  1. I haven't worked with ALC, so I'm not sure how...

    I haven't worked with ALC, so I'm not sure how you proxy points in. In the jace world when you add the point from the discovery,to the database. You can chose relinquish default, or type in 3113. Not...
  2. Try mapping the point as relinquish default. That...

    Try mapping the point as relinquish default. That would work. 3113 works also, in 6.0 FX which is niagara 3.8 JCI has come up with specific tuning policies for different points. Relinquish default is...
  3. Replies
    4
    Views
    276

    Nice!! sounds like you got it.

    Nice!! sounds like you got it.
  4. Replies
    4
    Views
    276

    I would personally custom program this. Not using...

    I would personally custom program this. Not using the selection, or any modules. There is a very large debate on the JCI connected community which I have posted on this subject of custom programming....
  5. Replies
    10
    Views
    446

    My background is also HVAC repair. I think that...

    My background is also HVAC repair. I think that is a solid foundation to start in controls. If you know the equipment you are controlling, and know the bad things that can happen with improper...
  6. Replies
    11
    Views
    490

    No T-TAPS!! Have seen some bad problems with...

    No T-TAPS!! Have seen some bad problems with that. One was where the maintenance staff ran N2 to new drives. In T-TAP form some over 50 feet. And there was lot a drives. I want to say like 40. I had...
  7. Thread: FX PCV

    by Norriski Tech
    Replies
    4
    Views
    273

    So what way do you proxy those points??

    So what way do you proxy those points??
  8. Thread: FX PCV

    by Norriski Tech
    Replies
    4
    Views
    273

    Proxy points as 3113. I think that is right?? I...

    Proxy points as 3113. I think that is right?? I will check my work laptop tomorrow, and let you know.
  9. I haven't seen this thread. I haven't had a good...

    I haven't seen this thread. I haven't had a good laugh for awhile!!! Thank you Ph33r!! The NAE host graphics,trends,alarms,etc. You will be golden!! The NAE is good for a tire block,boat...
  10. Replies
    3
    Views
    304

    On the JCI connected community there is some very...

    On the JCI connected community there is some very good videos. I'm assuming this regards your N2 network issue's in your other post?? Also in JCI 5.2 workbench they have added new tuning policies for...
  11. Replies
    3
    Views
    356

    Went to the website before my post. But thanks...

    Went to the website before my post. But thanks for the info. I spoke with the owner of Walker controls, he is going to provide some support. Not sure to what level yet!!!
  12. Replies
    3
    Views
    356

    Walker Controls

    We have took over a site, with walker controls. I have never seen the system before, and was wondering if there is someone out there who could answer some questions. I need to make some control...
  13. Replies
    4
    Views
    466

    You can bring that controller into Care, AX, Lon...

    You can bring that controller into Care, AX, Lon spec. Never had to use anything else, but we are a Honeywell dealer with access to the software. You need some software that is for sure!!!
  14. Replies
    4
    Views
    466

    There is configuration wizards in AX for that...

    There is configuration wizards in AX for that controller. Lon spec might also be a option. What sends occ mode to the controller, are you sure they at minimum not closed?? I also believe the...
  15. I have retrofitted many Trane machines over the...

    I have retrofitted many Trane machines over the years. Ranging from small to 100ton. Your unit by model number is 3 ton correct?? Without seeing the burner controller, even it you had to retrofit a...
  16. Replies
    16
    Views
    1,260

    I have replaced several N30s with the FX...

    I have replaced several N30s with the FX controllers. The JCI branded jace, allows for controller integration with PRN,and DMO files.If you have N2 controllers, I'm not sure how Alerton would talk...
  17. Replies
    13
    Views
    884

    Maybe we can back up here. What N2 devices do you...

    Maybe we can back up here. What N2 devices do you have?? What logic from the NCM will have to be recreated in the Jace?? Is there only MIGs that integrate your Mcquay heat pumps. N2 devices are...
  18. Replies
    13
    Views
    884

    I took over a site, that was in the middle of a...

    I took over a site, that was in the middle of a NCM to a FX70 swap by another employee that quit. It was a real nightmare!! due to my lack of knowledge of the MIGs. Both responses already are...
  19. Replies
    5
    Views
    591

    I'm not sure how many Jaces your site has?? But...

    I'm not sure how many Jaces your site has?? But you can just upgrade them?? Your new KMC jaces will have probably 3.7.106 which will work fine with 1_7_40 or 45 java. Depending on which versions your...
  20. Replies
    8
    Views
    467

    I run a win7 host machine with ultimate, and XP...

    I run a win7 host machine with ultimate, and XP mode for my older stuff. I have you also used Vmware workstation. I personally hate managing all the virtual machine!!! But its the world we live in....
  21. Replies
    10
    Views
    597

    You have to run the station on your PC. You now...

    You have to run the station on your PC. You now are the Jace!! When you copied the station from the jace, to your pc I assume its in the station folder under your JCI install. You have to open the...
  22. Yes, just like you have it in the brackets.

    Yes, just like you have it in the brackets.
  23. Hello, I have had this same issue with the PCG...

    Hello, I have had this same issue with the PCG controllers,and the FX-60. This caused me massive hours, and JCI tech support finally had an answer. In the default tuning policy of the jace, you need...
  24. Replies
    13
    Views
    1,139

    I don't know all the reason's for it. Once our...

    I don't know all the reason's for it. Once our vendor told us we couldn't get it for new jobs.We said fine, I was already doing Honeywell Ax so it was a fit for me to do FX. I just always thought,...
  25. Replies
    13
    Views
    1,139

    So berg2666 why didn't they bid a BSC NAE instead...

    So berg2666 why didn't they bid a BSC NAE instead of a FX60?? So it's a Network automation engine/Java application control engine.What does this mean?? Branch doesn't know the jace in are area. They...