  1. Replies
    3
    Views
    273

    What version of Rover are you using? Anything...

    What version of Rover are you using? Anything older than 7.1 sp8(or around there) is only going to look for the device on the ZL domain. You can use your LN tool to commission the 580, and then set...
  2. I believe that it's been out for 5 years or so. ...

    I believe that it's been out for 5 years or so. You could say that it's the BACnet equivalent of the 580/581, so anything that you would use a 580/581 for you could also do with the UC600.
  3. Replies
    8
    Views
    480

    12/13 to 27 is the default safety circuit. It's...

    12/13 to 27 is the default safety circuit. It's looking for a N/C contact. You can verify by looking at the digital input parameters through the display.
  4. Replies
    7
    Views
    716

    The older CGAF is referred to as the "Intellipak"...

    The older CGAF is referred to as the "Intellipak" chiller since it uses the same UI. You can get a Lon card but not BACnet for that model of chiller. The BCI-C BACnet interface is only for the...
  5. Replies
    6
    Views
    666

    Ensure baud rate is correct as stated above. ...

    Ensure baud rate is correct as stated above. Ensure that the polarity is correct, and that the Link switch is set for BACnet and not IMC. Use the BACnet setup tool to change baud rate if necessary,...
  6. Replies
    2
    Views
    337

    Point mapping, or actually what points exist in a...

    Point mapping, or actually what points exist in a particular device. Also used to bind info from device to device, for example if you have to vav's that serve the large conference room, you can bind...
  7. Newton systems is correct. You just have to...

    Newton systems is correct. You just have to create an account.
  8. Nlutil should be able to modify the DSN as...

    Nlutil should be able to modify the DSN as scrooloose says. Nodeutil might also work, however I haven't used it in a long time. Both can be found for free online.
  9. Replies
    2
    Views
    549

    Depends on the version of Tracker. Since you say...

    Depends on the version of Tracker. Since you say "slightly newer two line display units", I'm gonna suggest that you will need hyperterminal. You'll need an RJ12 connector to serial (Trane PCM/UPCM...
  10. If it's 2002, it's a Reliatel board and not a...

    If it's 2002, it's a Reliatel board and not a UCP. Simply disconnect the BAYSENS from terminals 1,2,3,4 etc., hook up your new stat on the conventional thermostat connections R,Y,G,W etc. If there...
  11. Replies
    1
    Views
    307

    You want to use the Comm4 tool. Observe proper...

    You want to use the Comm4 tool. Observe proper polarity, and switch if necessary. I don't remember anything about the PCMCIA card, I've always used a Black Box Comm4 adaptor. If the polarity isn't...
  12. I would personally hw and not do the comm unless...

    I would personally hw and not do the comm unless it is in the spec. Regardless of mfg or protocol.
  13. RTAC software is Techview which is free to any...

    RTAC software is Techview which is free to any and all to download. TU is not required or necessary to configure anything. It'll be very hard for you to purchase a copy of TU yourself. Your best...
  14. Replies
    1
    Views
    320

    I'll take a shot in the dark here. The...

    I'll take a shot in the dark here.

    The sensor accuracy is +/- .25C. Which means if your factory calibrated test instrument is measuring 19C, the sensor would read anywhere between 18.75C and...
  15. Replies
    2
    Views
    297

    You'll need Rover. I'm about 99% sure. There will...

    You'll need Rover. I'm about 99% sure. There will be some configuration available through Summit, but I don't believe that you can change the unit type.
  16. Replies
    13
    Views
    758

    You tell me. Is your JACE using DSN B? I'm...

    You tell me. Is your JACE using DSN B? I'm guessing it's not, but I don't work with the JACE platform. Making a config change in Rover won't change anything on the Lon network. You have to tell...
  17. Replies
    9
    Views
    874

    The +1.5 is shown in the VAV, it's called the...

    The +1.5 is shown in the VAV, it's called the "occupied offset". This makes the UC vav setpoint logic similar to the vv550, or Lon in general, where the "setpoint" is the median and the offset is...
  18. Replies
    13
    Views
    758

    If you don't know your domain, connect Rover,...

