Search:

Type: Posts; User: mmc

Search: Search took 0.00 seconds.

  1. Replies
    91
    Views
    32,647

    The answer is NO. The Ground Loop Converter...

    The answer is NO. The Ground Loop Converter replaces the serial port adaptor that you use for Comfortview. And you cannot use a phone cord for Flotronic Manager. This is really OOOOOOOOOOOOOOld...
  2. Replies
    2
    Views
    892

    I agree with BobbyBJr in that you have to include...

    I agree with BobbyBJr in that you have to include everything you propose to include for the price quoted. But just as important is that you also include whatever you are NOT responsible for... High...
  3. Replies
    91
    Views
    32,647

    OK hvac-alan, First contact Telebyte @...

    OK hvac-alan,

    First contact Telebyte @ 800-835-3298. Order a M/N 65A or you can go to their website ( http://www.telebyteusa.com ) and order it. It is an external powered Ground Loop Converter....
  4. Replies
    91
    Views
    32,647

    I believe the name of the software you're talking...

    I believe the name of the software you're talking about is Flotronic Manager. It's a DOS program that I run in WIN 98. The beauty is that you're able to see what the microprocessor sees. You may...
  5. Replies
    31
    Views
    2,188

    Hey fellas, Let's leave all the racial and...

    Hey fellas,

    Let's leave all the racial and political rhetoric to the politicians. They're experts at it. That's all they do. Hot air.

    Right now it's about saving people. These servivors have...
  6. Replies
    22
    Views
    2,409

    I'm running XP Pro and I'm not having any...

    I'm running XP Pro and I'm not having any problems. You have to have Config Tools. Inside Config Tools is a program called Auxillary Access. Connect to the devices with that. Then use HVAC Pro to...
  7. Thread: TCS Basys

    by mmc
    Replies
    5
    Views
    1,260

    Thanks fellas for the comments. But now I have to...

    Thanks fellas for the comments. But now I have to ask about the Rev Pro software vs. the QD2040 embedded webserver. Isn't the Rev Pro software DOS based? Is it CLUI or is it graphics? I appreciate...
  8. Thread: TCS Basys

    by mmc
    Replies
    5
    Views
    1,260

    Does anyone have any experience with TCS Basys. I...

    Does anyone have any experience with TCS Basys. I do alot of work out in the field with JCI and CCN but I haven't come across TCS Basys.

    The reason I ask is that we have 15 or 20 TCS stats in our...
  9. Replies
    6
    Views
    2,082

    Carrier used to make a board called an Iso-Sat or...

    Carrier used to make a board called an Iso-Sat or maybe it was an Iso 02. I can't remember now. I used to use an Iso-Sat and a modem to interface with the old Gen II VVT from a remote location. If I...
  10. Thread: HVAC PRO problems

    by mmc
    Replies
    17
    Views
    5,713

    None of my accounts have any Trane equipment. I...

    None of my accounts have any Trane equipment. I haven't had the oppertunity to try it.
  11. Thread: HVAC PRO problems

    by mmc
    Replies
    17
    Views
    5,713

    I use the B&B M/N 485CARLP9A converter to talk to...

    I use the B&B M/N 485CARLP9A converter to talk to Carrier 30GTN Flotronic Chillers. I use Comfort View 3.0. RJ11 to RJ11 phone cable.

    I use the B&B M/N 485SD9TB to talk to JCI on the N2 bus...
  12. Thread: HVAC PRO problems

    by mmc
    Replies
    17
    Views
    5,713

    I've always used a B&B M/N 485SD9TB RS232 X 485...

    I've always used a B&B M/N 485SD9TB RS232 X 485 converter for the serial port.
  13. Replies
    11
    Views
    1,147

    Take it down to 500 microns then watch it. If it...

    Take it down to 500 microns then watch it. If it rises a little but then stops and stays below 1000 for about 20 minutes, you're OK. If it rises and doesn't stop and climbs up above 1000 microns, you...
  14. Thread: HVAC PRO problems

    by mmc
    Replies
    17
    Views
    5,713

    All right. Hear that incontrol? Sounds like you...

    All right. Hear that incontrol? Sounds like you need a patch. Get 8.04 and see what happens. Thnaks #1 servicetech. Good info to have.
  15. Thread: HVAC PRO problems

    by mmc
    Replies
    17
    Views
    5,713

    This is to #1 servicetech. You did this with only...

    This is to #1 servicetech. You did this with only 2 wires? How?
  16. Thread: funny pressures

    by mmc
    Replies
    8
    Views
    1,101

    I have to agree with everyone on this. If it's...

    I have to agree with everyone on this. If it's not some sort of pressure control cycling, then it's probably the TXV hunting. Check and make sure the bulb is secure on the suction line. If that's not...
  17. Thread: HVAC PRO problems

    by mmc
    Replies
    17
    Views
    5,713

    I've never seen two wires work. It takes all...

    I've never seen two wires work. It takes all three. IF you have the little three barrell connector plug to fit into the N2 plug on the UNT, you see all three connections.(Ref, N2- & N2+) You need all...
  18. Thread: HVAC PRO problems

    by mmc
    Replies
    17
    Views
    5,713

    You don't necessarily need Cable Pro. An RS232 to...

    You don't necessarily need Cable Pro. An RS232 to 485 converter is all you really need. That's what I've been using for years.

    First unplug the N2 plug from the UNT and plug in your own plug from...
Results 1 to 18 of 30