10-12-2010, 09:53 PM
Thread: rtaa chiller
by Tranetek- Replies
- 20
- Views
- 1,615
Have you ran a diode check. Unplug the ct's from...
Have you ran a diode check. Unplug the ct's from the board, put your meter on diode check, should be 1.5 volts or close between the pens for each ct. If not replace the module.
-
06-13-2010, 11:35 PM
Thread: RTAA manual reset alarm ?
by Tranetek- Replies
- 7
- Views
- 671
circuit reset is in the p1 menu
circuit reset is in the p1 menu
-
06-09-2010, 12:01 AM
Thread: Trane rooftop unit
by Tranetek- Replies
- 17
- Views
- 2,499
Some of you don't need to be working in this...
Some of you don't need to be working in this field from what I can tell
-
04-02-2010, 09:33 PM
Thread: Honeywell W7900 won`t shut off
by Tranetek- Replies
- 7
- Views
- 1,045
You can use a Trane TOL101 to check out a w7900....
You can use a Trane TOL101 to check out a w7900. Comes with all connections and instructions for checking it out
-
01-11-2010, 01:15 AM
Thread: Trane vs. York Chillers
by Tranetek- Replies
- 10
- Views
- 1,185
I didn't know there was a York that wasn't loud.
I didn't know there was a York that wasn't loud.
-
11-19-2009, 07:04 AM
Thread: Trane RTAA 185 low oil flow
by Tranetek- Replies
- 63
- Views
- 5,785
Originally Posted by jt8350 forgot to mention...
Originally Posted by jt8350
forgot to mention that fan cycling controls. was the suggestion of a trane tech from the local trane office.
He wouldn't be a tech at my office making suggestions... -
11-17-2009, 11:16 PM
Thread: Trane RTAA 185 low oil flow
by Tranetek- Replies
- 63
- Views
- 5,785
People do this stupid crap because they don't...
People do this stupid crap because they don't know what they are doing and how the machine works. Learn now the machine operates and then figure out what the real problem is. Don't just put...
-
10-16-2009, 02:17 PM
Thread: make up air
by Tranetek- Replies
- 14
- Views
- 1,026
One of the first things I would do is drop the...
One of the first things I would do is drop the chilled water temp. 52 isn't going to dehumidify much of anything.
-
10-10-2009, 05:56 PM
Thread: RTAA phase reversal
by Tranetek- Replies
- 5
- Views
- 664
Find the correct service lit. and run a diode test
Find the correct service lit. and run a diode test
-
07-15-2009, 04:41 PM
Thread: Oil Pressure
by Tranetek- Replies
- 6
- Views
- 451
Differential pressure switch should trip at 50...
Differential pressure switch should trip at 50 psid
-
07-13-2009, 10:12 PM
Thread: SCROLL CHILLERS
by Tranetek- Replies
- 40
- Views
- 3,054
Actually Trane does have a water cooled scroll...
Actually Trane does have a water cooled scroll unit. CGW* My question is, if you are having so much trouble with load swing on the chiller why not put in a storage tank and have it pump to the...
-
07-11-2009, 11:57 PM
Thread: RTAA 80 oil system fault
by Tranetek- Replies
- 6
- Views
- 595
Check sat evap and suction temp sensors to make...
Check sat evap and suction temp sensors to make sure they are correct. You also need to check them to ground. If there is any reading to ground they should be changed. A grounded sensor can look to...
-
04-12-2009, 10:33 PM
Thread: CVHF surging
by Tranetek- Replies
- 39
- Views
- 2,894
It is usually one of three things. Air,...
It is usually one of three things. Air, condenser water to hot or fouled tubes. Condenser approach should be no more then 3 degrees at full load. Have you checked to see if your purge is actually...
-
04-08-2009, 06:17 PM
Thread: Trane RTHA noise
by Tranetek- Replies
- 3
- Views
- 621
Sounds like it is rotating backwards for just a...
Sounds like it is rotating backwards for just a little until the check valve closes. The thud you are hearing sounds like the check valve closing.