  1. Replies
    51
    Views
    7,738

    MKnyc- I agree, the RTAA needs to start the pump...

    MKnyc- I agree, the RTAA needs to start the pump and it does both start/stop of the pump and lets the pump run for 5 minutes after chiller is disabled. I use the remote contacts on the RTAA board to...
  2. Replies
    51
    Views
    7,738

    Graham, Yeah last October was about the last...

    Graham,
    Yeah last October was about the last time I had time to really look at this problem.
  3. Replies
    51
    Views
    7,738

    Chiller, The RTAA onboard computer controls the...

    Chiller,
    The RTAA onboard computer controls the pump. I installed a pressure differential switch which is monitored by the BAS for proof of pump before the chiller is enabled. The pump runs for 5...
  4. Replies
    51
    Views
    7,738

    Thanks my friend :)

    Thanks my friend :)
  5. Replies
    51
    Views
    7,738

    Freonrick-Hadn't thought of that one yet, thanks...

    Freonrick-Hadn't thought of that one yet, thanks I'll include this in my troubleshooting.
  6. Replies
    51
    Views
    7,738

    rtaa trips

    One thing I've learned and that's that this can be tricky problem on a RTAA.
    My stage 2 runs perfect. But stage 1 constantly trips on "low saturated refrigerant temperature". I've ran the EXV...
  7. Thread: VFD training

    by koolncali
    Replies
    8
    Views
    1,844

    chillerguy- It used to be that when I needed a...

    chillerguy-
    It used to be that when I needed a vfd replaced I would call for the ABB drive (we are sticking to ABB) factory rep and coordinated his visit with the EMS rep. But I stuck my neck out...
  8. Replies
    27
    Views
    2,445

    jayguy- thanks for the word of encouragement, I...

    jayguy- thanks for the word of encouragement, I just need to get back into the habit of double checking everything.
  9. Replies
    27
    Views
    2,445

    Thanks fcs

    Thanks fcs
  10. Replies
    27
    Views
    2,445

    Graham- thanks for trying to get me to think....

    Graham- thanks for trying to get me to think. sometimes i have to be knocked over the head :).

    And thanks to everybody who tried to help.

    It's really a great feeling that there are so many...
  11. Replies
    27
    Views
    2,445

    jayguy- Talk about troubleshooting from afar!...

    jayguy-

    Talk about troubleshooting from afar! Let me tell you that you hit the nail on the head! I read your post then I went and did what I should have done (and normally do) and double checked...
  12. Replies
    27
    Views
    2,445

    chiller- another interesting possibiliy. first...

    chiller- another interesting possibiliy. first I'm going to concentrate on the sensors I replaced since the new alarm started after I replaced them. Then I'll have to look elsewhere if necessary....
  13. Replies
    27
    Views
    2,445

    Psycho- this one is going off on low pressure...

    Psycho- this one is going off on low pressure cutout but I realize that temperature is being converted to a pressure reading so it's all related. I'll keep in mind your input about the solenoids.
  14. Replies
    27
    Views
    2,445

    Graham- Thanks for the great advice, I really do...

    Graham- Thanks for the great advice, I really do appreciate the input from you and all the other guys here.

    Yeah with the discrepancies of readings between my gauges and the UCM readings it looks...
  15. Replies
    27
    Views
    2,445

    Graham- Thanks for the input. My chiller (I work...

    Graham- Thanks for the input. My chiller (I work at a jr college) is an RTAA125 and it does have a low pressure switch for each compressor (2). Looks like 12vdc comes out of the module, passes...
  16. Replies
    27
    Views
    2,445

    Ok jayguy I see what you're saying is that if the...

    Ok jayguy I see what you're saying is that if the pressures are not actually what the UCM is reading and telling the low pressure cutout to open, then it can throw it out of balance and maybe cause...
  17. Replies
    27
    Views
    2,445

    Plugger I ran a check on circuit #1 EXV at the...

    Plugger I ran a check on circuit #1 EXV at the module and it ran the check ok.
  18. Replies
    27
    Views
    2,445

    Graham- it's a RTAA125 chiller. I replaced the...

