    IFM/Compressor phenomenon: Marginal flow can...

    IFM/Compressor phenomenon: Marginal flow can cause rapid temperature change at flow switch probe when compressors start/stop = Flutter effect/Nuisance trips.
    Glycol? Installed flow switch (cm/sec)?...
  2. Replies
    8
    Views
    814

    I have seen this a few times on Intellipaks with...

    I have seen this a few times on Intellipaks with an LCI-I/Lon board being used for comm. If unit has LCI-I, Switch unit control mode from BAS to LOCAL and see if unit starts.
  3. Replies
    3
    Views
    1,301

    A C02 error/fault will not shut the unit down,...

    A C02 error/fault will not shut the unit down, Unless BAS has something to do with it.
  4. Replies
    12
    Views
    776

    Why not use hot gas bypass and a liquid receiver.

    Why not use hot gas bypass and a liquid receiver.
  5. Replies
    41
    Views
    4,250

    This would be a true statement if this unit was a...

    This would be a true statement if this unit was a RTAA.

    graham,
    YOU SHOUTED OUT LOUDLY ABOUT THE FUNCTION OF THE GLASS, BUT YOU MISSED SUMTIN!
    The glass also indicates moisture. :D
  6. Replies
    41
    Views
    4,250

    Circuit charge can be checked with full load...

    Circuit charge can be checked with full load conditions and subcooling chart for tonnage/efficiency(standard,high) of that circuit. With a dropping film flooded type evaporator, Charge could be way...
  7. Replies
    37
    Views
    2,413

    :eek:

    :eek:
  8. Thread: CVHF

    by jimbob73
    Replies
    40
    Views
    2,629

    Yes, With dynaview/CH530, You need techview to...

    Yes, With dynaview/CH530, You need techview to service temperature sensors/pressure transducers or to operate devices manually like IGV, starter, etc.... This software is free and can be dowloaded...
  9. Thread: CVHE 650

    by jimbob73
    Replies
    27
    Views
    1,588

    Flows are incorrect, Crap load of oil in...

    Flows are incorrect, Crap load of oil in refrigerant/evaporator, Not enough flow, Glycol present, Hijacking "failure to accelerate thread" etc.........
  10. Thread: 5 ton RTU

    by jimbob73
    Replies
    18
    Views
    2,074

    Did you wash out in between the coils?

    Did you wash out in between the coils?
  11. Thread: CVHE 650

    by jimbob73
    Replies
    27
    Views
    1,588

    It can't be that easy, Although it seems 9 out of...

    It can't be that easy, Although it seems 9 out of 10 times it is. The 1 time it's not is when hairs start turning gray and hair loss increases.
  12. Replies
    46
    Views
    4,432

    It is an engineer designed hail guard for that...

    It is an engineer designed hail guard for that unit. If it can work on a piece of paper, then it will work on the unit. A classic example of how what is drawn on paper does not always work as well in...
  13. Thread: vacuum gauge

    by jimbob73
    Replies
    11
    Views
    1,034

    I really like the Inficon leak detectors, But the...

    I really like the Inficon leak detectors, But the Inficon vacuum gauge I don't care for. Been happy with my yellow jacket vacuum gauge.
  14. Thread: CVHF

    by jimbob73
    Replies
    40
    Views
    2,629

    T.O. makes things more interesting everywhere he...

    T.O. makes things more interesting everywhere he goes! I was gonna get rid of NFL Sunday ticket because the price of it is getting rediculous, But the BILLS keep finding ways to keep me paying for...
  15. Replies
    9
    Views
    1,516

    I agree with ascj, A remote panel with NSB (night...

    I agree with ascj, A remote panel with NSB (night setback) was used for setback control of the unit and I doubt they are still available.
  16. Thread: CVHF

    by jimbob73
    Replies
    40
    Views
    2,629

    It should have the new style economizer flanges? ...

    It should have the new style economizer flanges?
    If so, Silicon bead faces bolt heads, Torque in star pattern, 30 ft lbs then 55 ft lbs.
  17. Replies
    9
    Views
    956

    Plate and frame?

    Plate and frame?
  18. Replies
    9
    Views
    1,109

    I have replaced a few of em due to that. There...

    I have replaced a few of em due to that. There was a very rare problem with shaft/packing alignment on some of the suction butterfly valves. Only fix is to replace the entire butterfly valve.
  19. Replies
    24
    Views
    2,053

    An EBS guy in our office sent me those chiller...

    An EBS guy in our office sent me those chiller and CTV videos sometime back in November and that has been the only email I havn't deleted.


    About the bills and being in the midwest. I was born...
  20. Replies
    24
    Views
    2,053

    Here is another one for the CTV, Funny suff! :D ...

    Here is another one for the CTV, Funny suff! :D

    http://www.youtube.com/watch?v=_31uAoXzG7A&feature=related
  21. The Trane part number for that board is BRD00621....

    The Trane part number for that board is BRD00621. The factory no longer has it and there is no replacement available. You could try a electronics repair establishment or ebay. I heard of people...
  22. Thread: just curious

    by jimbob73
    Replies
    9
    Views
    653

    You guys can give me all the copper tubes, I'll...

    You guys can give me all the copper tubes, I'll get rid of them for ya! ;)
  23. Replies
    27
    Views
    2,490

    Simple Green, Then a pre moistened alcohol towel...

    Simple Green, Then a pre moistened alcohol towel just before assemply.
  24. Replies
    25
    Views
    3,916

    If you want to get technical, There is software...

