  1. Blade hasnt slide down the shaft and not running...

    Blade hasnt slide down the shaft and not running backwards.
    piston also correct
    Amana tech wants me to change the blade and motor because he said it should be drawing closer to 1 amp and its...
  2. 26 degree but also air seems to be coming out...

    26 degree but also air seems to be coming out the top 5inches of the condenser coils and out the top
  3. possible ive either seen them good or bad I was...

    possible ive either seen them good or bad I was thinking maybe the blade got bent but it dosent seem to be??
  4. 35/5/440 dual cap

    35/5/440 dual cap
  5. dual cap 35/5/440

    dual cap 35/5/440
  6. going over when I get a motor an blade just i...

    going over when I get a motor an blade just i ncase. It seems the condenseris not rejecting the heat an the condeser is clean for the amp draw to be that low???
  7. ran fine 8 years, pumped down with micron guage....

    ran fine 8 years, pumped down with micron guage. matched amana 2.5 ton
  8. should the amp draw be half of the rla on one leg...

    should the amp draw be half of the rla on one leg I think the rla was 1.2 & .6 on one wire
  9. never been replaced but im wondering if the...

    never been replaced but im wondering if the homeowner bent the blade cleaning out the unit
  10. rotation correct . I was thinking probably...

    rotation correct . I was thinking probably running hot with those pressures popped the capacitor to start with.
  11. would it make the pressures fluctuate if the fan...

    would it make the pressures fluctuate if the fan blade was bent . because the homeowner vacumed out the leaves he said and I was thinking maybe its not rejecting the heat but I dont know if that...
  12. 64oz and the lineset was @20ft

    64oz and the lineset was @20ft
  13. new 22 I charged by weight and pressure the same...

    new 22 I charged by weight and pressure the same as the first day I was there 85suc 350liq both fluctuating @70/85 315/350
  14. ive already put new 22 in but my pressures...

    ive already put new 22 in but my pressures continue to fluctuate like theres non condesables. not sur what else would cause this
  15. changed filter drier and weigh charge in still...

    changed filter drier and weigh charge in still same problem any ideas?
  16. ga1279 Im going to change the drier out and yes...

    ga1279 Im going to change the drier out and yes my pressures were moving around alot which intern was changing my temp. reading as they moved around so did my temps

    Thanks alot i really...
  17. Im going to and already should have Thanks so...

    Im going to and already should have Thanks so much ill let you know how it goes
  18. I just checked the tempature across not sure...

    I just checked the tempature across not sure aboout the psi unless you have a port there to check it
  19. when i got there i didnt add any refrigerant It...

    when i got there i didnt add any refrigerant It was running at 85/350 then i cleaned condenser and no difference. Although both pressures and line temps were fluctuating.
    My superheat and subcooling...
  20. Anyone know a list of things that would cause the...

    Anyone know a list of things that would cause the fluctuating of pressures and temps
    I thought non condesables,air, moisture
    condenser recirculation?
    condenser fan not functioning 100% (how to...
  21. What about the pressures fluctuating? the...

    What about the pressures fluctuating?
    the pressures both are going up and down along with my line temps ?
  22. a/c problem everythings running but need help

    Call started off a bad compacitor then i noticed they hadnt changed there spacegaurd for a while. Got unit up and runnning and told them to leave off till i got filter next day. Replaced filter unit...
  23. New install I just had one i couldnt get any SH,...

    New install I just had one i couldnt get any SH, subcooling was within range. I really didnt want to change the txv so i tried the charge/airflow/ and my txv would even throttle refrigerant when i...
  24. Replies
    11
    Views
    938

    Ok thanks, Is there any ways for me to obtain pro...

    Ok thanks, Is there any ways for me to obtain pro status or do i have to post alot of threads?
  25. Sticky: how i got into hvac

    Well my whole life i loved working on things and was always good with tools.
    Ive always been a hard worker and had a job since i was 12 yo. Well needless to say i never made a whole lot of money...
  26. Replies
    11
    Views
    938

    Didnt want to bother you but again just wondering...

    Didnt want to bother you but again just wondering how to PM you on here or If you would have any time whenever you get a chance to ask a few questions maybe via email. Just would really like some...
  27. Replies
    11
    Views
    938

    hvaclover

    Hey hvaclover i really appreciate your help, how did your icp txv changeout go. I ended up changing the whole coil out under warranty

    I couldnt figure out how to PM you...
  28. Replies
    11
    Views
    938

    txv cured my problems everything is working...

    txv cured my problems everything is working great. I really appreciate everyone helping out. Its nice to be able to get some advice from some pros. Thanks alot
  29. Installed new txv today, amazing i now have...