    Graham- it's a RTAA125 chiller. I replaced the "saturated evaporator sensor" and the "suction temp sensor" because the chiller was tripping daily on "low saturated temperature". I ran the...
  19. Replies
    27
    Views
    2,445

    Maxpower- no it's a packaged chiller sitting on a...

    Maxpower- no it's a packaged chiller sitting on a rack. It has two low pressure switches at the outlet of the chiller barrel.
  20. Replies
    27
    Views
    2,445

    RTAA trips on Low Pressure Cutout

    I need help from anyone who is knowledgeable on Trane RTAA chillers. I previously had a thread because my RTAA chiller circuit 1 was shutting off on "low saturated evap temperature". I replaced both...
  21. Replies
    51
    Views
    7,738

    Excellent advice Paceleader. I will check for...

    Excellent advice Paceleader. I will check for proper load/unloading of the compressor at the conditions you mentioned.
  22. Replies
    51
    Views
    7,738

    Yeah there is i guess i'm in luck.:cool:

    Yeah there is i guess i'm in luck.:cool:
  23. Replies
    51
    Views
    7,738

    Bowhunter- Thanks for the info now I just have...

    Bowhunter-

    Thanks for the info now I just have to see where I can get the part.
  24. Replies
    51
    Views
    7,738

    Cntrl- Thanks I'll check the manual for sh...

    Cntrl-
    Thanks I'll check the manual for sh adjustment. It's a temporary chiller set-up with fire hoses and primary flow only (one pump). The flow is constant. I hadn't thought about flow as an issue...
  25. Replies
    51
    Views
    7,738

    Bowhunter- Thanks for that advice. This morning...

    Bowhunter-
    Thanks for that advice. This morning circuit #1 was in a latched fault "low saturated refrigerant temperature" alarm once again. I took some readings on ciruit #1 while still in alarm and...
  26. Replies
    51
    Views
    7,738

    Iqbalissa- 1-I'm not sure yet how to adjust the...

    Iqbalissa-
    1-I'm not sure yet how to adjust the superheat on this electronic expansion valve.
    2- I don't see any evidence of a pressure drop through the drier core
  27. Replies
    51
    Views
    7,738

    Madhat- This is also a temporary chiller hooked...

    Madhat-
    This is also a temporary chiller hooked up to fire hoses running about 80 feet up to the rooftop air handlers on top of a 4-story building. But I'm responsible for this chiller because i...
  28. Replies
    51
    Views
    7,738

    thanks for the tip TAC and bowhunter I'll check...

    thanks for the tip TAC and bowhunter I'll check the sensors now that I found a manual with the readings. and know what to look for Bowhunter: I figured someone out there had ran into the same problem.
  29. Replies
    51
    Views
    7,738

    Graham- I found a Trane RTAA troubleshooting...

    Graham-
    I found a Trane RTAA troubleshooting manual online that goes into great detail about checking the EXV. So I'll have to dig into that.
  30. Replies
    51
    Views
    7,738

    Graham- I'm not suspecting low charge. No...

    Graham-
    I'm not suspecting low charge. No setpoints have been changed since the chiller was installed about 2 years ago and it has ran without a hitch up until about 3 weeks ago. The fluid being...
  31. Replies
    51
    Views
    7,738

    The sightglass is clear at all times.

    The sightglass is clear at all times.
  32. Thread: Tools

    by koolncali
    Replies
    29
    Views
    1,817

    [QUOTE=r404a;2016673]Does anyone here throw or...

    [QUOTE=r404a;2016673]Does anyone here throw or break tools when they get mad when overhauling equipment?


    As an apprentice I worked with a journeyman who had half of his index finger missing on...
  33. Replies
    51
    Views
    7,738

    Allstar- I'll check those readings this week and...

    Allstar- I'll check those readings this week and let you know.
  34. Replies
    51
    Views
    7,738

    That's with pressure gauges attached. Also I...

    That's with pressure gauges attached. Also I found that the pressure readings on the adaptive control are very close to my gauge readings.
  35. Replies
    3
    Views
    636

    I've had six Governair units running for about 15...

