller via pass through with an NCM. I can open up HVAC Pro and scan the N2 trunk fine with no problem. There is only one AHU controller on the network and every...
  11. Replies
    5
    Views
    192

    Sweet that worked thank you

    Sweet that worked thank you
  12. Replies
    5
    Views
    192

    Thanks mechdorn

    Thanks mechdorn
  13. Replies
    5
    Views
    192

    Central Daylight Time in Alarm Console

    On all of my stations that I setup the date and time-stamp from the alarms that come into the alarm console are all in central daylight time. I set the right date and time in the platform...
  14. Replies
    6
    Views
    240

    There are a lot of pitfalls with the NAE. What...

    There are a lot of pitfalls with the NAE. What is the part number of the NAE?
  15. Replies
    42
    Views
    1,776

    http://lmgtfy.com/?q=differences+between+bacnet+an...

    http://lmgtfy.com/?q=differences+between+bacnet+and+lonworks
  16. Replies
    9
    Views
    550

    Yes I did get it to work. I had to enter the...

    Yes I did get it to work. I had to enter the public IP address in the broadcast distribution table in the BACnet router. I had to enter it then refresh and ping that IP address a few times to wake...
  17. Replies
    9
    Views
    550

    Yes I can ping the router and get 100% response...

    Yes I can ping the router and get 100% response back as long as im on the same subnet. The Boilerroom and CommunityRoomAHU are on an MSTP trunk. I can ping both controllers with no problem. I'm...
  18. Replies
    9
    Views
    550

    Yes I have verified the router configuration and...

    Yes I have verified the router configuration and the Ethernet connection. They are all ok nothing has changed
  19. Replies
    14
    Views
    939

    I graduated in 2008 from PCT (Pennsylvania...

    I graduated in 2008 from PCT (Pennsylvania College of Technology) with a building automation degree. I was very impressed with the lab and all of the controls they have, however, we were on our own...
  20. Replies
    9
    Views
    550

    I also see this MESSAGE [08:09:37 04-Mar-14...

    I also see this

    MESSAGE [08:09:37 04-Mar-14 EST][bacnet.client] TransactionException pinging BacnetDevice {BoilerRoom}: Transaction:lockup: invoke ID 234
    ERROR [08:09:37 04-Mar-14...
  21. Replies
    9
    Views
    550

    Contemporary Controls BASRT-B

    Im working with a contemporary controls BASRT-B as a BBMD bacnet router back and trying to get it back online. Everything was working fine for months. The Ethernet side of the router was plugged...
  22. Replies
    8
    Views
    513

    Find the controller on the jace and discover the...

    Find the controller on the jace and discover the points. The point may not be mapped into the system, it should be called "Password Value"
  23. Replies
    0
    Views
    201

    Heat Recovery PCG Controllers

    Im having trouble determining how the bypass dampers in a heat recovery AHU work in PCT. Ive worked on air handlers with a heat recovery wheel several times before, but this will be my first using...
  24. Replies
    8
    Views
    927

    I was back on site this morning. I talked to...

    I was back on site this morning. I talked to Aerco tech support and found out I don't need the 232 to 485 converter. There is just one Aerco benchmark boiler with a C-More controller going directly...
  25. Replies
    8
    Views
    927

    I meant that I couldn't discover the protonode. ...

    I meant that I couldn't discover the protonode. There was no rs232 to rs485 converter supplied. Looks like I will have to call the factory on monday. Every time I run into aerco products I have...