    If you want to get technical, There is software that can be installed on a computer that can be hooked up to an Intellipak, It's called Tracer Summit! ;)

    I agree with graham, Post what active...
  25. Replies
    6
    Views
    642

    It hasn't done much good lately because a...

    It hasn't done much good lately because a majority of the PDF files are corrupt. Hopefully it will be fixed some time soon.
  26. Replies
    27
    Views
    1,544

    And condenser coil cleaning

    And condenser coil cleaning
  27. Replies
    8
    Views
    900

    Sounds like you have a bad liquid level sensor....

    Sounds like you have a bad liquid level sensor. Even with no refrigerant present, Sensor would indicate -1.1" or -1.0" on FP or techview. An actual sensor failure diagnostic is the same for...
  28. Replies
    10
    Views
    813

    A bee sting/insect bite while working on the job...

    A bee sting/insect bite while working on the job is a recordable, Who knew?
  29. Replies
    12
    Views
    1,000

    A metal rod is sophisticated, I understand. :D

    A metal rod is sophisticated, I understand. :D
  30. Replies
    12
    Views
    1,000

    It's uA DC that you want. Been a long time, But...

    It's uA DC that you want. Been a long time, But if I had to guess, A steady 1.5 microamps or greater is what you want?
  31. Replies
    20
    Views
    1,651

    Bug, What bug? I was referring to the right...

    Bug, What bug? I was referring to the right gloves for the job part. :D
  32. Replies
    20
    Views
    1,651

    You are one dedicated Trane citizen!

    You are one dedicated Trane citizen!
  33. Replies
    20
    Views
    1,651

    Geesh, In the midwest, USA, There are Trane...

    Geesh, In the midwest, USA, There are Trane offices all over the place so a job 3 hours away is considered a haul.
  34. Replies
    20
    Views
    1,651

    You were on a job 8 hours from home?

    You were on a job 8 hours from home?
  35. Replies
    20
    Views
    1,651

    chiller mekanik, Because there are people on here...

    chiller mekanik, Because there are people on here with too low of a post count that could do harm to themselves and others if they had the info :D

    I'm being sarcastic, Due to some of the stuff...
  36. Replies
    20
    Views
    1,651

    If you are a trane tech, Take a look on the back...

    If you are a trane tech, Take a look on the back page of the Sept/Oct 2008 technician newsletter.
  37. At setpoint of 0 to -11 C = 32 to 12.2 F, Your...

    At setpoint of 0 to -11 C = 32 to 12.2 F, Your short on freeze protection/glycol. While there may be burst protection with flow, Solution would turn to slush which would cause pump efficiency/flow to...
  38. You run the chiller at 0 to -11 degrees F with...

    You run the chiller at 0 to -11 degrees F with solution good down to 27 degrees? :eek: Am I reading this right? I would assume setpoint is Celsius because chiller setpoint I think only goes down to 0...
  39. Replies
    16
    Views
    1,638

    What would you do if you had an emergency stop...

    What would you do if you had an emergency stop circuit open on a voyager since you seen a lot of these? Emergency stop circuit serves the same purpose on an intellipak as a voyager or any other unit...
  40. Thread: NFL Week 4

    by jimbob73
    Replies
    12
    Views
    643

    GO BILLS!!!

    GO BILLS!!!
  41. Replies
    12
    Views
    2,002

    Intellipak supply temp sensors can't be...

    Intellipak supply temp sensors can't be adjusted/calibrated through HI.
  42. Replies
    7
    Views
    907

    The plastic that was on the control panel when...

    The plastic that was on the control panel when the chiller was new and had to be dismantled for install or the rag that the last tech left behind.
  43. Replies
    8
    Views
    826

    By everything you said, I think I would swap...

    By everything you said, I think I would swap breakers to be sure it isn't the breaker. I have seen quite of few breakers on these units that have weakened and trip well below must hold trip amps on...
  44. Replies
    1
    Views
    637

    standard capacity

    standard capacity
  45. Replies
    21
    Views
    4,472

    The compressor sounds lika a wannabe 3 phase :)....

    The compressor sounds lika a wannabe 3 phase :). Perhaps it's one of the new hybrid compressors that runs on single or 3 phase power :D
  46. Replies
    14
    Views
    2,686

    Long periods of time or conditions that cause...

    Long periods of time or conditions that cause higher then normal condenser pressures like walls, other units,etc. The permanent fix for this is to replace current EXV motors with the high torque...
  47. Replies
    23
    Views
    2,078

    The new Trane FR uniforms are surprisingly quite...

    The new Trane FR uniforms are surprisingly quite comfortable (breathable, thin and soft). The only down side is the navy blue pants, But still much better then our last uniforms which consisted of...
  48. Replies
    8
    Views
    972

    Loctite Chisel gasket remover works like magic on...

    Loctite Chisel gasket remover works like magic on valute flanges without jacking bolts, Especially motor to discharge flange. Once all but a couple of bolts are removed, Flood the empty bolt holes...
  49. Replies
    2
    Views
    813

    IOM's located at poolpak.com are a good start....

    IOM's located at poolpak.com are a good start. These will provide you with a majority of the information you need to know. If the units are under warranty, then you must attend the class in PA to be...
  50. Replies
    10
    Views
    1,153

    Are the motor terminals leaking on it too? Don't...

    Are the motor terminals leaking on it too? Don't try changing the subject or anything. :D