    Installed new txv today, amazing i now have superheat... Thanks everyone for all your help
  30. Thanks for the input. Wouldnt i still have...

    Thanks for the input. Wouldnt i still have superheat regardless if its over or undercharged unless the txv is bad? also the subcooling was normal.
    (non adjustable txv)
  31. Thanks again for everyones help I will find out...

    Thanks again for everyones help I will find out today and let everyone know
  32. Anything that would cause that ? Another guy...

    Anything that would cause that ? Another guy just told me he knows of 10 others D.O.A on. new install bad txv
  33. Replies
    11
    Views
    938

    Well you just made my day its been driving me...

    Well you just made my day its been driving me nuts having to go back on my own job. it sucks for all of us. Any tips to speed up the process? I think you cant pump down the scroll. An the evac takes...
  34. Replies
    11
    Views
    938

    subcooling was 12 but the unit is stamped for 10...

    subcooling was 12 but the unit is stamped for 10 degree subcool
    I was leaning on something wrong with the txv?
    Could be slightly overcharged but i think i would still have superheat
    Ive never...
  35. Replies
    12
    Views
    1,228

    I was always told not to pump down the scrolls. ...

    I was always told not to pump down the scrolls. I usually pump it down some and recover the rest
  36. Replies
    230
    Views
    49,741

    Sticky: Poll: (ICP) Arcoaire for moderate pricing Goodman on...

    (ICP) Arcoaire for moderate pricing
    Goodman on the cheaper side but getting away from Goodman
    Id like to get into some more expensive brands when people get more money to pay me
  37. Replies
    11
    Views
    938

    Coil condenser match??? Arcoaire

    arcoaire model# N4A330AKC200 condenser
    # END4X36T17A2 coil
    I either burned the txv i heat sinked around my fittings or this is not a match, I have no...
  38. Replies
    9
    Views
    1,538

    I usually leave something open or loosen up the...

    I usually leave something open or loosen up the valve stem so you dont get the pin holes on your last joints, Also you have to leave the regulator set at 50psi or less, Ive been told it can mess up...
  39. Thanks everyone for all the help I really...

    Thanks everyone for all the help I really appreciate it , IM going to make sure the coil/txv is really a match on monday. Id feel better if it was there fault instead of mine..
    If anyone knows my...
  40. Everything is all new and the same brand. I...

    Everything is all new and the same brand.
    I never trust the counter guy either i hope all the equipment is correct
    Ill find out Monday. Im just not sure any other reasons i wouldnt have any...
  41. Yes Gas furnace

    Yes Gas furnace
  42. The evap is a 3 ton and the unit is 2.5 ton. ...

    The evap is a 3 ton and the unit is 2.5 ton.
    Supply house said its fine and from my knowledge a 1/2 ton larger coil will just remove more humidity due to a larger surface area, the txv is supposed...
  43. Thanks alot I think that would be a good idea,...

    Thanks alot I think that would be a good idea, somthings not rite
  44. lo pressure 143 47 line temp -3 superheat hi...

    lo pressure 143 47 line temp -3 superheat
    hi pressure 381 102 line temp 12 subcooling
    these were the last measurements i took
    sorry for the confusion
    Thanks alot
  45. Shouldnt my superheat still be higher even if its...

    Shouldnt my superheat still be higher even if its overcharged?
    Thanks alot
  46. sp-143 50degree F at condenser (410a...

    sp-143 50degree F at condenser (410a refrigerant)New install
    lp-381 115 degree F at condenser
    IWB -? dont have now
    IDB-70
    ODB-85 inlet condenser air/ 98 exiting condenser (93 in...
  47. I just checked my notes on the job the unit is...

    I just checked my notes on the job the unit is requiring 12 degrees of subcooling and i had 10. Could it be slightly overcharged?
  48. Thanks SIX I thought overheating the bulb would...

    Thanks SIX I thought overheating the bulb would close off the txv??
  49. The txv was factory installed and insulated I...

    The txv was factory installed and insulated I did use heat sink around the connection, maybe not enough
  50. Thanks alot for all the help.... 12 degree...

    Thanks alot for all the help.... 12 degree subcooling and 0 on the superheat both measured at the condenser. everything else seems fine and its cooling well, I should have disconnected the bulb...
Results 1 to 50 of 57