    Does this happen when there is a power loss to...

    Does this happen when there is a power loss to the panels, server, or both?
  2. Replies
    6
    Views
    431

    Thanks for the info, I learned something....

    Thanks for the info, I learned something....
  3. Replies
    6
    Views
    431

    Only other possibility could be a scheduling...

    Only other possibility could be a scheduling issue? You mentioned it works for "real" alarms so I'm at a loss.....When I get back to work I'll see if I can duplicate the problem.
  4. Replies
    6
    Views
    431

    Try using the "manual" notification and verify...

    Try using the "manual" notification and verify that works i.e. send a page to your cell phone.
  5. Replies
    4
    Views
    1,182

    Set subpoint #59 from zero to 4. This will...

    Set subpoint #59 from zero to 4.

    This will reverse the reversing valve.
  6. Replies
    3
    Views
    804

    I think I'd be looking at the BLN (automation...

    I think I'd be looking at the BLN (automation level network) for cabinet errors or wiring issues.
  7. I'm sorry, I think I have the picture now..... ...

    I'm sorry, I think I have the picture now.....

    Remove the TEC from the system profile. Then, re-add the device. Typically when this happens the unbundled point shows up as *F* failed.
  8. Replies
    2
    Views
    506

    1)Set sub point #88 (stage count) to 1 2)DO 4 is...

    1)Set sub point #88 (stage count) to 1
    2)DO 4 is for stage 2 and DO 5 is stage 3. So, to be on the safe side try to command DO 5 after changing stage count.
  9. Replies
    15
    Views
    2,393

    Grounding is different on the PXC, take note. It...

    Grounding is different on the PXC, take note.
    It is possible that a MBC controller is failing...Ostracize the MBCs one at a time to see if problem is corrected.
  10. Not knowing the application I'm at a loss. ...

    Not knowing the application I'm at a loss.

    Perhaps the TEC revs are not the same?
  11. Hello, sorry for the delay. The application is...

    Hello, sorry for the delay.

    The application is usually point #2
    3.3 is the front end version.
    Since I don't know the application try #1 or #2 below:
    1) Set #14 to "yes" and command #13 to...
  12. I'll take a stab at this: Pre Apogee required...

    I'll take a stab at this:

    Pre Apogee required manual unbundle, i.e. adding point, lan, and cabinet numbers.

    Apogee allows you to auto unbundle from the front end (Insight) This is cool because...
  13. If you could tell me what application you're...

    If you could tell me what application you're using and what point number you are trying to command perhaps I could help.

    Some items (I think fan) is not commandable. Also, if you're out of range...
  14. Replies
    8
    Views
    1,144

    Temp Repair

    Get a known "good" TEC. Install about two feet of wire on new TEC, remove existing bad LAN and install good TEC with two feet of wire. If that works you have issues with "bad" P1 network. If that...
  15. Replies
    4
    Views
    864

    If you're using say a L2SL point it can be...

    If you're using say a L2SL point it can be configured to calculate run time (totalized). The PPCL command "total" can be used to calculate run times for lead lag, etc.
  16. Replies
    4
    Views
    864

    Are you doing this based on actual run time or on...

    Are you doing this based on actual run time or on a weekly / monthly interval? We can get creative here.
  17. Thread: siemens problem

    by pangea
    Replies
    17
    Views
    1,434

    Hi Larry, I'm sorry that I wasn't clear: ...

    Hi Larry,

    I'm sorry that I wasn't clear:

    Some of the TEC firmware and some of the older panel firmware would do strange things. i.e command priority would not be displayed correctly.
    ...
  18. Replies
    17
    Views
    1,235

    A better UPS will resolve the problem. Make...

    A better UPS will resolve the problem.

    Make sure that auxillary transformers (if used for this circuit) are on the UPS power. Often I will find the DDC control cabinet on UPS power but not the...
  19. Thread: siemens problem

    by pangea
    Replies
    17
    Views
    1,434

    I'm going to take a stab here: Is it possible...

    I'm going to take a stab here:

    Is it possible that there is a graphic for the 2051 (fan coil) application? If so, are these points displayed on the graphic that someone may be commanding with the...
  20. I've met some really great electricians in my 15...

    I've met some really great electricians in my 15 year plus career with controls. Some of these guys couldn't do control work if you held a gun to their head.

    However, the best end of the company...
  21. Replies
    1
    Views
    1,031

    I'd like to be contacted

    I'd like to be contacted
  22. Replies
    9
    Views
    1,520

    Hi, Datamate base is unstable at best....

    Hi,

    Datamate base is unstable at best. Datamate Advanced needs to be at the same revision as Insight to transfer data. The yearly license is out of the question!

    If you're setting up TECs then...
  23. Replies
    11
    Views
    1,340

    Controlgirl, I worked for Siemens for about 15...

    Controlgirl,

    I worked for Siemens for about 15 years and worked with the product 5 years before hiring on.

    Several of my intructors were from the Canada. From what I can tell Canada is the...
  24. Replies
    6
    Views
    1,828

    That's great news! You have one great Siemens...

    That's great news!

    You have one great Siemens branch, count your blessings.
  25. Replies
    11
    Views
    1,340

    Welcome to Siemens and the world of integration....

    Welcome to Siemens and the world of integration. Been there and done that, good luck!