  1. Replies
    15
    Views
    1,636

    I am not sure of the exact cost but some where in...

    I am not sure of the exact cost but some where in the 1500-2000 range.
  2. Replies
    18
    Views
    3,297

    Have a 30hxa076ry540 with the CARRIER...

    Have a 30hxa076ry540 with the CARRIER 30HXA076RY540 S/N 1602Q01447
    1. CHILLER 0,10 Alarm - 6 at 16:43 7-Sep-2007: A038 Oil Solenoid A1 Failure

    2. CHILLER...
  3. Replies
    16
    Views
    2,064

    Had a similar situation with a Few I-Pacs losing...

    Had a similar situation with a Few I-Pacs losing compressors, every one that
    failed had a defective CCH.
  4. Replies
    9
    Views
    3,126

    I have seen a utility from carrier that starts...

    I have seen a utility from carrier that starts and stops c-view, releasing the comm port driver. Carrier Rep said he would e-mail it to me.
  5. Replies
    6
    Views
    1,327

    Convert the system to 3v; Save yourself the...

    Convert the system to 3v; Save yourself the aggravation:
  6. Replies
    15
    Views
    1,636

    Dell D-630 with windows XP, has all the needed...

    Dell D-630 with windows XP, has all the needed ports. Carrier has come out
    with a new version of Service Tool that runs in windows. I am told it is half the
    price of C-View.
  7. Replies
    14
    Views
    1,232

    A properly sized VFD will convert the in coming...

    A properly sized VFD will convert the in coming single phase power to 3-Phase.
    The drive in such an application would be sized at 6 HP for a 3 HP single phase
    load, or there abouts.
  8. Replies
    27
    Views
    3,100

    The Carrier HX and HXA have performed well for...

    The Carrier HX and HXA have performed well for us. Keep up with the oil filter
    replacement recommendations and keep in mind that the water cooled machines
    do not like low condenser water temps....
  9. Replies
    7
    Views
    2,203

    This unit is a heatpump and has a sorted history...

    This unit is a heatpump and has a sorted history of lock out problems. Most units i have
    seen do not have LP switches but Loss of charge switches. Also there is a special LOC
    board that monitors...
  10. Replies
    13
    Views
    1,452

    Check out Maneurop compressors, they are less...

    Check out Maneurop compressors, they are less expensive and are a drop-in replacement for Trane scrolls.
  11. Replies
    2
    Views
    1,088

    Up grade to carrier 3V

    Up grade to carrier 3V
  12. Replies
    11
    Views
    1,136

    Just a thought, if the trane compressor is not in...

    Just a thought, if the trane compressor is not in warrenty you can get a much
    cheaper drop-in replacement from Maneurop.
  13. What type of compressor did you install? Are...

    What type of compressor did you install? Are their driers in the air handler?
  14. I have seen this problem when the valve is not...

    I have seen this problem when the valve is not installed properly[flow]
    Is the valve in the supply or return piping?
  15. Thread: 06D Oil loss

    by phixitman
    Replies
    7
    Views
    1,505

    What machine is this compressor in ?

    What machine is this compressor in ?
  16. Replies
    37
    Views
    3,901

    Fuses are thermal devices, the fuses are are...

    Fuses are thermal devices, the fuses are are overheating due to bad connections or there is a short to ground. Focus on the obvious.
  17. Replies
    9
    Views
    1,082

    Sounds like you lost a reed valve, maybe damaged...

    Sounds like you lost a reed valve, maybe damaged the rod on that cylinder. Check out superheat and cch.
  18. Thread: 20T Carlyle

    by phixitman
    Replies
    6
    Views
    838

    Does this setup have a liquid line solenoid, how...

    Does this setup have a liquid line solenoid, how is it controlled? Is the crankcase
    heater in good working order.What is the subcooling and superheat?
  19. Thread: Mold Smell

    by phixitman
    Replies
    9
    Views
    996

    Can this unit be set up to do some...

    Can this unit be set up to do some dehumidifcation, also seal up all return ducts,
    filter access doors ect.
  20. Replies
    15
    Views
    5,732

    Make sure the sensors are secure in their wells...

    Make sure the sensors are secure in their wells and that you are actually controlling to leaving water temp. Is this machine set up for Reset, does it have
    an EMM module. Check" Dely" setpoint...
  21. Replies
    15
    Views
    5,732

    Does this chiller have comfortlink controls...

    Does this chiller have comfortlink controls installed? What is the Approx. water
    volume in the system?
  22. Replies
    5
    Views
    829

    I agree with kcwong, most problems with chiller,...

    I agree with kcwong, most problems with chiller, boiler plants are due to the aux equipment.
  23. Replies
    11
    Views
    1,777

    Check the cc heater, verify correct control...

    Check the cc heater, verify correct control voltage. Start up with load side of
    contactors disconnected
  24. Replies
    11
    Views
    1,186

    With units disconnected from ICS and running in...

    With units disconnected from ICS and running in test modethe out put is again limited to 8,7 v
  25. Replies
    11
    Views
    1,186

    The Rain birds are connected to the correct...

    The Rain birds are connected to the correct pressure transducer port, Polarity of the drive signal is correct and was verified at both the RTAM and VFD. Static transducer out put was tested and found...
Results 1 to 25 of 28