    I've had six Governair units running for about 15 years and they have been reall workhorses. I've never had a compressor failure(knock on wood) but the factory auxiliary switches on the contactors...
  36. Replies
    51
    Views
    7,738

    Trane RTAA air-cooled chiller nuance trips

    Ok guys I've got a Trane RTAA 125 chiller with the standard adaptive control. About three weeks ago circuit #1 starting going into a "low saturated refrigerant temperature" alarm which shuts down...
  37. Replies
    15
    Views
    1,706

    compressor removal

    hvac-
    I've replaced several compressors weighing over 500 lbs. and setting high off the ground. I make a wooden box and sit it on a four-wheel dolly. I measure the box and dolly to be even with the...
  38. Replies
    14
    Views
    1,682

    Shiffer- I actually have 3 drives to replace....

    Shiffer-
    I actually have 3 drives to replace. For one building I have an air handler with defective Graham(Danfoss) drives for supply and return motors. Another building has a defective Saftronic...
  39. Replies
    95
    Views
    9,459

    sysint- Great information and links you got...

    sysint-

    Great information and links you got for me. I will put those links in my favorites for later. I have to say you know your stuff.
    And you are also right about the college's project...
  40. Replies
    14
    Views
    1,682

    dingman- Thanks for that info. Now I got to...

    dingman-

    Thanks for that info. Now I got to see if I got what it takes to make it run :)
  41. Replies
    14
    Views
    1,682

    dingman- What I'm doing is replacing an existing...

    dingman-
    What I'm doing is replacing an existing Saftronics drive. I'm want retrofit the Saftronic bypass to the new ACH550 which doesn't appear to be a problem. It looks like the easiest thing for...
  42. Replies
    95
    Views
    9,459

    siemens vs lonworks

    Guys-

    Ameresco usually conducts their meetings with an entourage of engineers, so if one stumbles, another is there to fill in the "missing links". Normally in these meetings is an Ameresco team...
  43. Replies
    95
    Views
    9,459

    siemens vs lonworks

    navair-
    Yeah hopefully that will inspire Ameresco to look out for everyone's best interest :). I will for sure be keeping an eye out for who's going to commission all the equipment.

    ...
  44. Replies
    95
    Views
    9,459

    siemens vs lonworks

    krac/navair-

    Yes all public colleges in California are funded by the state. Our new buildings are being funded by a state proposition passed by voters. <b>Krac</b> right now our 'Termgubinator' is...
  45. Replies
    95
    Views
    9,459

    siemens vs lonworks

    sysint-

    Well my boss and I had a meeting with Ameresco on Thurs but only one of their more recently hired mechanical engineers showed up and just took notes as we went through the "plans" which we...
  46. Replies
    95
    Views
    9,459

    siemens vs lonworks

    PS-
    That's good insight into my situation and great advice. I will take all of that into consideration. A central plant with a screwed up control system would be a true nightmare for me and...
  47. Replies
    14
    Views
    1,682

    siemens and abb speed drives

    krac- ok I was just concerned about rotation, but I know I can stop the motor quickly if rotation is wrong. For fan status I'll use a current sensor switch on one of the 480 leads to the motor to...
  48. Replies
    14
    Views
    1,682

    siemens and abb speed drives

    krac-
    Thanks for the good information. The safety contacts(smoke alarm) will be landed on the bypass so I'll jumper 10 + 16. I've got a diagram of the existing bypass but I'll have to find a copy of...
  49. Replies
    95
    Views
    9,459

    tudormatt- An energy project manager has been...

    tudormatt-
    An energy project manager has been awarded a contract to install a central plant at my campus. I have an existing Siemens BAS running on fiber and copper with a little Apogee and mostly...
  50. Replies
    14
    Views
    1,682

    Siemens and ABB speed drives

    Is anyone familiar with using Siemens to control an ABB ACH550 HVAC speed drive? I have to replace a Saftronic drive controlling a 10 HP return fan motor with an ABB drive and use the existing...