    200lbs plus tare weight of the drum. No it's not...

    200lbs plus tare weight of the drum. No it's not a 55 gallon drum.
  2. Thread: wye-delta

    by ryjowy
    Replies
    14
    Views
    2,157

    Had a friend run into this same issue. Compressor...

    Had a friend run into this same issue. Compressor was wired wrong internally. Re manufacture company wouldn't cop to it.
  3. Replies
    70
    Views
    12,806

    Ah, I see a problem. In your last 2 picks there...

    Ah, I see a problem. In your last 2 picks there is white stuff all over the ground and on your roof. Where I live, that's a problem.
  4. Replies
    3
    Views
    722

    Funny you should mention that, I found one in...

    Funny you should mention that, I found one in L.A., but his manual was in Chinese!!!!
  5. Replies
    3
    Views
    722

    IOM For Broad Absorbtion Chiller

    I'm looking for any info on a Broad Absorbtion chiller M#BD40N93.3/78.9-50 S# 01113198.
    I have a crew in from China replacing one of the pumps. I would like to read up and familiarize myself with...
  6. Replies
    16
    Views
    1,532

    JCI is much more forthcoming with tech data than...

    JCI is much more forthcoming with tech data than York was. JCI purchased Cal Air then York about 6 mo later in Ca. Once we were all part of JCI, getting the info was 100X easier. Just a hard co. to...
  7. I installed vfd's on 5h126's. Worked great. 30...

    I installed vfd's on 5h126's. Worked great. 30 sec ramp on start. 4 years and no problems yet. Open inspected last year and bearing surfaces looked fine. No lack of lube evident. Would never have...
  8. Replies
    11
    Views
    1,445

    Gents are right. Need to know all the delta p's...

    Gents are right. Need to know all the delta p's and t's. RLA, saturation temps etc. Sounds like there's air in it but don't know for sure without all the info.
  9. Thread: CVHF surging

    by ryjowy
    Replies
    39
    Views
    4,461

    Both approaches should run pretty close to each...

    Both approaches should run pretty close to each other. Check your design delta T's. Make sure you have temp drop as well as pressure drop. Tubes could be fouled. Good rule of thumb is 10* @ full ...
  10. Replies
    28
    Views
    1,972

    We have area teams. They consist of a supervisor,...

    We have area teams. They consist of a supervisor, journeymen and apprentices. They cover most of the commercial needs. I head up the Large Tonnage and Predictive group. I am there to support the...
  11. Replies
    19
    Views
    6,991

    If you ask York, they will say you need to...

    If you ask York, they will say you need to recover the charge, ole timers on the other hand will say bring it up to zero and hold it. Do they even sell the 6 spring anymore? I thought they did away...
  12. Replies
    45
    Views
    2,765

    Carribean Blue.....if it looks like a York,...

    Carribean Blue.....if it looks like a York, smells like a York, and if you're lucky, it just might run like a York...... YT that is.
  13. Replies
    28
    Views
    2,483

    I have replaced rear thrust using both methods...

    I have replaced rear thrust using both methods several times and like absrbrtk, I haven't had any issues in either circumstance. However, I have seen I don't know how many failures due to these...
  14. Replies
    14
    Views
    1,477

    How are you gents liking JCI? It's not working...

    How are you gents liking JCI? It's not working out so well in the bay area. Lot of us are moving on.
  15. Replies
    45
    Views
    2,765

    The units are rebuilt on site. Need to have a...

    The units are rebuilt on site. Need to have a qualified service mechanic look at your unit. Most factory Trane , York or Carrier mechanics are trained on competitors models or have moved from shop to...
  16. Replies
    339
    Views
    45,159

    San Fran Ca. 11 years in the trade. Large...

    San Fran Ca.
    11 years in the trade. Large Tonnage and predictive services.
    UA Local 467
    US Navy Engineman 4 years
  17. Replies
    12
    Views
    2,508

    Most of the new installs out here are going to...

    Most of the new installs out here are going to the DP's and away from the flows. Trane is mounting them on the side of the Control panel and using pnuematic tubing??? I replace with 1/4" copper on...
  18. Replies
    6
    Views
    2,465

    What compressor is on the unit?

    What compressor is on the unit?
  19. Replies
    6
    Views
    2,465

    If klove cant get it to you I can.

    If klove cant get it to you I can.
  20. Replies
    108
    Views
    6,594

    Here is the bay area, we have all sorts who are...

    Here is the bay area, we have all sorts who are just as capable as us ole white guys. Remember it's" Not the color of their skin, it's the quality of their character." And believe me, we have some...
  21. Replies
    9
    Views
    1,108

    Valves are replaced, I just couldn't believe this...

    Valves are replaced, I just couldn't believe this was an isolated incident.
  22. Replies
    11
    Views
    1,837

    Our company no longer reps them. Had Absurd...

    Our company no longer reps them. Had Absurd failure rate. The actual co. reps have been to our accounts where they are installed in place of Vilter 300 ES. Nothing but issues and revisions. Not yet...
  23. Replies
    37
    Views
    4,121

    Redi purge makes a great retro purge unit that is...

    Redi purge makes a great retro purge unit that is york OEM now and works similar to the trane purge. No more pumping oil and venting off pressure. PRG 11/123 c3 is the M#. It's the same as the...
  24. Thread: 19dk

    by ryjowy
    Replies
    21
    Views
    1,252

    Reverse wrap the 1st layer with scotch 33...

    Reverse wrap the 1st layer with scotch 33 electrical tape. Non-sticky against the terminal, sticky side out. Then 1 layer of friction tape, then linerless splicing tape followed by one last layer of...
  25. Replies
    9
    Views
    1,108

    RTAC Leaks on Suct Isolation Valve

    I'm told this is an isolated incident. Has anyone ran into RTAC's leaking out the valve stems of the isolation valves on top of the evap barrel? It's the same valve McQuay uses on their PH series...