04-09-2013, 08:32 PM
Thread: Trane economizer troubleshooting
by gwoner- Replies
- 14
- Views
- 800
Pull the access panel off the economiser hood and...
Pull the access panel off the economiser hood and verify actuator operation. Also red service lite should be on on uem board. When putting in test mode and nothings working, disconnect the j6 plug on...
-
04-05-2013, 09:46 PM
Thread: Trane economizer troubleshooting
by gwoner- Replies
- 14
- Views
- 800
Supply air sensor is the problem.Get new SAS or...
Supply air sensor is the problem.Get new SAS or pull OAS and use it.
-
01-27-2013, 10:33 AM
- Replies
- 4
- Views
- 451
Just shut down ckt 1, to dang cold out with...
Just shut down ckt 1, to dang cold out with windchill at -17* f. Will return at end of week to investigate. Customer happy and occupants in office below condenser happy with noise gone .
-
01-26-2013, 07:42 PM
- Replies
- 4
- Views
- 451
OROAB 5-210 R407C on Liebert Remote Condenser.
OAT 8*. head pressure control making a loud vibrating noise. Is this a sign of internal damage to the valve or diaphram or is it common at this low of ambients
-
12-16-2012, 09:56 PM
Thread: Trane YCD300 gas pack heat exchanger
by gwoner- Replies
- 2
- Views
- 480
Use existing back support under HE, use new bolt...
Use existing back support under HE, use new bolt that comes with new unit. Most come with inducer and gas valve if ordered. 1 guy for 4 hours, 1 guy for 8 hours.No crane needed to remove and replace,...
-
12-16-2012, 09:51 PM
Thread: Trane YCD300 gas pack heat exchanger
by gwoner- Replies
- 2
- Views
- 480
2 guys, 1 for 4 hours and 1 for 8 .No crane...
2 guys, 1 for 4 hours and 1 for 8 .No crane needed to install , maybe to get on the roof.
-
12-16-2012, 09:34 PM
Thread: Reznor Warehouse Furnace
by gwoner- Replies
- 22
- Views
- 1,457
Does the pilot lite? then go out. IGnition...
Does the pilot lite? then go out. IGnition control board
-
12-16-2012, 09:24 PM
Thread: WRONG WAY TO FIX CRACKS IN HTXCR
by gwoner- Replies
- 14
- Views
- 1,274
I wonder if the occupants getting headaches had...
I wonder if the occupants getting headaches had anything to do with this stupid repair. Must not own any red tags
-
11-29-2012, 08:00 PM
- Replies
- 22
- Views
- 1,814
Had same problem with a unit heater. Copper...
Had same problem with a unit heater. Copper cleaned, still wouldnt take. Picked up some Silvabrite 100 solder and wahlah, 95% tin 5% silver, problem solved. Stay away from water based flux.
-
11-15-2012, 08:39 PM
Thread: Trane Voyager Problems
by gwoner- Replies
- 2
- Views
- 778
Pull the J7 plug off the UCP .Check your DC...
Pull the J7 plug off the UCP .Check your DC voltage from J7-2 and J7-9.Apply power and jumper LTB -14 TO LTB -5. Should read 2.8 VDC for heat stage 1.LTB 14 TO LTB 3 HEAT 2 should be 3.71 VDC If the...
-
11-15-2012, 08:12 PM
Thread: Trane voyager troubles
by gwoner- Replies
- 7
- Views
- 761
I dont know if you meant -.2 I.W.C. , but thats...
I dont know if you meant -.2 I.W.C. , but thats the spec on that unit.
-
10-29-2012, 09:39 PM
Thread: rooftop charging in winter?
by gwoner- Replies
- 24
- Views
- 1,742
Use your recovery machine and weigh in . Works...
Use your recovery machine and weigh in . Works every time
-
10-15-2012, 10:42 PM
Thread: Rupp Temp Air MUA
by gwoner- Replies
- 0
- Views
- 212
Rupp Temp Air MUA
Anyone with info on where to get a IOM for MODEL CFA-220.
-
The new impellers come off really easy . Just...
The new impellers come off really easy . Just remove the dome nut. Most pull off .Havent had to use a puller yet
-
09-21-2012, 11:31 PM
Thread: coil cleaning
by gwoner- Replies
- 17
- Views
- 1,770
Water and dirt makes mud. You have to separate...
Water and dirt makes mud. You have to separate the split coils on the condensers.You will be surprised.What looks clean on the outside is most likely hiding enough cottonwood to knit grandma a...
-
09-19-2012, 09:49 PM
- Replies
- 11
- Views
- 914
Looks to me like your insulation on the HE access...
Looks to me like your insulation on the HE access panel is resting on that particular tube causing a hot spot.
-
09-19-2012, 09:40 PM
- Replies
- 45
- Views
- 3,463
What LED's are on when the failure occurs on...
What LED's are on when the failure occurs on the flow sensor and also what color is the flow proving sensor.Also what is the position of the black dot on the flow sensor.All very important for...
-
09-16-2012, 08:47 PM
- Replies
- 45
- Views
- 3,463
If the system is tripping after a short while,...
If the system is tripping after a short while, check the overloads on the compressor circuit breakers, they come from the factory set to zero, raise to 4 on all compressor c/b.'s, happened to me....
-
09-13-2012, 09:41 PM
Thread: Trane Summit DX VAV setup Question
by gwoner- Replies
- 22
- Views
- 1,678
Why not just raise the cooling setpoint on the...
Why not just raise the cooling setpoint on the individual vav box to please each zone thats an issue. This can be done in Tracer.
-
09-08-2012, 11:28 PM
- Replies
- 3
- Views
- 855
hold the self terst button in on the bottom of...
hold the self terst button in on the bottom of the sensor for 2-3 secs. t i think this action resets the sensor.
-
09-08-2012, 11:15 PM
Thread: Trane Voyager Unit issues
by gwoner- Replies
- 7
- Views
- 887
pull the j7 plug and check terminals j7-8 and 11...
pull the j7 plug and check terminals j7-8 and 11 to ground for 5 vdc. if not the ucp board is bad
-
i suggest testing the evap temp sensors, both in...
i suggest testing the evap temp sensors, both in and out. Replace as a pair.
-
09-08-2012, 10:55 PM
Thread: Trane RTU Identification
by gwoner- Replies
- 7
- Views
- 1,537
The AOP forums/Ask Our Pro's forums, are...
The AOP forums/Ask Our Pro's forums, are restricted to only Pro members that have been vetted by the AOPC can post advise, questions or commentary in a thread created by someone else. You need to...
-
08-26-2012, 08:43 PM
Thread: What do you guys think?
by gwoner- Replies
- 20
- Views
- 1,539
mini splits
Did half a dozen of them. No problems in 5 years. Just do it. Better than going home without pay.
-
08-26-2012, 12:10 AM
Thread: Trane Intellipak - High Pressure
by gwoner- Replies
- 32
- Views
- 2,560
intellipak
Never seen or heard of any charges other than R22 or R410A in an Intellipak
Results 1 to 25 of 108