    If you don't know your domain, connect Rover, service pin a device. You'll see a message in Rover stating something like "a service pin press was received on a different domain than the discovery...
  19. Replies
    14
    Views
    1,061

    You should only need to command the Multi-State...

    You should only need to command the Multi-State Output - 7 for occupancy (1=occupied, 2=unoccupied). The other Binary Outputs that you mentioned are to enable/disable heating or cooling etc. not an...
  20. Replies
    8
    Views
    782

    I'm old fashioned, I still use the 0-10vdc/4-20ma...

    I'm old fashioned, I still use the 0-10vdc/4-20ma and dry contacts to VFD's so I don't connect comm to them unless specified in the job requirements. However, Trane TR200 drive= Danfoss VLT6000 if...
  21. I've never done this, however I believe that I...

    I've never done this, however I believe that I can provide some insight...

    Yes, you will need to create BACnet points inside the BCU. This is done by going to setup>inputs/outputs>"point type...
  22. Replies
    14
    Views
    1,061

    You don't need Trane to do anything. What is the...

    You don't need Trane to do anything. What is the unit reporting back for active status, occupancy, etc.? Do they match what you're sending? Are there any field installed safties (duct detector,...
  23. Replies
    2
    Views
    452

    You are correct, MWU is only available through...

    You are correct, MWU is only available through the local HI. The Day Time Warmup points should be available through the LCI-I, but I'm not certain of the exact point names.
  24. Replies
    2
    Views
    714

    It doesn't appear that serialspy is available for...

    It doesn't appear that serialspy is available for download. The download center link was hidden, however serialspy isn't listed.
  25. Thread: Trane Rover

    by roadgear16
    Replies
    3
    Views
    707

    Summit and Rover are two different programs. ...

    Summit and Rover are two different programs. Rover is a configuration tool for unit controllers (AHU's, vav's, programmable controllers, etc.), and can be password protected separately from Tracer...
  26. Hopefully they're not using the data to actually...

    Hopefully they're not using the data to actually bill the tenant. I know I'm not paying an electric bill from the utility company unless they can prove to me that it's accurate (unless they under...
  27. Replies
    8
    Views
    654

    You can not do bindings manually between the IPAK...

    You can not do bindings manually between the IPAK and the BCU.

    I typically leave the RTU econ decision in auto unless I'm trying to coordinate multiple RTU's. Depending on the configuration from...
  28. Replies
    7
    Views
    354

    It appears that there is a TOD calendar patch. ...

    It appears that there is a TOD calendar patch. Do you have access to mytranecontrols or comfortsite? I vaguely remember this issue but never experienced it for my self. Here is a description of...
  29. Replies
    7
    Views
    354

    Man, maybe I should have looked at a calendar...

    Man, maybe I should have looked at a calendar before I posted that.

    The date is correct, but the day is off one. I've never encountered that problem. What version of Summit are you running? ...
  30. Replies
    7
    Views
    354

    I'm not exactly sure what you're asking. The...

    I'm not exactly sure what you're asking. The picture shows the schedule for "1st and 2nd floor conf/lobby" for the weekdays M-F. It appears that you have optimal events starting at 7:00am and...
  31. Replies
    4
    Views
    413

    Are you referring to a software BO/AO withing...

    Are you referring to a software BO/AO withing Tracer Summit, or a physical BO/AO on the MP581?
    Overriding a Summit point, BO/AO, will only change it's value being sent to the MP581. You'll have...
  32. If it's a reliatel just remove the RTCI board and...

    If it's a reliatel just remove the RTCI board and connect conventional T-stat connections to the RTRM. You can use your controller to control the unit. No need to completely gut the unit. If it's...
  33. Replies
    2
    Views
    475

    I found this in the archives, watch out for the...

    I found this in the archives, watch out for the spiderwebs and dust.
  34. Replies
    3
    Views
    752

    Verify that each RTU has a unique address set and...

    Verify that each RTU has a unique address set and you should be good. Granted those are the older UCP control boards which are safely 13+years old, so you may have a bad one or two. I think they...
  35. Replies
    3
    Views
    752

    The 'daughter board' can be set to Non-isolated...

    The 'daughter board' can be set to Non-isolated com3 or com4 as it is, or it can be rotated 90degrees CW and set to isolated com3. If I remember correctly the isolated com3 is not polarity sensitive...
  36. Replies
    11
    Views
    983

    The device is a solid state relay as previously...

    The device is a solid state relay as previously stated. It looks like you have an air flow or air proving switch (AFS) and a high temperature cutout (HTCO) that should break the 24v to the contactor...
  37. Replies
    2
    Views
    416

    If I'm not mistaken, the CCP3 will only...

    If I'm not mistaken, the CCP3 will only communicate with the Tracker. You can't even pull one into Tracer Summit. I'm not sure about taking it to another front end, but I'd say what you see through...
  38. Replies
    5
    Views
    783

    By older, are you referring to the UCP controls? ...

    By older, are you referring to the UCP controls? The BCI-R will work with the Voyager/Precedent units utilizing Reliatel controls, however the RTRM board has to be at or above v8 or something like...
  39. Replies
    3
    Views
    566

    I know mother Trane sent out an email not to...

    I know mother Trane sent out an email not to update to the newest Java (7 update 45 maybe?), or it would cause issues with the SC configuration UI. The high performance UI is unaffected. I'm not...
  40. Replies
    19
    Views
    1,607

    You shouldn't need Trane to do anything. There...

    You shouldn't need Trane to do anything. There is a free BACnet setup tool that you can use to change system units and baud rate. All points are available through the integration guide.
  41. What controldude said, you'll want to upgrade to...

    What controldude said, you'll want to upgrade to at least v16 summit, if not v17. The high capacity card is not necessary, just recommended when adding Lon to the BMTW. Someone (with Rover Lontalk)...
  42. Replies
    3
    Views
    760

    You can set an allowable range for the Local AV...

    You can set an allowable range for the Local AV when you setup the display. EG. you have a point named occ heat spt, when you add that point to your operator display, you have to check the box to...
  43. Replies
    11
    Views
    2,392

    If I remember correctly, unless your RTRM is v8.4...

    If I remember correctly, unless your RTRM is v8.4 or higher, the BCI-R will not use communicated unoccupied setpoints. Instead, it will revert to the default configuration setpoints in the board. I...
  44. Replies
    10
    Views
    1,777

    The property should already be referenced from...

    The property should already be referenced from the install, but their is a property called "VAS-Drive to Max" or something along those lines that needs to be referenced from the IPAK to the VAV's...
  45. Replies
    13
    Views
    1,712

    If I'm not mistaken, V17 is at SP10 update 1. It...

    If I'm not mistaken, V17 is at SP10 update 1. It is available on comfortsite. Click on tech support/software updates and tools/software service packs.

    And the service pack will encompass all...
  46. The wiring should be fine. When you put the...

    The wiring should be fine.
    When you put the chiller in BAS/EXT control and it shutdowns, what is the status of the machine? Does the setpoint change, does the occupancy mode change? Is the alerton...
  47. Not sure what the BACtalk is, but is there a BCU...

    Not sure what the BACtalk is, but is there a BCU that the Chillers communicate to? If there is a relay what controls the relay? Sounds like whoever is telling you doesn't know exactly how there...
  48. Replies
    4
    Views
    693

    http://www.douglaslightingcontrol.com/sites/defaul...

    http://www.douglaslightingcontrol.com/sites/default/files/elanswitches.pdf
    bottom of page 4 shows the snvt's. Can you not extract a xif with nodeutil or something?
  49. Replies
    5
    Views
    1,464

    Setup/Site Configuration/Devices/(select...

    Setup/Site Configuration/Devices/(select appropriate BCU if more than 1)/ assign neuron ID/select your problem UCM then select unassign, then save, repeat but assign instead of unassign. If the...
  50. Replies
    4
    Views
    594

    You should see his phone as an "event receiver"...

    You should see his phone as an "event receiver" in site configuration. When you see his phone, you can select which classes of alarms are sent to him. If you only want the critical alarms sent,...